Search:

Type: Posts; User: shylock

Page 1 of 4 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    13
    Views
    1,182

    I'm sorry, I don't know much about Apogee. ...

    I'm sorry, I don't know much about Apogee.

    Anyway, if you would like to add new chiller with existing BACnet controller inside, I don't understand, why you need to build an application and load it...
  2. Replies
    13
    Views
    1,182

    First, which Siemens system are you working with?...

    First, which Siemens system are you working with? There are two current systems (Desigo and Apogee) and at least half a dozen legacy ones.

    Second, why do you think you need all those tools to...
  3. Replies
    15
    Views
    3,639

    I e-mailed you

    I e-mailed you
  4. Replies
    15
    Views
    3,639

    USB key and v2.6. I think it was ENV-BT-2.6-MED

    USB key and v2.6.

    I think it was ENV-BT-2.6-MED
  5. Replies
    15
    Views
    3,639

    Similar story here: a client lost his Windows...

    Similar story here: a client lost his Windows with Envision installation. All screen files, database backup and USB dongle are available, but no Envision installation. Anyone would be so kind to...
  6. Replies
    8
    Views
    5,555

    Probably you meant "bytes" -- two bits of data...

    Probably you meant "bytes" -- two bits of data from a meter does not make much sense :)
  7. Replies
    8
    Views
    5,555

    Modbus is limited to 32 "unit loads". Most of the...

    Modbus is limited to 32 "unit loads". Most of the devices nowadays are 1/4 unit load, therefore there could be 128 devices per line.
  8. Replies
    8
    Views
    5,555

    The biggest M-bus advantage is that one could...

    The biggest M-bus advantage is that one could power M-bus devices from the communication line. So 2 wires are enough for everything.
    Modbus is much more popular and more simple. It could be much...
  9. Prices are "low", dictionaries are "cheap". Buy...

    Prices are "low", dictionaries are "cheap". Buy one.
  10. Just FYI: there are two completely different...

    Just FYI: there are two completely different third party C-bus drivers for Tridium available: from Infocon and Neopsis.
    Can't tell you much about their stability, but maybe it's worth to try.
  11. Replies
    21
    Views
    2,242

    When replacing 301 you should be aware, that...

    When replacing 301 you should be aware, that usually they read temperature from very specific 1.8K thermistors -- no other vendor uses them.
  12. Replies
    57
    Views
    4,175

    I say you go both ways. Choose one line (e.g....

    I say you go both ways. Choose one line (e.g. BACnet :)) as a main one. But if the client requests LON you could put an almost identical (electrically and programmatically) controller instead.
    And...
  13. Replies
    57
    Views
    4,175

    No, no, no! You just destroyed any reasonable...

    No, no, no! You just destroyed any reasonable discussion here.
  14. Replies
    57
    Views
    4,175

    Thumbs up for Distech. They have very similar LON...

    Thumbs up for Distech. They have very similar LON and BACnet lines with free (nice and powerful) programming software.
    But you really have to use Niagara (Distech calls it EC-NET AX) to fully...
  15. Thread: MSTP vs FT10

    by shylock
    Replies
    112
    Views
    6,535

    I see a little value in "LNS for BACnet", because...

    I see a little value in "LNS for BACnet", because of the way how inter-controller communication is handled in BACnet. I'll try to explain how I see it.

    LON has a unique separate "binding"...
  16. Replies
    7
    Views
    1,433

    Johnson will not licence you their N2 driver for...

    Johnson will not licence you their N2 driver for Honeywell Jaces, but there is other N2 driver (Infocon) which you could use.

    There are many drivers available, here is a list:...
  17. Cloud Marketing 101: Post a lot of unrelated...

    Cloud Marketing 101: Post a lot of unrelated links and invent nicknames for opponents (civility is for losers!). That will make your product a huge success!
    :bump:
  18. Cloud Marketing Pro. Calling names and trying to...

    Cloud Marketing Pro. Calling names and trying to prove his point with completely unrelated material (the subject is not even mentioned there!) :LOL:
    Are there some courses or is it innate ability?
  19. That's an interesting idea. Take a popular and...

    That's an interesting idea. Take a popular and poorly understood term, add something to it, and declare it applies to your product. Protect the concept by aggressively insulting anyone who doubts it....
  20. Thread: Tridium Niagra

    by shylock
    Replies
    8
    Views
    2,128

    AX certification course is quite good. Also...

    AX certification course is quite good. Also Tridium has advanced course (2 days), which you could take after certification.
    And then there is a developer course, but it is for Java programmers.
  21. Replies
    14
    Views
    2,830

    I use Aspmon...

    I use Aspmon a lot with different serial protocols. There is a Modbus plugin and even a scripting language.
    It is not free, but it worth it.
  22. Thread: Tridium Sedona

    by shylock
    Replies
    149
    Views
    18,264

    I have mentioned 3 types of IEC61131 controllers...

    I have mentioned 3 types of IEC61131 controllers (sysint talked about both IEC61131 and IEC61499).
    All these controllers are from industrial automation: Siemens Simatic, Beckhoff, Wago.
  23. Thread: Tridium Sedona

    by shylock
    Replies
    149
    Views
    18,264

    No, because of "different needs". I could...

    No, because of "different needs". I could describe these needs, but don't think you really wanna know.
    But I'll give you a hint: Profibus, DeviceNet and Canbus protocols are respected and...
  24. Thread: Tridium Sedona

    by shylock
    Replies
    149
    Views
    18,264

    These standards cover quite different needs...

    These standards cover quite different needs compared to Sedona. Plus there is a very limited acceptance of IEC61311 and IEC61499 in BMS industry.



    Of course, Sedona is just starting. AFAIK...
  25. Thread: Tridium Sedona

    by shylock
    Replies
    149
    Views
    18,264

    IEC61131 and IEC61499 do not specify low level...

    IEC61131 and IEC61499 do not specify low level code formats, programming interfaces etc. There is a very limited scope of compatible tools / vendors.
  26. In this case you already have some devices to...

    In this case you already have some devices to redirect your IR remote to central, one more device to choose one of many music sources to play, one more device to transmit this source to a particular...
  27. Crestron, AMX, Control4 play in a very different...

    Crestron, AMX, Control4 play in a very different and large market, audio/video mostly. Ipad will make them reduce prices for their panels, but it is not a real threat. Ipad can't speak to TV,...
  28. Replies
    13
    Views
    1,018

    www.gmx.com does not require SSL.

    www.gmx.com does not require SSL.
  29. Replies
    6
    Views
    574

    Thank you, that's what I needed! Site Book...

    Thank you, that's what I needed!

    Site Book gave me some errors in the beginning. But after all other M3 processes has been stopped, it uploaded all new points successfully.
  30. Replies
    6
    Views
    574

    It could be Site Book or Project Builder. If I...

    It could be Site Book or Project Builder.
    If I understand correctly, Site Book is used to establish communication between M3 and N30. Looks like it is not necessary in my case.
    Project Builder is...
  31. Replies
    6
    Views
    574

    This is exactly what I did. Copy/paste existing...

    This is exactly what I did. Copy/paste existing point, then selected "Edit Aliases" - there was Alias Definition "JC.BNOPC.2\@BMS:N30:AHU1-PE02". BMS is a site name, N30 - name of N30, AHU1-PE02 -...
  32. Replies
    6
    Views
    574

    Add new point to Johnson M3 Graphics

    The system structure is DX9100 => N30 => M3 Workstation.
    I have to add some new points from DX9100 to M3 graphical screen.

    So I have connected to N30 with hyperterm (JCI calls it "VT100 Terminal...
  33. Replies
    5
    Views
    653

    I'm not sure, but I think Care could be...

    I'm not sure, but I think Care could be downloaded and used offline without license.
  34. Replies
    4
    Views
    923

    Please, search the forum and read about 10000...

    Please, search the forum and read about 10000 posts.

    P.S. And please don't ask "Which is better, LON or BACnet" :)
  35. Replies
    25
    Views
    2,516

    European Tridium sells it, so the configuration...

    European Tridium sells it, so the configuration tool must be open for other brands.
  36. Please be so kind and e-mail it. If nobody...

    Please be so kind and e-mail it.


    If nobody publishes their source, then nobody in building controls industry is "completely open".
    BTW there are many open source players in IT world.
  37. Probably Java will stay as embedded and server...

    Probably Java will stay as embedded and server platform. But on client side Java sucks. Flash/Flex, Silverlight and, even better, HTML5 is the way to go.


    Not completely. It is not open source...
  38. Thread: AX Wizards

    by shylock
    Replies
    18
    Views
    1,766

    Distech should announce their new ECN (N2...

    Distech should announce their new ECN (N2 protocol!) controllers quite soon. After that LON and BACnet series will be obsolete. Who needs them anyway, N2 is superior.
  39. Thread: Distech

    by shylock
    Replies
    19
    Views
    2,690

    The compiler is provided by Distech (actually it...

    The compiler is provided by Distech (actually it is very similar to the one for Lon controllers). It is integrated into Niagara using additional Distech's module.


    I'm sorry, but it is not like...
  40. Thread: Distech

    by shylock
    Replies
    19
    Views
    2,690

    No, ECB controllers are fully Distech's, there is...

    No, ECB controllers are fully Distech's, there is no Niagara code inside them. Niagara is used the same way LonMaker is used in LON world.
  41. Thread: Distech

    by shylock
    Replies
    19
    Views
    2,690

    Distech sells OEMed Tridium Jaces as many others...

    Distech sells OEMed Tridium Jaces as many others do. But unlike others Distech also customizes Jaces heavily, including new graphics and a very good programming tool for ECP and ECB series of...
  42. Replies
    12
    Views
    2,319

    There are two third-party C-bus drivers for AX...

    There are two third-party C-bus drivers for AX already: Infocon and Neopsis.
  43. Replies
    14
    Views
    1,730

    My 5 cents: Remote programming and debugging...

    My 5 cents:

    Remote programming and debugging
    Autorouting of connection lines (I just hate to draw these lines manually. Hope the guys from TAC will look at Distech tool)
  44. Replies
    14
    Views
    5,011

    Really? SO long ago? :)

    Really? SO long ago? :)
  45. Replies
    12
    Views
    5,490

    All I have is a list on their website:...

    All I have is a list on their website: http://www.easyio-solution.com/infocon-solutions-driver-list. Try to contact them directly.
    Looks like there are more drivers now:

    Infocon
    Robertshaw...
  46. Replies
    12
    Views
    5,490

    Well, I could start. The information below it...

    Well, I could start. The information below it taken from Tridium, niagara-central.com and third-party websites. Or maybe I have heard it somewhere.

    Tridium
    American Automatrics PHP
    American...
  47. Replies
    9
    Views
    2,129

    It's AAM, not AL :)

    It's AAM, not AL :)
  48. Replies
    119
    Views
    17,558

    Looks like these guys have it also:...

    Looks like these guys have it also: http://www.ccontrols.com/basautomation/basremote.htm
  49. Thread: Jace graphics

    by shylock
    Replies
    10
    Views
    1,217

    Not necessary. You could create many point...

    Not necessary. You could create many point folders in one big controller (like VAV1, VAV2, FC1, FC2 etc) then create points with identical names in each folder (nviSetpt, nvoFan, nvoValve). Then you...
  50. Thread: Jace graphics

    by shylock
    Replies
    10
    Views
    1,217

    When I tried FX, I've got an impression that JCI...

    When I tried FX, I've got an impression that JCI added some appliance-like functionality of no real value. The only thing which may be necessary is N2 protocol.