  1. Thread: rtaa chiller

    by Tranetek
    Replies
    20
    Views
    2,246

    Have you ran a diode check. Unplug the ct's from...

    Have you ran a diode check. Unplug the ct's from the board, put your meter on diode check, should be 1.5 volts or close between the pens for each ct. If not replace the module.
  2. Replies
    7
    Views
    1,112

    circuit reset is in the p1 menu

    circuit reset is in the p1 menu
  3. Replies
    17
    Views
    3,610

    Some of you don't need to be working in this...

    Some of you don't need to be working in this field from what I can tell
  4. Replies
    7
    Views
    1,919

    You can use a Trane TOL101 to check out a w7900....

    You can use a Trane TOL101 to check out a w7900. Comes with all connections and instructions for checking it out
  5. Replies
    10
    Views
    1,815

    I didn't know there was a York that wasn't loud.

    I didn't know there was a York that wasn't loud.
  6. Replies
    63
    Views
    9,154

    Originally Posted by jt8350 forgot to mention...

    Originally Posted by jt8350
    forgot to mention that fan cycling controls. was the suggestion of a trane tech from the local trane office.

    He wouldn't be a tech at my office making suggestions...
  7. Replies
    63
    Views
    9,154

    People do this stupid crap because they don't...

    People do this stupid crap because they don't know what they are doing and how the machine works. Learn now the machine operates and then figure out what the real problem is. Don't just put...
  8. Thread: make up air

    by Tranetek
    Replies
    14
    Views
    1,699

    One of the first things I would do is drop the...

    One of the first things I would do is drop the chilled water temp. 52 isn't going to dehumidify much of anything.
  9. Replies
    5
    Views
    1,064

    Find the correct service lit. and run a diode test

    Find the correct service lit. and run a diode test
  10. Thread: Oil Pressure

    by Tranetek
    Replies
    6
    Views
    600

    Differential pressure switch should trip at 50...

    Differential pressure switch should trip at 50 psid
  11. Replies
    40
    Views
    4,228

    Actually Trane does have a water cooled scroll...

    Actually Trane does have a water cooled scroll unit. CGW* My question is, if you are having so much trouble with load swing on the chiller why not put in a storage tank and have it pump to the...
  12. Replies
    6
    Views
    865

    Check sat evap and suction temp sensors to make...

    Check sat evap and suction temp sensors to make sure they are correct. You also need to check them to ground. If there is any reading to ground they should be changed. A grounded sensor can look to...
  13. Thread: CVHF surging

    by Tranetek
    Replies
    39
    Views
    4,742

    It is usually one of three things. Air,...

    It is usually one of three things. Air, condenser water to hot or fouled tubes. Condenser approach should be no more then 3 degrees at full load. Have you checked to see if your purge is actually...
  14. Replies
    3
    Views
    1,067

    Sounds like it is rotating backwards for just a...

    Sounds like it is rotating backwards for just a little until the check valve closes. The thud you are hearing sounds like the check valve closing.