Search:

Type: Posts; User: RoadRunner

Page 1 of 3 1 2 3

Search: Search took 0.00 seconds.

  1. Replies
    5
    Views
    931

    Yes there is a base setup (Macro). If this drive...

    Yes there is a base setup (Macro). If this drive is on a pump or ahu, I would bet the farm that it is set for the HVAC macro. If so, unless someone has altered some of the parameters, it will auto...
  2. Replies
    3
    Views
    455

    w~p You will have to call johnson controls for...

    w~p

    You will have to call johnson controls for the part number on this. They havent sold these Obsys dongles in quite a while and barely still support it. They are available however through the...
  3. Replies
    3
    Views
    455

    Hardlock? Are you talking about the dongle for...

    Hardlock? Are you talking about the dongle for York ISN Facility Manager?
  4. Replies
    5
    Views
    774

    That setup and wiring should work. Make sure JP56...

    That setup and wiring should work. Make sure JP56 on the Micro is set to EMS and not modem. JP58 on the Micro needs to be set to 485 and not 232 as well. Set the chiller rotary ID switch on the...
  5. Replies
    5
    Views
    774

    Is this an OptiView or a one line panel? What...

    Is this an OptiView or a one line panel? What port are you coming off the ELink to the chiller? What port and terminal's did you land to on the MicroBoard from the Elink? What port is the 3rd party...
  6. You have mail.

    You have mail.
  7. Is it a MicroGateway or an E-Link? Does the CCN...

    Is it a MicroGateway or an E-Link?
    Does the CCN talk directly to the MicroGateway/E-Link?
    If it is a MicroGateway, what is the last 3 digits in the eeprom part number?
  8. Replies
    22
    Views
    1,652

    .

    .
  9. Replies
    22
    Views
    1,652

    .

    .
  10. Replies
    22
    Views
    1,652

    The York interface you speak of will either be a...

    The York interface you speak of will either be a MicroGateway or the new version called an E-Link. Both have a QuickStart setup that has to be perfomed and then should start talking to your third...
  11. Replies
    5
    Views
    1,720

    TomT, The Pathfinder is merely a router...Just...

    TomT,

    The Pathfinder is merely a router...Just part of what I would guess, is a large network, given the fact a Pathfinder is even being used. It has no logic what so ever. How many nodes or...
  12. Replies
    5
    Views
    1,720

    I may be able to help you...you need info on the...

    I may be able to help you...you need info on the Pathfinder or ISN?

    Bill
  13. Replies
    15
    Views
    1,584

    Use nothing but 567 here...

    Use nothing but 567 here...
  14. Replies
    5
    Views
    3,020

    You have mail. Bill

    You have mail.

    Bill
  15. Replies
    5
    Views
    3,020

    Whats you e-mail and model number of the screw...

    Whats you e-mail and model number of the screw chiller?

    Bill
  16. Replies
    2
    Views
    936

    Mod, Lon and Bacnet protocol's are availible and...

    Mod, Lon and Bacnet protocol's are availible and are all viable options. Ascii, ISN and N2 are availible as well. Depends on what protocol your Honeywell system talks or can talk. They all send and...
  17. Replies
    2
    Views
    648

    Your best bet is to drill through the hub and...

    Your best bet is to drill through the hub and each blade where they come into the hub and put a stainless steel screw through it. I have done a bunch of these and it works fine. About a 3/16th inch...
  18. Replies
    26
    Views
    2,615

    They closed the factory store???

    They closed the factory store???
  19. Replies
    23
    Views
    2,137

    Reset the VSD?....did it, or does it have a fault...

    Reset the VSD?....did it, or does it have a fault now? What type of fault needs to be reset?
  20. Replies
    3
    Views
    1,052

    Baker Distributing (Baker Bros.) is the product...

    Baker Distributing (Baker Bros.) is the product and parts dealer here in Florida. Hope this helped!

    http://www.bakerdist.com/products/line_card_1.asp
  21. Replies
    208
    Views
    28,677

    Streetsmart, where did you hear that? I would...

    Streetsmart, where did you hear that? I would have thought that number would have been higher actually.


    Flange, what area do you work in?



    [Edited by RoadRunner on 10-09-2006 at 06:06 PM]
  22. Replies
    20
    Views
    2,168

    Is this the same design you told me about when we...

    Is this the same design you told me about when we were working together at that plant in south Georgia?
  23. Thread: Low Suction

    by RoadRunner
    Replies
    16
    Views
    2,256

    What kind of amps do you have? Actual compared to...

    What kind of amps do you have? Actual compared to rated. I agree with 3rdgenhvac. Sounds like it may be busted valves in the compressor.

    just my 2 cents..




    [Edited by RoadRunner on...
  24. Replies
    18
    Views
    1,758

    One in my area here, and a couple more north of...

    One in my area here, and a couple more north of me that RichardL maintains. Works really good. Chiller and engine both. There practical and reliable if thats what the facility needs or wants. However...
  25. Replies
    11
    Views
    1,004

    Form

    Call your local York Factory office then and ask them to order it for you. Order the form number from the previous post. I assure you this is valid and the correct form you need. What part of the...
Results 1 to 25 of 52