Search:

Type: Posts; User: forservice

Search: Search took 0.01 seconds.

  1. Replies
    4
    Views
    1,916

    I have not returned to site to implement your...

    I have not returned to site to implement your suggestions. I hope to return on Monday. I will post results. The site has remote access but do not have the number.

    Thank each of you for your...
  2. Replies
    4
    Views
    1,916

    Trane MP581 mother board replacement.

    After replacing a failed MP581 mother board and reconfiguring the MP581 with Rover the BCU recognizes the new neutron as a SCC Generic device and not as a MP581. (Rover reports the device profile as...
  3. Replies
    6
    Views
    825

    RTHB - Momentary Power Loss - Resolved.

    Problem resolved. Found that 2T2 transformer had also been replaced. OEM replacement was not marked as to phasing - swapped leads and no more shutdowns. Thanks for your input guys.
  4. Replies
    6
    Views
    825

    I have been ask to resolve a Momentary Power Loss...

    I have been ask to resolve a Momentary Power Loss issue with a RTHB Chiller with a WYE starter. This condition accurs just after transition. Previous techs have replaced auxillary contacts, one CT...