Search:
Type: Posts; User: Chiller Tex
Search: Search took 0.01 seconds.
-
03-23-2011, 12:49 PM
Thread: CVHE wont transition
by Chiller Tex- Replies
- 3
- Views
- 577
D1 & D2 contacts are the "transition signal". It...
D1 & D2 contacts are the "transition signal". It is a relay built in the circuit board. Those contacts are on line 36 on the schemattic from the CVHE service guide page 7.14-4. The n.o. contacts...
-
03-23-2011, 11:14 AM
Thread: CVHE wont transition
by Chiller Tex- Replies
- 3
- Views
- 577
CVHE wont transition
I have a CVHE-071 that wont transition the starter. I trouble shot the starter and found the D1 & D2 contacts not closing to send it in the delta mode. This is an '84 model machine. The contacts that...
-
03-23-2010, 07:14 AM
Thread: 19DH guide vane rebuild
by Chiller Tex- Replies
- 12
- Views
- 800
I updated my info. If you found something on the...
I updated my info. If you found something on the IGV please send it. I like to have that in my library.
-
03-23-2010, 07:09 AM
Thread: 19DH guide vane rebuild
by Chiller Tex- Replies
- 12
- Views
- 800
Yall where right about Carrier Houston rebuild...
Yall where right about Carrier Houston rebuild shop. They had the exact IGV rebuilt and ready to go. Thanks for the input. That saved me the headach.
-
03-21-2010, 12:03 PM
Thread: 19DH guide vane rebuild
by Chiller Tex- Replies
- 12
- Views
- 800
19DH guide vane rebuild
Does anybody know what the service guide catalog # is from carrier that explains how to disasemble and reasemble the guide vane section? also does anybody have any pointers on rebuilding the guide...
-
02-25-2009, 06:43 AM
Thread: 19xr pic lll won't clear fault
by Chiller Tex- Replies
- 2
- Views
- 315
What soft key? Just kidding, yes l hit it. I went...
What soft key? Just kidding, yes l hit it. I went back to job site and disconnected the evap refrig sensor from micro. when l wired sensor back in the micro reset. I not sure why, but everything...
-
02-23-2009, 11:23 PM
Thread: 19xr pic lll won't clear fault
by Chiller Tex- Replies
- 2
- Views
- 315
19xr pic lll won't clear fault
I have a 19xr pic lll that won't reset. It went off on low evap temp. The evap sensors were reading 31.4 [actual was 48 ] & the cond read 45 [actual was 62 ]. I somehow got the sensors to read...
-
02-18-2009, 11:30 PM
Thread: 19xr comp o-rings & gaskets
by Chiller Tex- Replies
- 13
- Views
- 777
Thanks guys for the input. This is a cool website.
Thanks guys for the input. This is a cool website.
-
02-18-2009, 12:35 AM
Thread: RTAA fault
by Chiller Tex- Replies
- 44
- Views
- 4,278
Everyone has good suggestions. Also check the oil...
Everyone has good suggestions. Also check the oil level and the oil switch calibration. A quick way to check oil switch. Turn ckt off, leave the low port hooked up to oil line. Take the high port off...
-
02-17-2009, 11:53 PM
Thread: carrier xl19 no amps sensed fault
by Chiller Tex- Replies
- 2
- Views
- 426
Call Benshaw. Have the m#, s# of SSS panle and...
Call Benshaw. Have the m#, s# of SSS panle and chiller. Ask for tech help. They will walk you throu it.
-
02-17-2009, 11:29 PM
Thread: YORK YK SHUTDOWN
by Chiller Tex- Replies
- 28
- Views
- 1,506
It doesn't hurt the chiller to shut off when...
It doesn't hurt the chiller to shut off when loaded. It's not the best way, but no big deal. Think of it as when the power goes out. It stops.
-
02-17-2009, 10:49 PM
Thread: 19xr comp o-rings & gaskets
by Chiller Tex- Replies
- 13
- Views
- 777
19xr comp o-rings & gaskets
what do you use on the o-rings & gaskets? 515?
Results 1 to 12 of 56