    If these are new controllers I would agree you...

    If these are new controllers I would agree you need v6.0. It would be a good idea to load the August Cumulative Patches into FieldAssistant before you upload. They have made driver changes since the...
  2. Replies
    1
    Views
    132

    Do you have the recent patches installed? The...

    Do you have the recent patches installed? The cumulative patch releases for i-Vu also need to be applied to Field Assistant, which will also patch Snap & Equipment Builder if installed.

    Start...
  3. Not sure if it is wise to remove the CCN...

    Not sure if it is wise to remove the CCN ComfortLink Controls and replace with another controller.

    Carrier sells an Open UPC that will convert the CCN controls to BACnet MS/TP. Not sure if you can...
  4. Version 6 and down is accessed with...

    Version 6 and down is accessed with Hyper-Terminal. Version 10 and up is accessed with Trane's Tracker software.
  5. Replies
    6
    Views
    424

    You can find older versions here .......

    You can find older versions here .... http://www.oracle.com/technetwork/java/javase/downloads/java-archive-downloads-javase7-521261.html

    There are version all the way back to v7u1 on this page,...
  6. Thread: Trane VSEE vav

    by Balibe
    Replies
    5
    Views
    265

    +1 .... don't reuse the existing assembly. We...

    +1 .... don't reuse the existing assembly.

    We retrofit a lot of these, they are very common in my area. We are in the process of doing two floors with 60 of these per floor.

    We pull the...
  7. Replies
    3
    Views
    236

    +1 Rover will not configure a BCU. You will...

    +1

    Rover will not configure a BCU. You will not be able to access the BCU with a display by just adding one. They are configured, setup and downloaded to a BCU with Summit.
  8. Replies
    20
    Views
    716

    Check the updates they gave you, the USB...

    Check the updates they gave you, the USB communications update is a driver not included in cumulative update released in August. The driver file should have been “drv_ivuexp_6-00a-023.driver” which...
  9. Replies
    20
    Views
    716

    What version? If v6.0 Standard with the USB...

    What version? If v6.0 Standard with the USB adapter, there is a new driver released in March that resolves communications issues. Controls Bulletin #IOB14003A references the update.
  10. It is a 26.8mb zipped file, if you have access it...

    It is a 26.8mb zipped file, if you have access it is downloadable from hvacpartners.com.
  11. Replies
    1
    Views
    142

    You have mail .......

    You have mail .......
  12. Replies
    4
    Views
    292

    With CCN you broadcast, with Open you will need...

    With CCN you broadcast, with Open you will need to read. Open will broadcast when a Linkage is setup.

    You want System Outdoor Air Temperature, which is found under Properties\Network Points....
  13. Replies
    32
    Views
    1,361

    Your FXWorkbench should be licensed for...

    Your FXWorkbench should be licensed for everything [all drivers/protocols]. I have never had an issue hooking up directly to lon networks with FXWorkbench and a USB Lon adapter.
  14. Replies
    35
    Views
    2,746

    +1 Getting old seeing this guy resurrecting...

    +1

    Getting old seeing this guy resurrecting all these threads that are over a year old .... each with a PDF attachment??
  15. Thread: Orion Controls

    by Balibe
    Replies
    1
    Views
    232

    http://orioncontrols.wattmaster.com/literature-new...

    http://orioncontrols.wattmaster.com/literature-new.html
  16. Replies
    7
    Views
    332

    Johnson Controls also has a wireless system that...

    Johnson Controls also has a wireless system that works well.
  17. I have one jobsite with this same issue, works...

    I have one jobsite with this same issue, works fine on my Verizon hot spot and all hardwired connections but will not connect with the customers AT&T hot spot. I always thought the issue was with...
  18. Replies
    10
    Views
    491

    I did some research with a v4.2 and v6.0. I will...

    I did some research with a v4.2 and v6.0. I will try to make this easy to understand, but there is no formula/logic (decoder ring) that will easily get you the info you want. You will need to have...
  19. Replies
    10
    Views
    491

    So you are looking at the points on the IP side...

    So you are looking at the points on the IP side of the Router and trying to figure out which VAV the BACnet points are assigned to?

    If so I can look at one of my sites on the IP side to see if...
  20. Replies
    10
    Views
    491

    You wil not see the address under network points...

    You wil not see the address under network points with a factory control program. All point address's under the network points tab will be ccn:\\link\point_info, the "link" can be changed to the...
  21. Replies
    3
    Views
    327

    Snap has a programming block for lead/lag under...

    Snap has a programming block for lead/lag under Misc\Proof. It does rotation based on runtime and failsafe if the lead does not proof. It will also generate fail & hand alarms if needed. If you have...
  22. Replies
    6
    Views
    321

    The 4th digit of the model number is the...

    The 4th digit of the model number is the Development Sequence. F = Sixth & G = Seventh. The breakdown is in one of the PDF's I emailed you.
  23. Replies
    6
    Views
    321

    Model Number: SXHFC6040M56C79D6001BELRT8PK Job...

    Model Number: SXHFC6040M56C79D6001BELRT8PK
    Job Name: Concord Park
    Shipped: 10-16-1997

    The original model number breakdown does not show an LCI. The unit documents only go back so far. I found...
  24. Replies
    6
    Views
    321

    From my understanding is the older panels do not...

    From my understanding is the older panels do not support the LCI. I don't know when the change occurs. Not 100% but think you can replace the panel with a newer version that works with an LCI. That...
  25. Replies
    11
    Views
    666

    When you right click the VAV graphic and edit...

    When you right click the VAV graphic and edit UCM, you are in the UCM. You can use Summit to modify the settings. They are live settings in the UCM versus a local saved database.