Search:

Type: Posts; User: El Presidente

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Replies
    9
    Views
    271

    Same way. Monitor space temp and override units...

    Same way. Monitor space temp and override units on when setback setpoints are reached. Back off after a set differential.
  2. Replies
    9
    Views
    271

    If it uses Java then it is the old gateway. Here...

    If it uses Java then it is the old gateway. Here is the IOM:

    https://www.dropbox.com/s/fr2gccnt2jqvd4f/MFL37115823_LG%20BACnet%20Old.pdf

    Are you sure the IDUs have been discovered by the...
  3. Replies
    157
    Views
    27,208

    Ok let's see if this works. This version is three...

    Ok let's see if this works. This version is three years old so not sure if it is even current anymore. If anyone has a more current version, send it to my email and I'll setup a new link.
    ...
  4. Replies
    157
    Views
    27,208

    August posters, check your mail. Anyone else, let...

    August posters, check your mail. Anyone else, let me know.

    Pres
  5. Replies
    157
    Views
    27,208

    Version I have is 6.201. Not sure if that is even...

    Version I have is 6.201. Not sure if that is even current anymore. Haven't used it since 2011. Who wants it?!

    Pres
  6. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    1,229

    You're welcome! Let me know if you need anything...

    You're welcome! Let me know if you need anything else.

    Pres
  7. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    1,229

    They work. I would take the BACnet over Lon. More...

    They work. I would take the BACnet over Lon. More functionality, more capacity, and less issues. They are both monitoring and control. You can see the points lists here:
    ...
  8. Thread: LG V-net

    by El Presidente
    Replies
    20
    Views
    1,229

    What do you want to know?

    What do you want to know?
  9. Replies
    6
    Views
    531

    You should see just a bunch of points. The number...

    You should see just a bunch of points. The number after the object name corresponds with the address in the stat. For example StartStopCommand_000 corresponds with group address 1-00. 001 is 1-01...
  10. Replies
    11
    Views
    3,011

    What gateway firmware version? If it is 1.x you...

    What gateway firmware version? If it is 1.x you just have to have the equipment connected to see the points. If it is 2.x you must go in through the webserver and perform a discovery within the...
  11. Thread: Can2Go

    by El Presidente
    Replies
    37
    Views
    6,652

    Graphical programming is available. Pres

    Graphical programming is available.

    Pres
  12. For Daikin you have to limit the writes for...

    For Daikin you have to limit the writes for changes of value. If you write On when the unit is already on every two seconds it is fine as the gateway will not actively write to the indoor unit EEPROM...
  13. BACnet - Excellent, this got all my points...

    BACnet - Excellent, this got all my points working except for MSI, MSO, MSV. Thanks!

    Xarralu - SCL Elements confirmed Multi-states will not be available until November Firmware update.

    Pres
  14. CAN2GO UN2 - BACnet readProperty Request

    Hi all,

    I'm trying to use this controller to run simulations and trend points on my VRF system through a BACnet gateway.

    Script syntax for the request is (device instance, object type and...
  15. Tridium --> LG Lon Gateway SNVT Type Size Mismatch

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type (hvac_status) should be 12...
  16. Replies
    11
    Views
    3,011

    Ok, thanks anyway. Pres

    Ok, thanks anyway.

    Pres
  17. Replies
    11
    Views
    3,011

    Type Size Mismatch

    hvaccontrolsguy,

    I'm trying to help out a guy integrating Tridium and LG and he says for SNVT nvoUnitStatus, his system reports “Type Size Mismatch (13bytes). LonMark says this data type...
  18. Replies
    11
    Views
    3,011

    What was the problem and how did you solve it? ...

    What was the problem and how did you solve it?

    Pres
  19. Replies
    13
    Views
    2,438

    Have each of the indoor units been assigned a...

    Have each of the indoor units been assigned a group address? If not, do that and then cycle power on the gateway.

    Pres
  20. Replies
    157
    Views
    27,208

    C, check your mail. threefiddy, my e-mail...

    C, check your mail.

    threefiddy, my e-mail bounced back. Not sure what the problem is.

    Pres
  21. Replies
    157
    Views
    27,208

    C, add an email to your profile. Pres

    C, add an email to your profile.

    Pres
  22. Replies
    157
    Views
    27,208

    threefiddy, check your mail. Pres

    threefiddy, check your mail.

    Pres
  23. Replies
    157
    Views
    27,208

    Ok, what's the IP address of the Jace? It will...

    Ok, what's the IP address of the Jace? It will have to be 192.168.0.X if the gateway is left at default IP of 192.168.0.1 without enabling the gateway as a foreign device.

    If it is on a different...
  24. Replies
    157
    Views
    27,208

    De nada and you're welcome.

    De nada and you're welcome.
  25. Replies
    157
    Views
    27,208

    amigo, check your mail. Pres

    amigo, check your mail.

    Pres