  1. Replies
    37
    Views
    1,442

    Ok I'll bite,whats "eqpt", shiny. you may want...

    Ok I'll bite,whats "eqpt", shiny. you may want to add "private message" to your profile.
  2. Replies
    29
    Views
    1,410

    Why cant you check voltage too ignitor? I always...

    Why cant you check voltage too ignitor? I always confirm 120v to ignitor before replacing.Have been waiting to find an 80volt,but have yet to.But was relying on this test to tell me I am using...
  3. Replies
    9
    Views
    461

    Ive had Carriers turn blower on first,then go...

    Ive had Carriers turn blower on first,then go off,and normal sequence starts.Only to find out this is normal!
  4. Replies
    13
    Views
    1,449

    Now the World knows where all the Experts chat !

    Now the World knows where all the Experts chat !
  5. Replies
    13
    Views
    1,066

    I've had this.,replace the ignitor. I know its...

    I've had this.,replace the ignitor. I know its glowing red hot. Its worked twice for me.I carry Glowfly's,so it probably was not with factory OEM.
  6. Replies
    12
    Views
    733

    Is this furnace in basement?If so would not...

    Is this furnace in basement?If so would not running fan all the time,pull more radon thru the home,unless returns were sealed very well?
  7. Replies
    188
    Views
    16,477

    Over 100 posts,yet no one has posted the original...

    Over 100 posts,yet no one has posted the original factory bulletin!
  8. Replies
    11
    Views
    576

    Condensating furnaces are not a good idea up here...

    Condensating furnaces are not a good idea up here in the north for seasonal homes,That said I've always wondered if you added a "switch" to run inducer fan with not heat for an hour or so,if it would...
  9. Replies
    6
    Views
    354

    One tip I have used,remove hi limit...

    One tip I have used,remove hi limit switch,Install there to get before AC coil.
  10. I think the "guest" is referring to pulling...

    I think the "guest" is referring to pulling refrigerant back into the comp. Not pulling a vacuum before "setting" proper charge. My question,why are you doing this on "new' units?
  11. Replies
    13
    Views
    714

    Very good. Was there a piston attached to the...

    Very good. Was there a piston attached to the condenser? Thats the one to use,if not,double check charts.quessing about a .055.
    Pressure look pretty good to me,
  12. Replies
    16
    Views
    711

    I believe the E.R. uses liquid cocaine to re...

    I believe the E.R. uses liquid cocaine to re leave pain. Obviously not available over the counter!
  13. How do you check the pressures with both service...

    How do you check the pressures with both service ports closed?
  14. Replies
    6
    Views
    583

    And why didnt you try to warranty it? seems like...

    And why didnt you try to warranty it? seems like alot of work. We all know who's going to eat that!
  15. Replies
    5
    Views
    875

    Was out on routine service.Goodman GMS,this is...

    Was out on routine service.Goodman GMS,this is single stage nat gas,hi eff. (sorry no Mod&Ser). First thing I noticed was,plate in front of burner brown in color,more burnt look than rust. Visually...
  16. Replies
    33
    Views
    2,267

    [QUOTE=Af7171;18116211]Tech who do side work can...

    [QUOTE=Af7171;18116211]Tech who do side work can do it a lot cheaper .they use the company truck and company stock . No overhead . It all profit .

    Your correct there! We had a large HVAC Co....
  17. Replies
    33
    Views
    2,267

    A very prosperous salesmen once told me,If your...

    A very prosperous salesmen once told me,If your getting every job you bid,add 20%.,If work slows down,adjust accordingly!
  18. Replies
    22
    Views
    1,600

    Did I miss something?

    Did I miss something?
  19. Replies
    44
    Views
    14,404

    The "cleaning" property's of R410A are so much...

    The "cleaning" property's of R410A are so much better than say R22,. Been told by Reps. if you cut lines open down the road,there crystal clean! You know where it went?
  20. Replies
    19
    Views
    950

    Tip; Remove hi limit switch,take supply reading...

    Tip; Remove hi limit switch,take supply reading there.also take heat rise temp test.
  21. Replies
    14
    Views
    1,777

    Ditto; Goodman made a good move there!

    Ditto; Goodman made a good move there!
  22. Replies
    2
    Views
    389

    SALON...,have been told,chemical used in these...

    SALON...,have been told,chemical used in these place raise havoc with H.X etc! Bet the mechanical room is used to store them. Did have roofers once push chimney cap down,almost completely shut....
  23. Replies
    5
    Views
    538

    Yes the pilot did appear to be high,however they...

    Yes the pilot did appear to be high,however they have a heatshield above it,and cover.(could you even adjust it?) I did run my camera in to burner access,up to first bend,no holes. I did do a heat...
  24. Replies
    5
    Views
    538

    HEIL HELP NEEDED !

    Have an older Heil,condensating furnace. Msd NTGM100EHA3 Ser. L983817999 It keeps tripping roll-out switch,which I have replaced,that is attached to the closed combustion burner box.Box does appear...
  25. Replies
    29
    Views
    1,944

    Hows that work with "stand pipes" in cyl. tanks?

    Hows that work with "stand pipes" in cyl. tanks?
  26. Replies
    27
    Views
    2,096

    Had this same problem after replacing HSI with a...

    Had this same problem after replacing HSI with a retro fit. Lost seal in combustion air box,swirling air would not allow to light. Resealed with silicone,worked fine. Original HSI should have been...
  27. Replies
    36
    Views
    1,536

    Dido's....,7 cracks,one of the clam shells was...

    Dido's....,7 cracks,one of the clam shells was completely rusted off at face plate. Customer said the "click-it" switch was bad,he bypassed it. Was a roll-out switch. Cant fix stupid!
  28. Replies
    9
    Views
    1,136

    Traps can fool ya,by the time you get there,a...

    Traps can fool ya,by the time you get there,a partial blockage in trap will drain down. Will work fine when you reset the lock out.,then starts backing up water later when you've left. Clean em!
  29. Replies
    35
    Views
    2,267

    Did you clean orfice in pilot! Did one other...

    Did you clean orfice in pilot! Did one other day,the smallest "broach" they make bearly fits. Flame doubled in size afterwards! Yes...,they can be a ***** to get out! Sorry to bust up movie review.
  30. Replies
    32
    Views
    1,579

    Our electric suppliers give up to $450 rebate for...

    Our electric suppliers give up to $450 rebate for higher seer ratings.I then take half of that away on bid,for doing all the paperwork B.S.
  31. Flattin out those small "duct hangers" and zip...

    Flattin out those small "duct hangers" and zip screws,after a bead of silicone. Anglehead screwgun helps.
  32. Ok...,I'll bite. What the difference?

    Ok...,I'll bite. What the difference?
  33. Replies
    5
    Views
    875

    INSHOT BURNER NOISE ?

    Was out on routine service.Goodman GMS,this is single stage nat gas,hi eff. (sorry no Mod&Ser). First thing I noticed was,plate in front of burner brown in color,more burnt look than rust. Visually...
  34. Replies
    9
    Views
    1,042

    COMPANY OWNER CANT SHUT UP !

    I and other, subcontract ourselves to a supplier to do both installs and service,"we are not employees". He has a well established business,and does count for a good part of are annual income.As most...
  35. Replies
    8
    Views
    1,095

    Thanks Capt. This is the info I was looking...

    Thanks Capt. This is the info I was looking for,and will share with others.
  36. Replies
    8
    Views
    1,095

    A friend who has a Bacharach,told me he sends his...

    A friend who has a Bacharach,told me he sends his back to factory to be recalabrated every year or so,at almost a third the cost of the machine! Is this necessary? Does the Testo require the same?
  37. Replies
    8
    Views
    1,095

    Note: This is a combustion anaylzer,we are using...

    Note: This is a combustion anaylzer,we are using them out there right? Mr CO,you out there?
  38. Replies
    8
    Views
    1,095

    TESTO 310 vs TESTO 320

    Going to buy Analyzer,for residential use,and not that much of it. Looking to hear some thoughts from others. Not locked in on Testo,all though Johnstone has them a C note cheaper than last year....
  39. Replies
    43
    Views
    4,797

    For better or worse,richer or poorer....,equal...

    For better or worse,richer or poorer....,equal rights! Lots of jobs for women nowdays.In five years his record will be cleaned up,retirement should be in the beginning of your career,when your young...
  40. Replies
    2
    Views
    660

    WATER LEAK FROM HELL !

    Customer added 2nd story to home 1200sq.ft. Put in a 80% downflow with AC. After about 8 yrs,while running AC.,water leak coming thru ceiling on lower level. Because cased a-coil is on floor,they...
  41. Replies
    33
    Views
    1,900

    Pic of coil....,423081

    Pic of coil....,423081
  42. Replies
    33
    Views
    1,900

    Ok.,Was told by different supplier,they wont sell...

    Ok.,Was told by different supplier,they wont sell the Heil "N" coil uncased. Opened up plenum,removed "N" coil.,this was a "hack" job at best! Was a 17"furnace,with a 13" coil. They installed the...
  43. Replies
    33
    Views
    1,900

    Garychance: change your profile so you can accept...

    Garychance: change your profile so you can accept private messages....,That is the coil,didnt come cased,had a plate over right outer coil slab.
  44. Replies
    33
    Views
    1,900

    beenthere..,have to agree with ya there. the new...

    beenthere..,have to agree with ya there. the new coil will probably have a new x-valve.If it works,we may never really know!
  45. Replies
    33
    Views
    1,900

    Ok,getting this second hand,from original...

    Ok,getting this second hand,from original installer. Factory Rep. says hes seen this before,he installed "N" coil app.17".,on to a new 24" furnace. Rep claims you cant get enough air through it,and...
  46. Replies
    33
    Views
    1,900

    Said he had deep vacuum on for an hour. Also as...

    Said he had deep vacuum on for an hour. Also as far as overheating bulb.,it was factory install. I did gain almost 8-10 degrees SLT,after correcting airflow.Thought we had it.Maybe his welds didnt...
  47. Replies
    33
    Views
    1,900

    84 degrees LLT., I also thought nitro charge...

    84 degrees LLT., I also thought nitro charge sounded funny. Of course this was verified by a "parts" person. Original installer has call in for factory rep. I forgot to mention this is an "N" Coil.Im...
  48. Replies
    33
    Views
    1,900

    FREEZING COIL & BRAIN !

    Have a Heil new 2ton with X-valve. New furnace also. I was called in after the install,was told Heil sends out Cond. with a Nitro Charge,original installer didnt realize this,let charge go and topped...
  49. Replies
    28
    Views
    4,093

    Read original post "it went down 15 degrees..,not...

    Read original post "it went down 15 degrees..,not to 15 degrees.
  50. Replies
    37
    Views
    2,822

    Remember Goodman was just purchased by...

    Remember Goodman was just purchased by Dukain,they are now the largest manufacture in the world! They must be doing something right.