Search:

Type: Posts; User: GYUR22

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Possibly they are configured as remote alarms...

    Possibly they are configured as remote alarms look into:
    Feature 41 - Alarm Route 450.20-CP2.41 (603) Pages 1 to 10
    Feature 42 - Alarm Configuration 450.20-CP2.42 (202) Pages 1 to 6
  2. We have another device - Modbus RTU cards for...

    We have another device - Modbus RTU cards for FX14/15/16 and FX07, so it's possible to use any Modbus TS
  3. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    961

    yes you need the image files with your version

    yes you need the image files with your version
  4. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    961

    Try to reflash w NUT

    Try to reflash w NUT
  5. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    961

    smallest file ;)

    smallest file ;)
  6. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    961

    Check this:...

    Check this:
    http://files.mail.ru/77A89297009D4C509869F52DC69A8212
    p.s. I can't attach file to message
  7. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    961

    looks like security system issue, check if you...

    looks like security system issue, check if you can use remote desktop
    ps ask guys from local JCI they shoud know
  8. Replies
    1
    Views
    315

    both because consists of two independent devices

    both
    because consists of two independent devices
  9. Replies
    5
    Views
    528

    1. remove associated w nae55 files from tftp...

    1. remove associated w nae55 files from tftp directory
    2. unzip from archive all files again
  10. Thread: NCE Question

    by GYUR22
    Replies
    23
    Views
    1,140

    1. NAE part Recomended object quantity on NAE...

    1. NAE part
    Recomended object quantity on NAE part of NCE :2500objects - including network objects
    Recomended network objects per ms/tp or n2 trunk : 1000
    So for example 1000 network objects...
  11. Replies
    6
    Views
    1,641

    yes http://files.mail.ru/237EN4

    yes

    http://files.mail.ru/237EN4
  12. Thread: FX05

    by GYUR22
    Replies
    1
    Views
    454

    NO mstp on Fx05,06 only on FX07

    NO mstp on Fx05,06
    only on FX07
  13. Thread: NAE animations

    by GYUR22
    Replies
    6
    Views
    525

    You need Advanced graphics package (it's a Visio ...

    You need Advanced graphics package (it's a Visio plugin) to make your own animation
    or only standart graphic with it's animated fan only
  14. Because of FEC for NCE and it's display siting on...

    Because of FEC for NCE and it's display siting on this bus
  15. As I can understand McQuay is third party...

    As I can understand McQuay is third party equipment for MSEA.
    You should try- go to Integration
    1.Add Field bus (if you have it don't need)
    2.Then add Bacnet on Field bus
    3. Scan network
  16. Replies
    3
    Views
    461

    I think you should care about M-Authorize patch,...

    I think you should care about M-Authorize patch, file name - M_Authorize 5.4.30 Patch.EXE (I can e-mail it)

    Bad thing that you need authorize M3 again
  17. Thread: JCI M3i

    by GYUR22
    Replies
    1
    Views
    471

    I have some installations My opinion - works...

    I have some installations
    My opinion - works well
    M-Graphics - perfect
    other parts M-alarm, M-Trend, etc- not so convinient
    EDE OPC- good convinient tool
    BACnet OPC - I have not BACnet systems...
  18. Replies
    9
    Views
    1,291

    You need YES or ICE and programm file for it

    You need YES or ICE and programm file for it
  19. Thread: FX upload

    by GYUR22
    Replies
    4
    Views
    583

    controllers like - FX16X - possible to upload,...

    controllers like - FX16X - possible to upload, FX16D - NOT
    They are even different in hardware
  20. Replies
    16
    Views
    5,042

    This may help

    This may help
  21. Thread: NAE issue

    by GYUR22
    Replies
    25
    Views
    1,166

    Try to put BACnet integration with you Fieldbus...

    Try to put BACnet integration with you Fieldbus as parent then discover
  22. Replies
    5
    Views
    651

    Thank you

    Thank you
  23. Thread: MS/TP under NAE

    by GYUR22
    Replies
    20
    Views
    1,439

    I tested York CX UDC on NAE R3.1 MS/TP trunk -...

    I tested York CX UDC on NAE R3.1 MS/TP trunk - it works
    but it was only a test not serious job
  24. Replies
    12
    Views
    1,168

    Objects restrictions: NAE35,45 - 2500 NAE55...

    Objects restrictions:
    NAE35,45 - 2500
    NAE55 -5000
    This mean overall objects in NAE

    I think you better go cgproducts.johnsoncontrols.com and search docs with words like: NAE, MSEA

    ps Example...
  25. Replies
    5
    Views
    651

    ddcfreek, Salmon_king Thank you I already have...

    ddcfreek, Salmon_king
    Thank you I already have xif and profile but not shure in exact variables
    for example CurrentA and CurrentD?