  1. Replies
    6
    Views
    712

    What we have found is that if a schedule is...

    What we have found is that if a schedule is created inside a Unit Controller, the JACE will be able to import that on the MSTP link, and then you can use the Schedule Exporter and it will work.
    ...
  2. Replies
    6
    Views
    712

    Create BACNET Writeable Schedule in AX

    Hello all.

    We have a site that we are using a JACE6 to control some units at a site where we need the AX Schedules to be BACNET Writeable.

    So there will be another controller writing to the...
  3. Replies
    4
    Views
    1,116

    Does anyone know if there is a standard point...

    Does anyone know if there is a standard point that would be triggered to Re-Calibrate the VAV on a VAV-SD Controller?

    I know that these are freely programmable, but I didn't know if there was a...
  4. Replies
    4
    Views
    1,116

    Alerton VAV-SD BACNet Point Issues

    Hello all. I am working with a Tridium front end on an Alerton BACNet MS/TP link. The VAV's on the link are the VAV-SD units. I have not dealt with these before and I am having some strange issues so...
  5. Replies
    10
    Views
    1,512

    Sure do. Shoot me an email or a PM.

    Sure do. Shoot me an email or a PM.
  6. Replies
    17
    Views
    1,927

    Well the diagnostic for an "8" code is "Processor...

    Well the diagnostic for an "8" code is "Processor in reset, or no functioning software. A persistent “8” means that service is
    required." So you could have something as serious as a processor issue....
  7. Replies
    17
    Views
    1,927

    What did the LED Display do during the DIP reset?...

    What did the LED Display do during the DIP reset? Did it do any EC codes?
  8. Replies
    17
    Views
    1,927

    When you are replacing the Memory Cards, are they...

    When you are replacing the Memory Cards, are they brand new? You should be doing a DIP Switch reset and then letting the panel re-download Code/Database from the local Summit PC.
  9. Replies
    13
    Views
    3,897

    I would double check that the DIP Switches are...

    I would double check that the DIP Switches are addressed properly. It is easy to get the On and the Off confused on those.

    -P means that it is waiting for a database from the Tracer Summit...
  10. Replies
    10
    Views
    1,507

    It sounds to me like you have a varience between...

    It sounds to me like you have a varience between the setpoints in the Area Control and the setpoints in the VAV's. First off, are you using UCM I/II/III/IV VAV's or Comm5 VV550/1's? Remember that...
  11. Replies
    1
    Views
    506

    Just making sure, you have the custom graphic...

    Just making sure, you have the custom graphic going to "Universal Input[1]" as opposed to something like "Universal Input Units[1]" correct?

    I have seen things like this with UI13 on an AH540...
  12. Replies
    10
    Views
    1,507

    Well it should at least make it so it won't try...

    Well it should at least make it so it won't try to use the Termainal Reheat if your zone temp gets too low where it would normally use it so you won't be aimlessly trying to reheat a zone with the...
  13. Replies
    0
    Views
    408

    Jace IO Bus RS-485 Port Settings?

    Hello all. Hoping that someone might have some information here for me.

    I have a Security Jace that has an R2R Module attached to it, but I want to add another R2R in a remote location. So...
  14. Replies
    10
    Views
    1,507

    We have this happen occasionally as well. Here is...

    We have this happen occasionally as well. Here is basically what happens...

    When a PC connects to the site, the internal database on the BCU and the PC compare timestamps on their last database...
  15. Replies
    0
    Views
    250

    JACE BDT Table Question

    Hello all. Hopefully someone can answer this easily becuase I can't find the answer in WorkPlace Help.

    If you have a BDT table under IP Port BAC0 (47808) and another BDT table under IP Port BAC1...
  16. Replies
    13
    Views
    3,104

    I have ARCNET and Ethernet cards. Shoot me an...

    I have ARCNET and Ethernet cards. Shoot me an email and let me know what you need.
  17. Replies
    0
    Views
    564

    PoolPak ECCIII Lon Fault Codes?

    Hello all. Long time no post!

    I have a PoolPak with an ECCIII controller on it and some how we lost programming in our BCU for it. I have the .xif file but there are some points like...
  18. Replies
    8
    Views
    2,221

    I am confused. Are you asking if the Comm5 card...

    I am confused. Are you asking if the Comm5 card is compatible or the Version 5 software? The card itself is and you need Rover version 7 if you want to run on 7 pro or ultimate. It is not approved...
  19. Replies
    6
    Views
    1,009

    I guess what I am curious to know is if you are...

    I guess what I am curious to know is if you are trying to use this on the LAN side of the router or if you are trying to use this on the Internet from home. BACNET does not traverse the internet very...
  20. Replies
    2
    Views
    609

    Trane ZN517 TOV on an AX Platform?

    Hello all,

    I have a ZN517 that has been integrated into a JACE. The issue that I am running into is that I need to have TOV at the stat using the On/Off buttons (Or Occ/UnOcc if you prefer).
    ...
  21. Replies
    6
    Views
    2,051

    If you want to look to see what boxes are...

    If you want to look to see what boxes are associated with an Area, go to Setup -> Area -> Select the area where the VAV boxes should be associated -> then look at the "Members" tab. Your VAV boxes...
  22. Replies
    10
    Views
    1,512

    Just throwing it out there again that I have a...

    Just throwing it out there again that I have a stock of these =)
  23. Replies
    5
    Views
    1,348

    I would suggest a DD-WRT configuration...

    I would suggest a DD-WRT configuration personally.

    It is 3rd party firmware for wireless routers where you can tweak transmit power signals.

    I would suggest something with RP-TNC or SMA...
  24. Replies
    9
    Views
    1,032

    This method seemed to work. It takes the...

    This method seemed to work. It takes the 12345.6789 and takes it down to 12345.6700. That works for me since I don't need to be absolute.

    Unfortunatly the methods that tShort described resulted in...
  25. Replies
    9
    Views
    1,032

    OK I will try to explain a little better. I...

    OK I will try to explain a little better.

    I have a Service that is figuring out CO2 Carbon Footprint and kBTU usage. In the service wire sheet, I cannot edit the format of the output.

    So lets...
  26. Replies
    9
    Views
    1,032

    JACE - How To Round A Number?

    Hello all,

    I am trying to figure out how to take a number such as 123.456789 and round it down to 123.46 when using a Numeric Writeable.

    The most obvious answer would seem to be to set a...
  27. Replies
    13
    Views
    3,104

    I have a stock of the ethernet cards. Shoot me an...

    I have a stock of the ethernet cards. Shoot me an email if you still need one.
  28. Replies
    15
    Views
    1,973

    Well I got my CBL-STAT75 and it is just CAT3...

    Well I got my CBL-STAT75 and it is just CAT3 cable with RJ45's on the ends that are pinned straight through.

    I am assuming that I need to convert this over to Serial so I can get to it talk to...
  29. Replies
    4
    Views
    747

    Remote building with CCP2. Want to connect to...

    Remote building with CCP2. Want to connect to BMTX in another building. Ethernet network is available but rather than using the IFS 1300/2300 Fiber Converters, I want to use a serial tunnel. We have...
  30. Replies
    4
    Views
    747

    On most Trane stuff that is the case...

    On most Trane stuff that is the case (Mini-Monitor / Comm4 Rover / Hyperterminal to CCP's ect) but those aren't working in this case. Seems to be something deeper than that.
  31. Replies
    4
    Views
    747

    Trane Isolated Comm3 Port Settings?

    Shot in the dark here but does anyone know the proper port settings for Isolated Comm3? I know it is RS-485 1200 Baud but I am looking for Parity/Data Bits/Stops Bits/Flow Control/Duplex Mode/ And...
  32. Replies
    15
    Views
    1,973

    Thanks for all the responces. I will see what I...

    Thanks for all the responces. I will see what I can find.

    As far as the IR Gun, I know what you are saying. But what I have always done is taken a plain white cloth with me and waved it back in...
  33. Replies
    15
    Views
    1,973

    JCI Zone Bus Cable

    Does anyone know where to obtain a JCI Zone Bus Cable? Or maybe the proper pin-out on making your own?

    The reason that I ask is because I was at a JCI job that they had been kicked out of and the...
  34. Replies
    6
    Views
    1,728

    Per our rep we cannot return the card and any...

    Per our rep we cannot return the card and any additional card will cost $5,000. Do you have a link to this points list? And does it conform to the MODBUS RTU protocol?

    But I am thinking that...
  35. Replies
    9
    Views
    1,608

    I agree with Dapper. Just call Echelon and see if...

    I agree with Dapper. Just call Echelon and see if they have the PCMCIA cable for the PCC-10 Model 73200 card. That should be what you need. It might come out to a serial connection but you should be...
  36. Replies
    6
    Views
    1,728

    Liebert to Trane Tracer Summit BCU

    Hello All,

    Well it has been a while since I have come to the site for help but now is one of those times where assistance is needed.

    I have a job going in with a Liebert unit that was sold with...
  37. Replies
    4
    Views
    1,031

    Send me an email. Monetary donations always...

    Send me an email. Monetary donations always apperciated ;-)
  38. Replies
    15
    Views
    2,001

    I have seen these kinds of issues when there are...

    I have seen these kinds of issues when there are power fluctuations / outages.

    For instance, there is a school district here in the Cleveland area that had the same issue with only 1 MP580...
  39. Replies
    5
    Views
    1,792

    I made my own cable too. Pretty easy once you get...

    I made my own cable too. Pretty easy once you get all the pins figured out on the PCMCIA.

    I was thinking of selling them ;-) lol.
  40. Replies
    4
    Views
    1,031

    Shoot me an E-Mail if you still need this stuff.

    Shoot me an E-Mail if you still need this stuff.
  41. Replies
    2
    Views
    946

    Shoot me an EMail if you still need this.

    Shoot me an EMail if you still need this.
  42. Replies
    2
    Views
    499

    Even a BCU with a lot of items on its links...

    Even a BCU with a lot of items on its links should almost always be over 50% free on the Idle Time.

    If it is below this you might want to look at CPL routines to see if you have any that are not...
  43. Replies
    6
    Views
    1,254

    Well upgrading from v12 firmware would be a good...

    Well upgrading from v12 firmware would be a good solution regardless. I would at least go to v16 with 16.092 firmware. There has been a ton of fixes and improvements in the firmware images.

    I...
  44. Replies
    8
    Views
    1,357

    There has been the "Compatability Mode" option...

    There has been the "Compatability Mode" option that you speak of since Windows XP. Basically you can right click on the icon of a program and go to the properties and tell it to run in compatability...
  45. Replies
    4
    Views
    587

    Well in Setup -> Site Configuration -> Event...

    Well in Setup -> Site Configuration -> Event Receivers...pull up the workstation that is getting the alarms and change the "System Print" and "System Log" to Never. That should get rid of the Log...
  46. Replies
    8
    Views
    1,357

    Make sure that it is Windows XP "Professional"....

    Make sure that it is Windows XP "Professional". The "Home" version is not supported.

    You can use Vista "Business" if you have Summit v17.

    I have heard talk of people getting Summit to run on...
  47. Thread: Trane BCU

    by Webbyz
    Replies
    20
    Views
    2,696

    If all the BCU is doing is showing a -P you can...

    If all the BCU is doing is showing a -P you can always send it over to me and I will gladly use it ;-)
  48. Thread: Tracer Summit

    by Webbyz
    Replies
    6
    Views
    974

    Well along the same lines I would go into the...

    Well along the same lines I would go into the "Objects and Properties" and go to Device and pull the diagnostics from the BCU's and see how much memory you have remaining on the BCU's. If the numbers...
  49. Thread: Trane BCU

    by Webbyz
    Replies
    20
    Views
    2,696

    I have New In Box ethernet cards specifically for...

    I have New In Box ethernet cards specifically for the BMTS. These will also work in BMTW's if needed. If you need any please contact me.
  50. Thread: MP 581

    by Webbyz
    Replies
    1
    Views
    570

    You have to contact your local Trane office along...

    You have to contact your local Trane office along with the challenge code from the 581 and they will give you a one-time only password to unlock the unit.

    But you have to be in front of the 581...