Search:

Type: Posts; User: Igotworms

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    17
    Views
    817

    Are you having problems with the network? ...

    Are you having problems with the network? Controllers going on and offline? If not I wouldn't mess around with it. The only way I know how to change instance numbers is to change it in CCT...
  2. Replies
    6
    Views
    558

    Yes every jace has a Niagara network that can...

    Yes every jace has a Niagara network that can share data between them. It does not need a peer to peer license or any other license to do this
  3. I did Google LWC and found a few .pdf files but I...

    I did Google LWC and found a few .pdf files but I haven't seen anything about that FF diagnostic address. Ill keep looking
  4. Nick, Where did you see that document? I did...

    Nick,

    Where did you see that document? I did notice that on the LWC the address was set to FF. I tried to change it to 5 which is what is mapped into the NCM but it didn't do anything.
  5. AX Metasys MIG and McQuay Loop water contontroller

    I'm converting an existing site from a Metasys NCM to an FX70. The NCM is integrating to a few McQuay OPM panels with a MIG and also a McQuay loop water controller that also goes back into a MIG. I...
  6. Replies
    4
    Views
    392

    What kind of controller is the temp sensor wired...

    What kind of controller is the temp sensor wired to? What protocol is being used? Are any tuning policies set up?
  7. Replies
    1
    Views
    196

    I have a bunch of DX9100 accessories along with...

    I have a bunch of DX9100 accessories along with other N2 devices shoot me a PM
  8. Thread: Lon nci

    by Igotworms
    Replies
    15
    Views
    808

    This seems like a stupid question but I can't...

    This seems like a stupid question but I can't figure it out. How do you edit a .lnml file in the text editor? I'm able to navigate to the lnml file in my modules section of workbench on my machine,...
  9. Replies
    5
    Views
    326

    I know how to change it based on the status but...

    I know how to change it based on the status but what I'm trying to do is a little different. I have the image changing based on zone temp with no problem. But now I want to have the image change if...
  10. Replies
    11
    Views
    710

    It was a company specific module that I wanted to...

    It was a company specific module that I wanted to test out. My laptop was not licensed for it though
  11. Replies
    5
    Views
    326

    Unreliable PX Graphic

    Is there a way to change a picture on a graphic based on the status of the controller? I'm able to change the colors of the LEDs in kitPxGraphics based on zone temperature, but I would also like to...
  12. Replies
    32
    Views
    1,367

    What type of cabling do you usually use for Lon? ...

    What type of cabling do you usually use for Lon? In this building there is a 16 gauge wire ran for the comm trunk. That seems awful big for a comm trunk but the jacket of the wire specifically says...
  13. Replies
    4
    Views
    257

    What version is your jace running? Do you have...

    What version is your jace running? Do you have the same version of workbench on your pc as the jace?
  14. Replies
    2
    Views
    225

    Yes open up HVAC Pro and go to Central Plant...

    Yes open up HVAC Pro and go to Central Plant Applications. There is a Pump Leag/Lag question and answer application under that.
  15. Replies
    32
    Views
    1,367

    The very first thing I did on this job was wire...

    The very first thing I did on this job was wire the FX70 as another node on the network so there were two supervisory device online at once (The NAE and the FX70). With the NAE still online, I did a...
  16. Replies
    32
    Views
    1,367

    I got about half of the network online yesterday...

    I got about half of the network online yesterday and left it over night. I checked the alarm console this morning and had no ping alarms. I got the rest of the network online and it seems ok. I...
  17. Replies
    32
    Views
    1,367

    I think I'm finally starting to make some...

    I think I'm finally starting to make some progress with this. What I started doing is killing the power to all of the heat pumps. I turned on one breaker at a time which fed about 3 heat pumps per...
  18. Replies
    32
    Views
    1,367

    I can't select the heat pump as a device because...

    I can't select the heat pump as a device because I cant discover it to bring it into the database. I did find the authentication key part under lon network management and it is set to false with FF...
  19. Replies
    32
    Views
    1,367

    I just hooked up an FX60 directly to one of the...

    I just hooked up an FX60 directly to one of the heat pumps so that was the only thing on the network. I went to Lon utilities and hit the service pin and I took a screen shot of what I got. Its...
  20. Replies
    32
    Views
    1,367

    The EOL resistors didn't work and splitting the...

    The EOL resistors didn't work and splitting the trunk isn't helping. Isn't there a simple way to unbind links from a previously managed network!?
  21. Replies
    32
    Views
    1,367

    I should also mention that the lon trunk is ran...

    I should also mention that the lon trunk is ran in 2 conductor 18 gauge unshielded wire. The jacket of the wire specifically says "lonworks communication" right on it so im assuming that is the...
  22. Replies
    32
    Views
    1,367

    I know for a fact that it is not licensed. I...

    I know for a fact that it is not licensed. I order a ftt10 to usb adapter a while back but I couldn't order a lon license for my machine for some reason. I have some capacitor/resistor combination...
  23. Replies
    32
    Views
    1,367

    Matrix, I have noticed that a few of the heat...

    Matrix, I have noticed that a few of the heat pumps are on subnet 4. The rest of them are on subnet 1. There are a total of 45 heat pumps on this network. What throws me off about communication...
  24. Replies
    32
    Views
    1,367

    No I dont think its shielded

    No I dont think its shielded
  25. Replies
    32
    Views
    1,367

    I don't think I can connect a lon network...

    I don't think I can connect a lon network directly to my workbench pc because my pc is not licensed for lon. I did notice that the EOL was not terminated with a resistor or anything else. There was...