Search:

Type: Posts; User: ahansen

Search: Search took 0.00 seconds.

  1. Replies
    6
    Views
    350

    oBIX is just another protocol. If your access...

    oBIX is just another protocol. If your access control system doesn't already talk obix, then it isn't going to work for you. FWIW, I wrote Tridium's obix driver.

    If the web interface is html...
  2. Replies
    6
    Views
    614

    People can develop, sell and deploy their own...

    People can develop, sell and deploy their own software on Niagara. The software ecosystem is constantly growing.
  3. Find out if your utility provider supports green...

    Find out if your utility provider supports green button (Google it). If so you can get your load profile directly from the source.
  4. I believe Maxline's Apogee driver for AX is P2.

    I believe Maxline's Apogee driver for AX is P2.
  5. Understanding the sequence of operations and...

    Understanding the sequence of operations and doing it "right" is the best way to go. However, it isn't always possible; most flash products are designed to withstand 100,000 - 1,000,000 writes.
  6. Jeremy is correct, it is slow. It takes 2.5s to...

    Jeremy is correct, it is slow. It takes 2.5s to poll a single point.

    If you need to trend 100 points, then your poll cycle is a little over 4 minutes.

    However, if all you need are points for...
  7. Replies
    9
    Views
    1,137

    Serial to ethernet adapter: ...

    Serial to ethernet adapter: http://www.digi.com/products/serialservers/digionesp#overview
  8. Replies
    26
    Views
    3,510

    FM - F'ing Magic

    FM - F'ing Magic
  9. Replies
    10
    Views
    1,855

    http://obix.tridium.com

    http://obix.tridium.com
  10. Replies
    14
    Views
    1,157

    I think Ebonix has one.

    I think Ebonix has one.
  11. Replies
    14
    Views
    1,157

    http://mlkshk.com/r/1BIF

    http://mlkshk.com/r/1BIF
  12. Replies
    4
    Views
    1,722

    Seimens part # 540-143

    Seimens part # 540-143
  13. Thread: Demand Meters

    by ahansen
    Replies
    8
    Views
    748

    I don't have domain expertise, I don't know what...

    I don't have domain expertise, I don't know what you mean by a 13,800 feed...

    But if you haven't already, check out the class 3000 meters from Emon which can go up to 3200 amps:
    ...
  14. Replies
    19
    Views
    1,984

    http://pub.controls.johnsoncontrols.com/publish/b2...

    http://pub.controls.johnsoncontrols.com/publish/b2b_aa/us/eng/abcs_exchange/facility_explorer/Webcasts.html
  15. Replies
    19
    Views
    1,983

    Tridium AX with the CSI3 System 600 Driver. The...

    Tridium AX with the CSI3 System 600 Driver. The driver is slow because it "screen scrapes" the VT100 MMI port, but it works.
  16. Replies
    12
    Views
    5,563

    CSI Cubed is incorrect / out of date (as is our...

    CSI Cubed is incorrect / out of date (as is our own website):

    Siemens Sys600 / Apogee
    Barber Coleman Network 8000
    Emon meters
    SMA inverters
    Particle Measuring Systems Airnet devices
    Any...
  17. Replies
    5
    Views
    829

    Was that a Jace?

    Was that a Jace?
  18. Get any and all software upgrades you can,...

    Get any and all software upgrades you can, especially the JCI modules.
  19. Thread: Salesman....

    by ahansen
    Replies
    8
    Views
    901

    Salesman...

    It is my sincere belief that progress is made when the consequences are not well understood. Understanding the human condition is far more important in sales.

    Welcome to the toolbox brother.
  20. Thread: Kw to kW Hours

    by ahansen
    Replies
    23
    Views
    1,951

    You're right. I wrote that formula backwards it...

    You're right. I wrote that formula backwards it should be (time / one hour) which equates to the number of hours.
  21. Thread: Kw to kW Hours

    by ahansen
    Replies
    23
    Views
    1,951

    I believe it's: (oneHour / (duration of poll...

    I believe it's:

    (oneHour / (duration of poll interval)) * (numPulses * pulseValue)

    The hour and interval need to be the same units (ie millis, seconds...)
  22. Thread: Facet help

    by ahansen
    Replies
    5
    Views
    543

    Off the cuff options: 1. Name your point...

    Off the cuff options:

    1. Name your point accordingly. Instead of Damper, how about something like Damper_Closed?
    2. In your graphics you can change the format of your value bindings. Normally...
  23. Digi

    IMHO - this is the best response. It is the only USB adapter that I have found that works with HVAC Pro. If your field-bus depends upon sub-100ms timing, this is the best option that I have found.
  24. Thread: WEB-MON ?

    by ahansen
    Replies
    7
    Views
    765

    And? How'd it work out?

    And? How'd it work out?
  25. Replies
    7
    Views
    656

    Is your AX box Windows? If so, maybe you can run...

    Is your AX box Windows? If so, maybe you can run a local exchange server that accepts smtp (only from localhost) and routes to the primary exchange server?
  26. Replies
    16
    Views
    1,052

    I haven't used this, but I've heard good things...

    I haven't used this, but I've heard good things about it:

    http://www.controlbyweb.com/webrelay/
  27. Replies
    8
    Views
    636

    If you can code: http://www.controlbyweb.com

    If you can code: http://www.controlbyweb.com
  28. Replies
    15
    Views
    1,359

    Oops, enforma.com is a mistake. archenergy.com...

    Oops, enforma.com is a mistake. archenergy.com is where you'll find the Enforma product.
  29. Replies
    3
    Views
    423

    In general, 'out' does not necessary mean the...

    In general, 'out' does not necessary mean the last written value. In several of the drivers I'm familiar with (PUP is not one of them), out reflects the last polled value.
  30. Replies
    15
    Views
    1,359

    Here's what I can come up with off the top of my...

    Here's what I can come up with off the top of my head. Not all of these have drivers, but they have all developed software products for Niagara AX:

    quicksilverintegrations.com
    activelogix.com...
  31. Replies
    7
    Views
    700

    http://hvac-talk.com/vbb/showpost.php?p=1861170&po...

    http://hvac-talk.com/vbb/showpost.php?p=1861170&postcount=5
  32. Replies
    5
    Views
    628

    The CSI3 GCM driver connects to GCMs or LCMs, you...

    The CSI3 GCM driver connects to GCMs or LCMs, you can't rip them out. It's a text based driver, it integrates with the VT100 HMI. It is not a speed demon.

    The timeout is two hours. Restart the...
  33. Replies
    2
    Views
    525

    Google "emon modbus point map". You don't need...

    Google "emon modbus point map". You don't need to convert anything, you can get kw directly from the meter.
  34. Replies
    3
    Views
    421

    Oh, sorry, it sounds like a bug in someone's...

    Oh, sorry, it sounds like a bug in someone's BACnet interface.

    Tridium has a System 600 / Apogee driver and while it is slow, if you use it exclusively for writes you'll be fine. I don't know if...
  35. Replies
    3
    Views
    421

    In my experience, those points can not be...

    In my experience, those points can not be unbundled and are therefore not commandable. The way Insight does it is to change the initial value (write to flash memory) which is different from...
  36. Thread: Ax reports

    by ahansen
    Replies
    4
    Views
    451

    Just in case you are unaware, there is an AX...

    Just in case you are unaware, there is an AX based tenant billing application available for sale now. In an effort to not spam the board, I'll say no more unless you are interested.
  37. Thread: Cheap Beer?

    by ahansen
    Replies
    41
    Views
    1,654

    A six pack of any Yuengling brew was < $5 two...

    A six pack of any Yuengling brew was < $5 two years ago. Can only be found on US Atlantic states. Outstanding beer, sorry I moved.
  38. Replies
    46
    Views
    4,896

    Has anyone implemented UA on non-Windows? I...

    Has anyone implemented UA on non-Windows? I haven't kept up with OPC, but back in the DCOM days you ultimately ended up with Windows issues that neither the client nor server vendor could repair. I...
  39. Replies
    15
    Views
    5,339

    Nope, TEC points are available in Niagara. ...

    Nope, TEC points are available in Niagara.

    The tunnel is just a convenience if you want to get on the Seimens system to do some programming or validate what the driver is telling you.
  40. Replies
    15
    Views
    5,339

    Regarding the CSI3 driver... When you go to...

    Regarding the CSI3 driver...

    When you go to add TEC points, there is a drop down that lets you select the point type. There is no point definition report for TEC points so driver doesn't know...
Results 1 to 40 of 42