Search:

Type: Posts; User: Merkas

Search: Search took 0.00 seconds.

  1. Replies
    1
    Views
    417

    Have you played with AutoHotKeys app. I posted...

    Have you played with AutoHotKeys app. I posted about using it for a Siemens kiosk awhile back

    http://hvac-talk.com/vbb/showthread.php?926502-Siemens-Apogee-PPCL-OIP-Command
  2. Replies
    3
    Views
    265

    The QFA3001.BU is a 3 wire device. (1) is DC+,...

    The QFA3001.BU is a 3 wire device. (1) is DC+, (2) is DC-, and (9) is RH 4-20mA or 0-10V
  3. Replies
    3
    Views
    265

    You can till order a 2 wire version. Its...

    You can till order a 2 wire version. Its QFA3001.WU-2W
  4. LonWorks RS-485 to Fiber - Fiber to RS-485?

    I'm not very versed with Lon so bear with me. We have a building with a Lon network (6 devices) and then a RS-485 to fiber going out to another location with a fiber to RS-485. This second building...
  5. Noticed you said you were setting up the page as...

    Noticed you said you were setting up the page as A4 can you change this to Letter and try again? Tried it as a test and the A4 does leave a lot of "White Space" were the Letter was not to bad.
  6. can you post an example, one of the live graphic...

    can you post an example, one of the live graphic and one of the print preview?
  7. If its on windows 7 use the snipping tool to do a...

    If its on windows 7 use the snipping tool to do a screen shot. May give you better results then the print function in graphics.
  8. Switch print layout to landscape before you...

    Switch print layout to landscape before you preview.
  9. Replies
    19
    Views
    2,011

    whart or bonzai . It was user configured

    whart or bonzai . It was user configured
  10. Replies
    19
    Views
    2,011

    Using this on a laptop or android phone? Setup...

    Using this on a laptop or android phone?
    Setup on phone was load aDosBox update config file. Load DOS CIS files onto phone. Connect to Air Console XL WiFi. Log into the web interface for the Air...
  11. Replies
    19
    Views
    2,011

    you can't use serial bot. Load aDosBox from...

    you can't use serial bot. Load aDosBox from Google Play. Add the config line to the aDosBox .cong file. Did you buy an Air Console XL device?
  12. Replies
    19
    Views
    2,011

    serial1=nullmodem server:192.168.10.1 port:2167...

    serial1=nullmodem server:192.168.10.1 port:2167 transparent:1
  13. Replies
    19
    Views
    2,011

    Itís not really a Siemens App but I've been able...

    Itís not really a Siemens App but I've been able to connect to a TEC with a Droid 4 phone. You have to load aDosBox and the old Siemens dos CIS software. Then use a WI-FI to serial device for the COM...
  14. Replies
    2
    Views
    444

    Try here for...

    Try here for manualhttps://www.hqs.sbt.siemens.com/gip/general/dlc/data/assets/us/APOGEE-Heat-Pump-Controller---Multi-Stage-Owner-s-Manual_A6V10308419_us-en.pdf
  15. Replies
    3
    Views
    640

    Well I figured I'd do a follow up. So I've...

    Well I figured I'd do a follow up. So I've managed to us the ICC xltr-1000 to pull the BACnet points from a Carrier 30MPW system (after the Carrier rep put in the CCN to BACnet card) and export them...
  16. Replies
    3
    Views
    640

    ICC xltr-1000 BACnet MSTP to FLN?

    Have a customer that wants to use an ICC xltr-1000 to bring a Carrier chiller BACnet MSTP points into a Siemens FLN. I looked over the manuals and it's kind of vague on the Siemens FLN side. Sounds...
  17. Thread: Siemens node

    by Merkas
    Replies
    10
    Views
    925

    Monitor "your own node" APOGEE Powers Process...

    Monitor "your own node"

    APOGEE Powers Process Control Language (PPCL) Userís Manual

    Syntax
    LINK
    Use
    This resident point indicates the condition of communications.
    Depending on the...
  18. Ok don't laugh too much at this. 1) Go into...

    Ok don't laugh too much at this.

    1) Go into report builder and create a new Trend Definition Report. Click the Add button and in the object selector window enter * as the point name and do a find...
  19. Replies
    8
    Views
    975

    357551

    357551
  20. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    675

    I know, Just checking that gazoo knows that....

    I know, Just checking that gazoo knows that. Should be able to do it from the front end even if its never had telnet enabled before. I do it all the time.
  21. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    675

    Is this PXCM on a PII hard wired trunk or on...

    Is this PXCM on a PII hard wired trunk or on ethernet?
  22. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    675

    Is there an Insight front end? Go to system...

    Is there an Insight front end? Go to system profile and double click on the panel you want to enable telnet. Find the button "Terminal Definitions" a config window will open with a check box to...
  23. Replies
    15
    Views
    2,251

    "You all agree/disagree using two different...

    "You all agree/disagree using two different BACnet netowrk numbers on the same network is going to cause trouble like this?"

    Not sure? Anyone?

    Can you move you "BACnet/IP 47808" port to another...
  24. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,255

    Formulas for a 4-20mA input on a UC Slope = (V2...

    Formulas for a 4-20mA input on a UC
    Slope = (V2 - V1) / 2602
    Intercept = V1 - (Slope x 650)

    Sensor 0-65
    V1 = 0
    V2 = 65

    Slope = (65 - 0) / 2602
    Slope = 0.024981
  25. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,255

    From the Book table B-3; Range Slope ...

    From the Book table B-3;
    Range Slope Intercept
    0 - 100 0.038435 -25.0
  26. Replies
    5
    Views
    1,089

    Can you log into the panel from the HMI port and...

    Can you log into the panel from the HMI port and poll the rev string. Or from the front end in system profile. If it is a rev 3.0 , 3.1 , 3.2 your true BACnet. Anything in the 2.X range is P2.
  27. Replies
    5
    Views
    1,089

    If "Siemens panel that already has the BACnet...

    If "Siemens panel that already has the BACnet drivers" means it is a P2 controlled loaded with the BACnet MSTP driver then your out of luck. Siemens has to manually build the application and loaded...
  28. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,255

    There is no option for UC in point editor. Your...

    There is no option for UC in point editor. Your 1000 ohm RTD would have a slope of 0.1 and intercept of -40.0, not taking into account wire size or lenght.
  29. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,255

    Check out Appendix B. Slopes and Intercepts of...

    Check out Appendix B. Slopes and Intercepts of this manual
  30. Replies
    3
    Views
    669

    gazoo, You can change the slope and intercept...

    gazoo,

    You can change the slope and intercept for the UC from the edit points menu. See the attached. highlight the field and start typing your values in. There is no calculator built in for this....
  31. Replies
    2
    Views
    720

    Tsasso, try this; 00010 PT1 =(6.112 * 10...

    Tsasso,
    try this;

    00010 PT1 =(6.112 * 10 .ROOT. (1/(7.5 * DEGC /(237.7 + DEGC))) * HUM / 100)
    00020 HUMIDEX = DEGC + 5/9 * (PT1 - 10)

    To raise a number to the power of another you use the...
  32. Replies
    4
    Views
    497

    You need to delete the printer from System...

    You need to delete the printer from System Profile. Also there is an Insight Printer Service that needs to be disable and stopped. Once those are done you're all set.
  33. Replies
    1
    Views
    746

    Realy that simple. The virtual point doesn't even...

    Realy that simple. The virtual point doesn't even realy need to be created. IE:

    Panel 1
    Point: TEST1

    Panel 2
    Point: TEST2
    PPCL in panel 2 could be: IF ("TEST1" .EQ. ON) THEN ON("TEST2") ELSE...
  34. Thread: Siemens PXC

    by Merkas
    Replies
    6
    Views
    778

    Ethernet or RS-485 (P2)? The setup is different...

    Ethernet or RS-485 (P2)? The setup is different based on the communication type. Do you have a PC with a serial port and the MMI cable to connect to the panel?
  35. Thread: Siemens Insight

    by Merkas
    Replies
    2
    Views
    646

    Do you have full access? In other works do you...

    Do you have full access? In other works do you have config/edit to program editor and all access groups. You can check in the user accounts application. If so then you can upload the panel databases...
  36. you've got mail

    you've got mail
  37. Replies
    6
    Views
    1,005

    Graphics Cycler

    Had this same request from a customer just a while ago. If you don't need user interaction and just want a slide by slide display of dynamic graphics I used a free app called AutoHotKey...
  38. Replies
    14
    Views
    1,190

    I was an electrician by trade before I became a...

    I was an electrician by trade before I became a Service Automation Tech (non Union). With that said, on small service install jobs I'll install the controls, wire, program and build graphics. On...
  39. Replies
    3
    Views
    492

    Is this a windows XP machine. Check to see if the...

    Is this a windows XP machine. Check to see if the firewall is turned on iether the server or client. Try turning the firewall off and seeing if the alarms go though.

    Also check you destinations...
  40. Thread: Siemens Forum?

    by Merkas
    Replies
    6
    Views
    881

    I know the DAS's (District Automation Specialist)...

    I know the DAS's (District Automation Specialist) for Siemens us a fourm or blog for bouncing ideas off each other and swapping utilities. Was wondering if there was one for the techs?
  41. Thread: Siemens Forum?

    by Merkas
    Replies
    6
    Views
    881

    Siemens Forum?

    Are there any other Siemens forums iether on the internet or intranet?