  1. Replies
    15
    Views
    1,128

    heat problem

    Thanks for the last reply. I fixed it the thermostat was wired for a gas pack, and not a heat pump. I had to add a jumper between w2 and E to get the strips to kick on....WOW DOES THAT METER...
  2. Replies
    15
    Views
    1,128

    heat problem

    Yes we went from a 2 ton to a 2.5 ton
  3. Replies
    15
    Views
    1,128

    heat problem

    Yeah I never had a chance to respond to that because I was dumb founded about all the negative comments. I did do a lot of the work like tear out to save money. But a contractor friend of mine came...
  4. Replies
    15
    Views
    1,128

    heat problem

    yes he told me if I go to a 10 kw that I would have to pull a 60 amp line just for it. The problem is I have a 60 amp feeding two 30 amp breakers, thus the reason for only 5 kw.
  5. Replies
    15
    Views
    1,128

    heat problem

    I do have an amp clamp, and that was my thought too. I was going to see if it was on at the unit. Other than that its not heating up. Even my old unit had warmth coming out of the vents when in...
  6. Replies
    15
    Views
    1,128

    An hvac contractor installed a 5kw heat kit in my...

    An hvac contractor installed a 5kw heat kit in my heat pump packaged unit. The heat pump works and the ac unit works. However, when I kick the heat to Emergency heat, the air doesnt seem to get hot...
  7. Replies
    3
    Views
    723

    Ok I have a good one. I have a goodman 2.5 ton...

    Ok I have a good one. I have a goodman 2.5 ton heat pump packaged unit. This unit is brand new. I added a 5kw heat strip to the unit on install. I have a 30 amp breaker for the heat pump itself,...