  1. Replies
    3
    Views
    106

    Do you have an insight front end. You can also...

    Do you have an insight front end. You can also view PPCL and point database from the system profile.
    These devices are dinosaur and Siemens decided years ago to make them difficult to use by...
  2. The Siemens to Lon integration is bulky and at...

    The Siemens to Lon integration is bulky and at this point obsolete. They are pushing you to go BACnet because of this. Siemens will price this job so BACnet makes more sense. $$


    Sent from my...
  3. Replies
    4
    Views
    177

    I believe the 550-530 tec is a Lon heat pump...

    I believe the 550-530 tec is a Lon heat pump controller.


    Sent from my iPhone using Tapatalk
  4. It is easier for Siemens to push you to go...

    It is easier for Siemens to push you to go BACnet. There are several different ways for them to achieve this. All of them costly. What are your concerns?


    Sent from my iPhone using Tapatalk
  5. Replies
    10
    Views
    426

    There a many different sequences to control your...

    There a many different sequences to control your dampers. Simple control would be to control your economizer to maintain discharge are set point. You also have air quality control where you monitor...
  6. Replies
    7
    Views
    379

    These are Siemens apogee devices. You can do...

    These are Siemens apogee devices. You can do everything you need with the PXC controller. Unfortunately programming this will not be easy, for someone not familiar with PPCL, especially thru hyper...
  7. Replies
    2
    Views
    361

    I the research I have done is that the driver is...

    I the research I have done is that the driver is p1 devices only. I needed to install Siemens bacnet server and use the insight machine as a "gateway" in order to make this work.


    Sent from my...
  8. Replies
    17
    Views
    1,217

    Yes it has several different applications per...

    Yes it has several different applications per stat with different amount of relays per part number. The Kmc website also has an interactive demo


    Sent from my iPhone using Tapatalk
  9. If the only thing that has changed was moving the...

    If the only thing that has changed was moving the server to the new location, then this is where you have to start. Have you replaced the switch?
  10. Replies
    2
    Views
    256

    The pxcm is unable to connect, has anything...

    The pxcm is unable to connect, has anything changed on the network? Try a warm start (battery stays in)
  11. Replies
    3
    Views
    227

    You press it once in the middle to put it into...

    You press it once in the middle to put it into "hand" and a second time on either side to open or close the relay.


    Sent from my iPhone using Tapatalk
  12. Replies
    4
    Views
    318

    You will not be able to pull any point expansion...

    You will not be able to pull any point expansion into tridium. The point database resides in the field panel which is P2 communication. As of right now there is no driver for p2 only p1 which the tec...
  13. Replies
    6
    Views
    621

    Siemens Bacnet BBMD Help please?

    You need to have a BBMD configured on both subnets to route the BACnet packets across the router. You will need to have two in order to communicate. The chiller may have a BACnet table configuration....
  14. Replies
    16
    Views
    1,105

    Thanks Sam, My needs are a portable scope that...

    Thanks Sam,
    My needs are a portable scope that can be used to verify readings on customers RS485 trunks prior to integration. I'd like to be able to do screen captures on my laptop. I'm pretty...
  15. Replies
    16
    Views
    1,105

    Oscilloscope recomendations

    I have been given the green light to purchase a oscilloscope for our department. I would like to get recommendations.
    Thank you in advance.
  16. Best practice is to run your VFD with at least...

    Best practice is to run your VFD with at least three hard wired point, start/stop, status and your speed command. I don't like to pass the covs over the network.
  17. Replies
    1
    Views
    423

    N2 reference termination at Jace.

    what is the best practice for terminating the reference wire at the Jace. And also the proper grounding of the shield? is anyone using a 100 ohm PTC thermistor to terminate the shield?
  18. Your right dingman, thanks for clarifying.

    Your right dingman, thanks for clarifying.
  19. We're doing this integration. P1 to Jace. It...

    We're doing this integration. P1 to Jace. It helps that I am ex-Siemens. Each Fln truck can reside on a separate port. Any point expander ie DPU, mpu, bim and uc will not discover, and you will...
  20. The line in ppcl would be unresolved

    The line in ppcl would be unresolved
  21. Siemens: Unbundle FLN device points to field panel??

    Unless it's the day/night point it will need to be unbundled, in they system profile, I believe under tools.
  22. Replies
    8
    Views
    522

    Is the Emerson unit propriety communication? I...

    Is the Emerson unit propriety communication? I read nothing of open protocol in their spec.
  23. Replies
    1
    Views
    305

    Metasys UNT141 BI-4 Pulse configuration

    We are taking over a JCI system with UNT141 controllers and will be tying the N2 network to a JACE. I know that the UNT141 is capable of being configured as a pulse accumulator, but can not find...
  24. Replies
    3
    Views
    364

    It is a fume hood controller, I'll look around...

    It is a fume hood controller, I'll look around for the tech sheet.
  25. Replies
    37
    Views
    13,599

    Are there any PXC controllers that have manual...

    Are there any PXC controllers that have manual knobs like some MEC controllers? As in being able to manually modulate 0-10V output.

    Yes there is a part that takes the battery cover of the PXC and...
  26. I would have rather a customer change day night...

    I would have rather a customer change day night set points, CTL setpoint overrides these values and depending on the firmware in your tec, might not appropriately control heating amid cooling. He...
  27. If this were still a Siemens system they would...

    If this were still a Siemens system they would tell you to unbundle the points you would want to see on a graphic, in your case to be commanded form the jace. IYour network shouldn't have an issue as...
  28. You will need to unbundle these points thru hyper...

    You will need to unbundle these points thru hyper terminal.

    Sent from my DROID4 using Tapatalk
  29. What version of apogee and what type of...

    What version of apogee and what type of controller are we dealing with?

    Sent from my DROID4 using Tapatalk
  30. Are these points "unbundled" ? Sent from my...

    Are these points "unbundled" ?

    Sent from my DROID4 using Tapatalk
  31. Replies
    8
    Views
    737

    I'm doing a trane job now with about 300 trane...

    I'm doing a trane job now with about 300 trane uc400 and uc600s going thru a jace with no issues.
  32. Replies
    10
    Views
    813

    Keith, I haven't had an opportunity to throw it...

    Keith, I haven't had an opportunity to throw it in my station yet, but what you gave should do great. Thank you.
  33. Replies
    10
    Views
    813

    I'm actually reading a numeric point and using a...

    I'm actually reading a numeric point and using a multiplication block. The pulse accumulator discovered as a numeric point.
  34. Replies
    10
    Views
    813

    email added, thank you Keith.

    email added, thank you Keith.
  35. Replies
    10
    Views
    813

    Totalized gas usage in niagara

    I have a pulsed input that I am multiplying to get my adjusted gas usage. I want to get the usage broken down per month but can't seem to get it to reset on the first of the month. I am still very...
  36. Replies
    1
    Views
    407

    The trend collection time specified in scheduler...

    The trend collection time specified in scheduler determines how soon you will see data in your trend collection. If you need to see sooner info run a panel trend collection.

    Sent from my DROID4...
  37. Replies
    8
    Views
    613

    You know what I meant. Lol

    You know what I meant. Lol
  38. Replies
    8
    Views
    613

    I didn't even realize you said alc server, not...

    I didn't even realize you said alc server, not Shute whether you can do this, you may be able to talk to the controllers depending on you set up, but you can not have two masters.
  39. Replies
    8
    Views
    613

    What flavor BACnet, do you have the BACnet server...

    What flavor BACnet, do you have the BACnet server license?
  40. Replies
    9
    Views
    625

    That is exactly what I was looking for preciate...

    That is exactly what I was looking for preciate it!
  41. Replies
    9
    Views
    625

    I know to split it, trying to give the rock hard...

    I know to split it, trying to give the rock hard facts and not just "best practice" if they are anything more than half load devices it won't work.
  42. Replies
    9
    Views
    625

    Yes I have acquired a network that potentially...

    Yes I have acquired a network that potentially could have 75 uc400 and uc600s and over 5000 ft. Trying to talk them into splitting the network and not the band aid of repeaters.
  43. Replies
    9
    Views
    625

    Trane UC400/600 BACnet loads

    Are the uc400 and uc600 considered full load devices?
  44. Replies
    37
    Views
    13,599

    Telnet is hyper terminal via the command prompt...

    Telnet is hyper terminal via the command prompt over the Ethernet.
  45. Replies
    1
    Views
    275

    Hi "jmiranda" the spec states this as a 3000 ohm...

    Hi "jmiranda" the spec states this as a 3000 ohm sensor. I don't believe it is supported.
  46. I agree I'm not against a capable end user adding...

    I agree I'm not against a capable end user adding a panel to the system. But it's a little far fetched to ask professionals,that have years of training and experience, how to do their job on a forum.
  47. The hmi replaced the mmi in name only. Baud...

    The hmi replaced the mmi in name only. Baud rate can be anywhere from 9600 to 115200 at 8N1. Start with 115200 as that is the default.
  48. Replies
    37
    Views
    13,599

    Yes a license is required to be able to...

    Yes a license is required to be able to communicate Bacnet
  49. I am so confused as to what exactly you want on...

    I am so confused as to what exactly you want on this report. Sys activity log tells you when a point was commanded in operator priority, as you stated.
  50. Which front end? This question can have a handful...

    Which front end? This question can have a handful of different answers, do you have a Insight workstation and an Apogee field panel and you want a different solution?