  1. well 141F was inlet condenser temp... I did a...

    well 141F was inlet condenser temp... I did a check and found 500 psi head on startup led to a quick bypass and overload cut out. This freezer was running 250psi last visit for 30 min and drop box...
  2. im also thinking 141 not a reasonable temp if not...

    im also thinking 141 not a reasonable temp if not impossible..... no rla on unit so not sure if 8amps could trip OL. obviously need to find some more info tommarrow
  3. 404A cap tube

    404A cap tube
  4. not shiny but no visable buildup. good airflow

    not shiny but no visable buildup. good airflow
  5. Victory vf 2 freezer 2door standup digital display

    Erratic operation complaints.. found working normally on 1st call. 2nd call find display erratic/ throwing 20 different 2 digit codes but nothing close to any actual trouble codes. just jibberish. ...
  6. Replies
    3
    Views
    374

    OK I knew there was a simple answer I was...

    OK I knew there was a simple answer I was missing..... so control cuts in at 39 and cuts out between 22F and 9F based on setpoint of dial...:beat: thanks for the reply
  7. Replies
    3
    Views
    374

    constant cut in controls

    Specs on constant cut in controls got me scratching my head alittle. warm off 22 , normaloff 15, cutin off 39 and cold 0ff 9 Im thinking SPST switch unit will restart at 39F. when will it stop 9F?...
  8. Replies
    53
    Views
    2,805

    yep that's the plan now that ive

    yep that's the plan now that ive
  9. Replies
    53
    Views
    2,805

    This is working out well also. The staff has all...

    This is working out well also. The staff has all informed me they notice the difference. Lots of comments on how cold the beer is . Bartenders are rotating reach in Stock with walkin stock at the...
  10. Replies
    53
    Views
    2,805

    Went back today and found still running @ 34F ...

    Went back today and found still running @ 34F SAC Thank you for your input works great! Wow lots of replies here. I'm putting BEER in all my thread titles. This cooler is only for bottle beer.
  11. Replies
    53
    Views
    2,805

    Went back today after 3 days. Big improvement in...

    Went back today after 3 days. Big improvement in temp 38F no ice on coil. Decided to put bulb inside coil anyways as it makes more sense. I am pretty well convinced that the unit is operating...
  12. Replies
    53
    Views
    2,805

    No timer I feel I could solve this with one also....

    No timer I feel I could solve this with one also. It just has a LP safety. and tstat. You know if I go in this place and condemn everthing he will never call me back. He has been burned badly in the...
  13. Replies
    53
    Views
    2,805

    Yep you are angry... this is not behind the...

    Yep you are angry... this is not behind the owners back, I dont have time to explain further thanks for the reply
  14. Replies
    53
    Views
    2,805

    He's got a goldmine.... must be the women

    He's got a goldmine.... must be the women
  15. Replies
    53
    Views
    2,805

    Thanks again for all the input but like i...

    Thanks again for all the input but like i said.....''Customer not convinced he has a problem here so any more logical suggestions involving $$ will have to saved for later"..post#1 "The bulb in coil...
  16. Replies
    53
    Views
    2,805

    Im not running a coil below freezing in AC. If I...

    Im not running a coil below freezing in AC. If I was and all I had was a tstat and sensor, I would put this sensor somewhere where it could cycle unit off before an iced coil could reduce capacity.(...
  17. Replies
    53
    Views
    2,805

    Trying to make me think and guess what the...

    Trying to make me think and guess what the problem is? Im married I am very familar with this . I do realize the bulb is best in the coil to avoid freeze ups. My thinking was take it slow and...
  18. Replies
    53
    Views
    2,805

    Coils clean and did a complete check, plain and...

    Coils clean and did a complete check, plain and simple it is cycling off on temp before the beer is cold. The bulb in coil is just to show customer some 35 -38F beer. The employees and customers...
  19. Replies
    53
    Views
    2,805

    Beer Cooler 45F beer

    Walk in cooler R22 customer has no problem with 45F beer I DO. 25 yrs HVAC but no Refrigeration exp. Im new to this customer and could make some big points here or loose also. Huge bar 300+...
  20. Replies
    13
    Views
    1,326

    thanks looks great exactly what I was looking for...

    thanks looks great exactly what I was looking for thanks again
  21. Replies
    13
    Views
    1,326

    Industrial light cover what material is that made...

    Industrial light cover what material is that made of? Plus why hinges? Can u post a picture?
  22. Replies
    13
    Views
    1,326

    I was thinking of thin unistrut or even thinner...

    I was thinking of thin unistrut or even thinner steel channel but figured if i asked someone on this site had experimented with this and i could benefit from their trial and error.
  23. I am hoping its not a big deal I get alot of...

    I am hoping its not a big deal I get alot of great HVAC help from this site and dont want to be blacklisted... oops is blacklisted OK? no harm intended ThankYou
  24. I Knew when I posted this I was going to...

    I Knew when I posted this I was going to offend someone. I should have erased it then. Where I'm from this is so widely abused it really aggravates me. I don't Own a gun I never shot anyone nor do...
  25. Replies
    13
    Views
    1,326

    Van" Ceiling Shelf"

    Any ideas to lower inside van ceiling using that space created for small ladders, lineset rolls, pipe lengths, foldable hand truck Flat sheet metal ect. Kind of like raising the floor but from...