Search:

Type: Posts; User: climpro

Search: Search took 0.01 seconds.

  1. Replies
    7
    Views
    1,808

    http://www.trane.com/Commercial/LiteratureSearchLi...

    http://www.trane.com/Commercial/LiteratureSearchList.aspx
  2. Replies
    6
    Views
    1,502

    its cvhf-091 s\n L -02d0620651, ch-530...

    its cvhf-091 s\n L -02d0620651, ch-530 panel,leak tested thursday,recovery 1800 lbs R-123,changed elbow o-rings (RNG-1056,RNG-1107) and economiser flat gasket ( GKT-1925) just finished job...
  3. Replies
    6
    Views
    1,502

    trane cvhf-091 suction elbow leak

    leak = flanche suction elbow to evap, removed loctite , rust with fiber disk and acetone. what s best sealant,loctite 515 ,dowcorning 111, or gortex? I know no loctite 515 suction elbow...
  4. Replies
    23
    Views
    2,673

    call benshaw canada tech support = 1-519 291...

    call benshaw canada tech support = 1-519 291 5112 damn good support! http://www.benshaw.com/benshaw_canada.asp
  5. R-123 is HCFC , OEM phase-out = 01-01-2010...

    R-123 is HCFC , OEM phase-out = 01-01-2010 ?? what,s the future of R -123 ??????
  6. trane centravac chiller best-of the best award ??

    EPA has selected TRANE hcfc-123 centravc chiller for contribution to the protection of the ozone layer and climate changes ...
  7. Replies
    11
    Views
    991

    abs could you send me a copy my email is in my...

    abs could you send me a copy my email is in my profile

    thanks

    clim
  8. Replies
    16
    Views
    5,467

    BBusby i have a pdf copy 160.55-m1 form ...

    BBusby i have a pdf copy 160.55-m1 form optiview service instruction
  9. Replies
    58
    Views
    14,377

    esornivram I wanna installed txs on voyager...

    esornivram


    I wanna installed txs on voyager , send me youre jpgs and
    info my email is in my profile

    thanks

    clim
  10. Replies
    58
    Views
    14,377

    abs, I need your york tech support email and...

    abs,

    I need your york tech support email and phone .My email is in my profile

    Thanks

    Clim
  11. Replies
    17
    Views
    4,245

    deal

    deal
  12. Replies
    17
    Views
    4,245

    this service M manual isn,t available on www...

    this service M manual isn,t available on www york. com
  13. Replies
    0
    Views
    1,062

    york optiview 160.81-M1

    i need a pdf copy of this service teck manual =160.81-m1 ,it,s not available on www .YORK. com would you send my email is in my profile

    thanks

    clim
  14. Replies
    17
    Views
    4,245

    it,s rotary screw liquid chiller model=...

    it,s rotary screw liquid chiller model= yrbwbat2-53as s/n=snnm580292 , optiview controler ,solid state starter
  15. Replies
    17
    Views
    4,245

    optiview service manual

    Hey out there
    I have missed place my copy of service instruction 160.81-mi optiview service teck manual does any one have this in pdf
    let me know my email

    Climpro

    Thanks
  16. Replies
    13
    Views
    4,907

    scott 123 you,re Bolan trane guys?????

    scott 123

    you,re Bolan trane guys?????
  17. Replies
    14
    Views
    1,606

    pressure drop thru trane condensor coil is 30-50...

    pressure drop thru trane condensor coil is 30-50 psi (subcooling coil )higher amb temp +higher comp load=higher press drop
  18. mc1647 after youve changed oil filter got diag...

    mc1647 after youve changed oil filter got diag oil press transducer,set net oil pressure =22psid if transducer see 30psi youll get this diag , u need service bulletin cvhe-sb -32a ask copy...
  19. Thread: RTAC185

    by climpro
    Replies
    15
    Views
    1,727

    log teckview ,configuration window,starter,...

    log teckview ,configuration window,starter, desable test integrity and load configuration
  20. Replies
    8
    Views
    1,324

    LON card for ucp-2 rthb chiller isnt avalable ...

    LON card for ucp-2 rthb chiller isnt avalable from trane ,you must retrofit with ch-530 controls,this is the answer from factory trane pueblo ,i have same problem,expensive answer$$$$$$ stay with...
  21. Replies
    4
    Views
    1,742

    belimo parts =lf24-3r us ,it must be a 90 sec...

    belimo parts =lf24-3r us ,it must be a 90 sec opening motor
  22. Replies
    37
    Views
    4,195

    outside rep call Roger Richmond Smith...

    outside rep


    call Roger Richmond Smith ,Danfooss-Turbocor inc in Montreal phone= 1-514-421-0523,you,il know truth
  23. Replies
    37
    Views
    4,195

    I dont hav more info talk of town in LAX

    I dont hav more info talk of town in LAX
  24. Replies
    37
    Views
    4,195

    outside rep do you know why Multistack stop...

    outside rep


    do you know why Multistack stop production of Turbo-core on there chillers ????????
  25. Replies
    2
    Views
    1,287

    tigger i have 2 trane chiller model cckc-040 ...

    tigger
    i have 2 trane chiller model cckc-040 heat recovery with w-7100g controler,it,s old technology ,i had tried reset , problems oil return ,oil lost ,lock-out guard-pack , dont know...
  26. Replies
    18
    Views
    3,120

    ask your trane dealer a copy of start-up...

    ask your trane dealer a copy of start-up log,your first post ,looking at literature,look at page 110 iom bulletin rthd-svx01a-en ,i think trane must recovery r-134a charge ,change all relief...
  27. Replies
    18
    Views
    3,120

    chipper2 talk with my trane local...

    chipper2 talk with my trane local dealer ,Kestrel view software for ch-530 ,trend log , data log you can view what happend and download the file at factory trane.com for...
  28. Replies
    18
    Views
    3,120

    chipper2 I have on service pm 2 rthc with...

    chipper2 I have on service pm 2 rthc with ucp-2 in series , not rthd with ch-530 , desing, first unit ,54-49,sec chiller 49-44 ,first unit always shut-down over-load ,i called trane pueblo ...
  29. Replies
    15
    Views
    1,533

    had noisy rthc,replaced oil check vaive,poe oil ...

    had noisy rthc,replaced oil check vaive,poe oil charge , filter,not enough oil flow to rotor at start-up,move gaz pomp fill sol.on top near oil cold filter, chhc compressor service bulletin =...
  30. Replies
    15
    Views
    1,533

    jogas , you can overhaul the slide valve in the...

    jogas , you can overhaul the slide valve in the field ,if you want changed the compresssor, www tarrantparts.com ,i think they can help you,trane parts replacement.
  31. Replies
    8
    Views
    2,052

    on eagle cd ask your local trane dealer or...

    on eagle cd ask your local trane dealer or call trane lax service tch training Bob Roberts
  32. Replies
    8
    Views
    2,052

    neilvac check service bulletin cvhe-sb-32a...

    neilvac check service bulletin cvhe-sb-32a page 20 , i had same problem, changed high presur control and disable in field start-up settings, password= ++--++ ,enter
  33. Thread: Canatal units

    by climpro
    Replies
    22
    Views
    3,304

    jtricor canatal touch screen what is the...

    jtricor canatal touch screen what is the service pass word , what is laptop requirement
  34. Replies
    25
    Views
    2,039

    r404 chilled water pomps must stop,...

    r404 chilled water pomps must stop, check building b.a.s if pomps are not start and stop by chiller control panel,leak check purge sol. valves,r-123 in vent line??
  35. Replies
    25
    Views
    2,039

    steve638 install a rupturseal from ...

    steve638 install a rupturseal from redicontrols.com or a rupturgard from trane or york
  36. rudy ,low charge ,add refrig ,rot cvhe evap app...

    rudy ,low charge ,add refrig ,rot cvhe evap app is 7deg at 100% ,your chiller evap approach is 55 - 34.5 = 21.5 degs??? flow??
  37. Confortable air ...

    Confortable air your...
  38. Replies
    4
    Views
    1,455

    on tranet ,search, kestelview or call lax ...

    on tranet ,search, kestelview or call lax servicetech talk BOB ROBERTS
  39. Replies
    31
    Views
    3,530

    take a lap-top ,pro-windows X-P programe file ...

    take a lap-top ,pro-windows X-P programe file window recording and a microphone or mp3
  40. Replies
    31
    Views
    3,530

    the piston slide valve can be field repaired...

    the piston slide valve can be field repaired ,call PUEBLO service tech,talk to JOHN BASSET there,s service bulletin on it
  41. all sensors are not in wells you must have...

    all sensors are not in wells you must have service bulletins rtaa-sb-5 & rtaa-sb-9 5vdc powered 10k ohms at 77 neg temp coef thermistor
Results 1 to 41 of 50
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine