  1. Replies
    11
    Views
    570

    Just to follow up on this, the battery was not...

    Just to follow up on this, the battery was not bad. The supervisor at the site runs version 3.7 but the JACE panels are at 3.4. Viewing the info from the supervisor shows the battery failed but...
  2. Replies
    11
    Views
    570

    Thanks. Good info in there. Passing on to the...

    Thanks. Good info in there. Passing on to the tech who reported the battery issue.
  3. Replies
    11
    Views
    570

    https://lh6.googleusercontent.com/-3-LBVHUeAu0/U2z...

    https://lh6.googleusercontent.com/-3-LBVHUeAu0/U2zekVHa_cI/AAAAAAAAAe4/5My1zuUETQo/w476-h846-no/Jace.jpg

    I don't see any fuses on the board. The image is of a spare I have at my office.
  4. Replies
    11
    Views
    570

    The 5.4 was a typo but I a reply to correct it...

    The 5.4 was a typo but I a reply to correct it instead of editing the post.

    I thought IT500 was the generic Tridium name. My bad :) It is Niagara AX 3.4. It is one of the discontinued models...
  5. Replies
    11
    Views
    570

    It has been a few weeks now and the guy that went...

    It has been a few weeks now and the guy that went back by to check it said it was over 13vdc.
  6. Replies
    11
    Views
    570

    Bah! I'm speaking from the future :) 3.4 would...

    Bah! I'm speaking from the future :) 3.4 would be the version
  7. Replies
    11
    Views
    570

    JACE says new battery is bad. Why?

    It is an IT500 at version 5.4. Battery has good voltage yet the power monitor service still says the battery is bad.

    Any ideas?
  8. Replies
    5
    Views
    485

    Well i figured out why the bacnet spyder is...

    Well i figured out why the bacnet spyder is required. Looks like one of the VAVs on the 2nd floor was replaced with a Honeywell Spyder controller. One more quick question for the Alerton peoples;...
  9. Replies
    5
    Views
    485

    Sounds good. Thank you.

    Sounds good. Thank you.
  10. Replies
    5
    Views
    485

    I don't know why I need Spyder license either but...

    I don't know why I need Spyder license either but when I try to open the bacnet network with workbench it says "missing module honeywellBacnetSpyder on local machine". I copied the module from the...
  11. Replies
    5
    Views
    485

    Alerton VAV-SD Balancing

    We aquired a sick building that seems like it would benefit from calibration and re-balancing of the fan powered VAVs. The points required for this are not mapped into the Jace and due to not having...
  12. Replies
    0
    Views
    522

    Niagara AX App Failure - Strange Error

    This is a new one to me. I have corrected corrupted bog files before but this one is not related to the bog file as far as i can tell. I have loaded other stations into this FX60 but get the same...
  13. Replies
    59
    Views
    7,621

    By default the Sage & PUP devices do not use...

    By default the Sage & PUP devices do not use token passing but it can be enabled. If setup for token passing then there is no sole master and you could have the Sage and Jace online at the same...
  14. Replies
    5
    Views
    591

    Field technician.

    Field technician.
  15. Replies
    5
    Views
    591

    You are welcome. When i saw the alarm on my...

    You are welcome. When i saw the alarm on my phone and thought "you go girl, kick some ass!" i made myself laugh so i figured i would share.
  16. Replies
    5
    Views
    491

    There are only 2 places N30s belong. 1. Small...

    There are only 2 places N30s belong.

    1. Small simple jobs as a time clock.
    2. Garbage cans

    Without knowing what is in your box of crap i don't think anyone can point you in the right direction.
  17. Replies
    5
    Views
    591

    Proof that nothing can beat a NAE

    Got an alarm from one of our sites this morning proving my topic:

    5/9/2013 10:49:42 AM NAE-1 High Alarm CPU Usage
    Value 1e+006 %

    Most CPUs have to be dipped into...
  18. I think i have the issue fixed, or fixed good...

    I think i have the issue fixed, or fixed good enough until i hear back if there is something known to do about it.

    Where this machine may be a great server, it seems a bit light on the GPU side. ...
  19. Well that didn't help at all. It is not related...

    Well that didn't help at all. It is not related only to .px files though. For example, in the platform Application Director, moving the mouse up/down over the buttons on the right gives a...
  20. It runs great when logged into from another...

    It runs great when logged into from another machine but a bit sketchy directy at the server. Going back to swap a jace tomorrow so i'll give that a go and see if it helps. The guy at my office...
  21. New install Niagara 3.6 on Server 2008 has strange mouse "stuttering" issue

    Everything seems to work but whether i use IE or Workbench running on the server itself, when mousing across something on a px file or anything in the system that would show link data down in the...
  22. Replies
    1
    Views
    262

    FX07 not reading NRM ZT riddle

    Another tech i work with is dealing with this. The FX07 has a BACnet/MSTP card in it, controls a heat pump, is exactly the same is 12 others in the building, and has worked for over a year.

    Not...
  23. Replies
    2
    Views
    1,039

    Niagara AX Network Time Protocol kicking my butt

    Apparently we have been lucky for years on this as i have never given time sync much thought. We have two FX60s in a school district though that can't keep time well(migrating from NCMs slowly). ...
  24. Replies
    7
    Views
    671

    On my old WinXP laptop i had all the versions...

    On my old WinXP laptop i had all the versions installed and just copied the license file between them. I think the issue is as shown by ControlsInMT since the old version does not have a 64 bit...
  25. Replies
    7
    Views
    671

    Bah! I guess i'm not upgrading it then. I...

    Bah! I guess i'm not upgrading it then. I figure the host ID thing is due to the 1.2 version being 32bit only and the newer one having a 64bit installer.

    Thanks everyone for the feedback.
  26. Replies
    7
    Views
    671

    Jace version 3.0.106.1 upgrade issue

    I am trying to upgrade this FX40 to version 3.6 and when commissioning with my FX Workbench 4.0 it says i do not have the core software. I figured i need to do it in steps since it is old but my...
  27. DDC control of a Honeywell V4062A-1156 gas valve???

    I have been tasked to do this except the people tasking me thought that it was just a Hi/Low arrangement where this valve wired into a Raypack boiler has a series of relay/resistors to modulate it...
  28. Replies
    2
    Views
    549

    That is what i figured.

    That is what i figured.
  29. Replies
    2
    Views
    549

    Integrating Vector's CANape to Niagara AX?

    Has anyone ever done this? We have a customer that has a PC running CANape 10.0 that monitors some testing equipment. He would like to pass some of that data to the Niagara AX based system to...
  30. Replies
    8
    Views
    705

    Well the good news is that my SCT has time again...

    Well the good news is that my SCT has time again and seems to be working 100% correctly. My new road block is the NAE i think. Test login works but when i try to download it i get Communications...
  31. Replies
    2
    Views
    374

    Not sure if this is as reader's digest as you...

    Not sure if this is as reader's digest as you want but i typically do it this way.

    Export the existing points database using the job scheduler (points only)

    Copy that file to your PC/laptop and...
  32. Replies
    8
    Views
    705

    Thanks. I don't have the laptop i was using for...

    Thanks. I don't have the laptop i was using for this with me today but should be able to pick it up tonight and give it a try.
  33. Replies
    8
    Views
    705

    That would be great. I figured it was a DST...

    That would be great. I figured it was a DST thing but could not find anything that looked like it would help me. We are an ABCS but neutered on the NAE product for so long now that it is all very...
  34. Replies
    8
    Views
    705

    I used the NUT to get put the NAE at the same...

    I used the NUT to get put the NAE at the same version and logged into it afterwards and changed its IP address without and issues. The SCT works but down at the bottom where it normally shows the...
  35. Replies
    59
    Views
    7,621

    Sounds like you got the wrong number. AAM would...

    Sounds like you got the wrong number. AAM would certainly give you the closest local dealer's contact information.
  36. Replies
    8
    Views
    705

    SCT 2.0 java error. Patch? Help!

    Trying to get this version running in windows XP but i'm thinking there is a patch or something i am missing. The end result is i can not download the the NAE because my SCT does not know what time...
  37. Replies
    1
    Views
    466

    FX60 Not booting. Shell mode shows.....

    Press <ctrl-c> to stop autoboot...
    Autobooting...
    npm6xx startup version 0.06

    IPL for NPM 6 (PPC440EP) v0.08


    That is where it stops. I did this in rapid succession for a while unplugging...
  38. Replies
    3
    Views
    1,320

    SCT ActionQ broken x 2; How to fix?

    I just did and upgrade on an ADS with SCT installed and everything seems to run (finally) except when i try to download the database into the ADS it won't work.

    Test login says invalid login. If...
  39. Replies
    19
    Views
    1,370

    The Jace is also going to talk to some Liebert...

    The Jace is also going to talk to some Liebert siteLink panels over IP so i can't really turn that off.

    I found one of the LD1500 EOL switches was in mid position. Once it was on I had all the...
  40. Replies
    19
    Views
    1,370

    There are very few adjustable parameters...

    There are very few adjustable parameters regarding the bacnet protocol on the FX16 and the LD1500s so if anything i think sniffing the network may show the problem but there still may be no way to...
  41. Replies
    19
    Views
    1,370

    That is what i came up with as well :) I...

    That is what i came up with as well :) I literally just got off the phone asking if we had a com card handy at our shop before clicking the link that you had replied to my thread. I'll end up with...
  42. Replies
    19
    Views
    1,370

    All the devices are on the MSTP network. I found...

    All the devices are on the MSTP network. I found i have more of an issue though as th RLE devices don't stay online 100% of the time even with the FX16 disconnected.
  43. Replies
    19
    Views
    1,370

    BACnet Communication voodoo, please help!

    I have a FX20 talking BACnet to a FX16 controller in the same panel and out in the field i have 5 LD1500 leak detectors made by RLE technologies.

    With everything plugged in i can only see the...
  44. Replies
    8
    Views
    1,307

    It does say the baud rate is configured at the...

    It does say the baud rate is configured at the "global controller" so i'll buy into auto sensing. I'll talk to my guy that was out there and see what order he did things in and see if he got a look...
  45. Replies
    8
    Views
    1,307

    Honeywell Spyder BACnet VAV no talkie

    There were 8 of these installed with a com line run between them but no head end controller. We are trying to add that but can not communicate with them.

    We have tried from Jace and a few other...
  46. Replies
    0
    Views
    335

    Tridium ScheduleSelector Object issue

    I created something similar to this object in the past but it involved a lot of linking where using an EnumScheduleSelect is a much cleaner method.

    This issue is that it does not seem very...
  47. Replies
    1
    Views
    686

    Nevermind. I re-tried a statement i thought i...

    Nevermind. I re-tried a statement i thought i already tried and it worked.
  48. Replies
    1
    Views
    686

    BQLNumericRecap when you are a BQL idiot?

    Ok so i know how BQL works for many things in the program service for making mass changes and links and such. And i can use it to create tables to show various things in .px files. But i can not...
  49. Replies
    26
    Views
    1,554

    Sorry i missed your previous post about making a...

    Sorry i missed your previous post about making a GUI to replace NBPro. Sounds like you have to give up on that part of it for now and just make them viewable and jump into NBPro to make changes.
    ...
  50. Replies
    26
    Views
    1,554

    What is the end result you are looking for? From...

    What is the end result you are looking for? From the picture you posted it sounds like you want to change where a BO is getting its command from and you wish to select that from a Jace. How many...