  1. Check out Flexim. They are pricey but good. I...

    Check out Flexim. They are pricey but good. I just put a dual channel ultrasonic BTU meter on a chilled water loop and it is awesome! You can get all data via Modbus out of the meter.
  2. Replies
    2
    Views
    314

    That was it. Thanks!

    That was it. Thanks!
  3. Replies
    2
    Views
    314

    RTD Question

    I have an RTD that I need to reuse on an AHU. This reads the discharge temp on a gas burner. There is no part number in it. There is some info on the sensor that says RTD CO 1000 ohms @ 0 C 79457-1....
  4. Replies
    22
    Views
    1,452

    That wouldn't be in a public school in northern...

    That wouldn't be in a public school in northern Connecticut would it?
  5. Replies
    2
    Views
    269

    Sorry for the delayed response. That was it....

    Sorry for the delayed response. That was it. Thanks for the help!
  6. Replies
    2
    Views
    269

    Ax BACnet Export Write Fail

    I have a customer that is putting some demand based energy software into his facility and he wants to use it to command points in the Jace via BACnet IP. He can see all of my points and I have all...
  7. Replies
    0
    Views
    102

    Flexim AMD-7407 Modbus Integration

    Trying to figure out the registers on a Flexim AMD-7407 BTU meter. The factory was no help at all. Has anybody integrated to these before? Thanks in advance.
  8. Thanks

    Thanks
  9. You are correct. This is a Contemporary Controls...

    You are correct. This is a Contemporary Controls router. The problem is, I can't get it to scan into my device manager. I made sure I can get into the config through a browser, so I know the IP side...
  10. Alerton BACtalk Programming with IP to mstp Router

    Does anybody know if you can set up an IP to mstp router to be able to upload/download BACtalk controllers through Envision for BACtalk? I'm running a copy on my laptop with a valid key and I can't...
  11. Replies
    8
    Views
    373

    Sent you an email.

    Sent you an email.
  12. Replies
    8
    Views
    373

    I found the 1.8 disks. Is it on the auxiliary...

    I found the 1.8 disks. Is it on the auxiliary disk? What is the name of the program? Never throw anything away!!
  13. Replies
    8
    Views
    673

    You've got mail.

    You've got mail.
  14. Replies
    7
    Views
    403

    Got it! Thank You!

    Got it! Thank You!
  15. Replies
    8
    Views
    373

    I have a set of 1.8 utility disks somewhere in my...

    I have a set of 1.8 utility disks somewhere in my many piles of crapola. I'll look around and if I find it, I'll post it.
  16. Replies
    7
    Views
    403

    Thanks for the response. I like the way you...

    Thanks for the response. I like the way you think! Always striving to do things better. I'd like to see an example of the program object if possible. If not, I totally understand. I've been trying to...
  17. Replies
    7
    Views
    403

    BQL Information

    Does anybody have some good information on setting up BQL summaries? Thanks in advance.
  18. Replies
    8
    Views
    673

    Do you have access to the JCI FX site? One of the...

    Do you have access to the JCI FX site? One of the JCI FX guys posted a PWM module.
  19. Replies
    1
    Views
    193

    Never mind. Figured it out.

    Never mind. Figured it out.
  20. Replies
    1
    Views
    193

    Metasys GGT Question

    I have a customer that would like me to change all of the room names on the graphics and in the tree structure of the NAE's. How do I re bind the points in the GGT? I think they are using aliases....
  21. Replies
    1
    Views
    165

    Carrier Aquasnap BACnet Communications

    Does anybody have a list of BACnet points available for a 180 ton Aquasnap? I need to know what is writeable. Thanks in advance.
  22. Dave has a good point. I would go as far as to...

    Dave has a good point. I would go as far as to use a max version of 7 update 17. Personally, I would go with a new 30 and then you will have some support from your local supplier. What part of the...
  23. Replies
    6
    Views
    403

    Thanks for the replies! Very helpful information.

    Thanks for the replies! Very helpful information.
  24. Replies
    2
    Views
    244

    I just put a pop up binding on the bound label...

    I just put a pop up binding on the bound label and link it to that point's trend. FYI, I found a workaround in the Ax Community by using a drop down menu as the point label, then I can have multiple...
  25. The license is permanent and resides within the...

    The license is permanent and resides within the FX20, so it won't be locked. The Workbench tool is mostly complete, and you should be able to set it up in a browser. The reason that the 20 isn't...
  26. Replies
    2
    Views
    244

    AX Bound Label Pop Up Windows

    I have some bound labels that have pop up windows that show individual histories. My customer wants to have multiple pop up windows which he wants selectable from a drop down menu. I'm at a loss on...
  27. Replies
    6
    Views
    403

    Thanks for the reply. I don't know the version of...

    Thanks for the reply. I don't know the version of software or the exact model of the Tier 1 device. I just took over this facility and am trying to learn this system. I do know that there are KMD...
  28. Replies
    6
    Views
    403

    Figured it out. I needed to add a DALARM...

    Figured it out. I needed to add a DALARM statement to the program
  29. Replies
    6
    Views
    403

    KMC Total Control Alarms

    I'm trying to make a binary alarm email out to the in house guys. I have the input changing state properly and the class is set up just like all the other alarms that are working. The change of state...
  30. Is the network sensor set up for warmer/cooler...

    Is the network sensor set up for warmer/cooler adjust or setpoint? If it's set up for setpoint, that may be your issue. If you set it up for W/C, the program will spit out a writable point that you...
  31. Good point about the RAM issue.

    Good point about the RAM issue.
  32. Instead of writing to Present Value, try writing...

    Instead of writing to Present Value, try writing to 3113.
  33. Replies
    10
    Views
    1,772

    Wondering the same thing myself. I'm going to be...

    Wondering the same thing myself. I'm going to be doing an identical project in a few weeks.
  34. Replies
    29
    Views
    1,143

    I'm going to go out on a limb and say they sent...

    I'm going to go out on a limb and say they sent you 2 bad ones in a row. Wouldn't be the first time. This is a weird one. Please post the outcome. Good luck.
  35. Replies
    148
    Views
    4,426

    1) I Can Only Imagine 2) How Great Thou Art

    1) I Can Only Imagine
    2) How Great Thou Art
  36. Replies
    2
    Views
    220

    I believe that you need to configure the Site...

    I believe that you need to configure the Site Link for BACnet communications via hyper terminal with a 9 pin cable. There should be instructions in the manual on how to do this.
  37. Replies
    2
    Views
    368

    You've got mail.

    You've got mail.
  38. Replies
    14
    Views
    549

    Just go ahead and set up your station. When you...

    Just go ahead and set up your station. When you go live, if there is anything that doesn't jive, you can just do a discover on the LON network and match the right controller in the field to the right...
  39. Replies
    14
    Views
    549

    What type of field controllers do you have? You...

    What type of field controllers do you have? You will need to get the XIF files for them. I have built LON stations offline before. I have a LON PCMCIA card on my machine and I just discovered the...
  40. Replies
    3
    Views
    309

    You can use a line segment and re-create the...

    You can use a line segment and re-create the curve. Just set up the input as resistive and link to the line segment and you're good to go. I've done this with 3k sensors before and it worked fine.
  41. Replies
    12
    Views
    876

    Nevermind. I was misinterpreting the manual.

    Nevermind. I was misinterpreting the manual.
  42. Replies
    12
    Views
    876

    Wondering if anyone can help. I'm integrating to...

    Wondering if anyone can help. I'm integrating to a Lochinvar Knight via Modbus. Everything is talking and I'm able to see temps but how do I set up % points to read/write correctly? The book gives me...
  43. Replies
    10
    Views
    679

    On its way

    On its way
  44. Replies
    10
    Views
    679

    You've got mail.

    You've got mail.
  45. Replies
    10
    Views
    679

    I've got a copy. I'll find it and email it to you.

    I've got a copy. I'll find it and email it to you.
  46. Replies
    7
    Views
    584

    Thanks for the help. I'm already back at the old...

    Thanks for the help. I'm already back at the old rev and running fine. My support channel is working on a solution.
  47. Replies
    7
    Views
    584

    I did a clean dist and recommission. I tried...

    I did a clean dist and recommission. I tried everything multiple times with the same result. The license file doesn't say anything about sun. I think the customer is going to have to buy a new...
  48. Replies
    7
    Views
    584

    Yes. I verified that the license is at 3.8. I did...

    Yes. I verified that the license is at 3.8. I did look at the license file and there was no reference to sun anywhere. I took this site over from another contractor and they changed out a Talon Jace...
  49. Replies
    7
    Views
    584

    Jace Upgrade Issue

    I had a new one today. I upgraded a Vykon supervisor and 4 Jaces from 3.5.34 to 3.8. All went well until the last Jace. The station failed with an error "Feature sunj2se not licensed, station...
  50. Replies
    8
    Views
    580

    I saw the Loytec stuff online. Looks pretty good...

    I saw the Loytec stuff online. Looks pretty good as well. Do you have to be a dealer to buy?
Results 1 to 50 of 921
Page 1 of 19 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event