Search:

Type: Posts; User: OStaine

Search: Search took 0.01 seconds.

  1. Replies
    16
    Views
    3,096

    Try running it using internet explorer instead of...

    Try running it using internet explorer instead of firefox.
  2. Replies
    24
    Views
    2,675

    Had a fan motor making noise. I found the inner...

    Had a fan motor making noise. I found the inner race of the ball bearing turning on the shaft. That's because the bearing should have been a press fit instead of a clearance fit. That's just poor...
  3. Replies
    15
    Views
    1,944

    I've had some training and read some articles on...

    I've had some training and read some articles on this subject. There are strict guidelines concerning the application of hydrocarbon in supermarkets and there are strict guidelines to remove all...
  4. Replies
    15
    Views
    1,944

    Any one heard of "redtek"? Its the HC (R12a)...

    Any one heard of "redtek"? Its the HC (R12a) replacement for R134a . "Redtek" is not acetylene but its a hydrocarbon and it will fuel a fire. I wonder would happen if a vehicle charge with "redtek"...
  5. Replies
    5
    Views
    988

    Thanks for the Info. I found a Baker Dis.shop in...

    Thanks for the Info. I found a Baker Dis.shop in Doral FL., A manager by the name of Tony Peres. He had one so I arranged to have him fedex the oil level control to us, this is for the 10 hp...
  6. Replies
    5
    Views
    988

    Thanks for confirming that. I will replace...

    Thanks for confirming that. I will replace it.Have a great day , to day ! special thanks to tripointIO and jpsmith1cm :grin2:
  7. Replies
    5
    Views
    988

    sporlan oil level control

    sporlan valve OL-60XL; I got oil flowing up to inlet screen of control but not oil is filling crankcase. I check inlet screen but it not plug up . oil pressure in supply line to control is 40 psi....
  8. Replies
    29,825
    Views
    1,154,506

    Poll: have a great day FCS.

    have a great day FCS.
  9. Replies
    29,825
    Views
    1,154,506

    Poll: She is pretty. Can she take the top off and just...

    She is pretty.
    Can she take the top off and just cover with a manifold gauge ?
  10. Replies
    64
    Views
    5,567

    Stone fly, Thanks. Olson

    Stone fly,
    Thanks.

    Olson
  11. Replies
    64
    Views
    5,567

    Ok, I will send you one with the proper...

    Ok, I will send you one with the proper instructions but please allow some time as this will be costing me.
    Please dont order as yet from Smith Enviromentals as this info has not been released to...
  12. Replies
    64
    Views
    5,567

    ok . Send someone on a plane with test gear and...

    ok .
    Send someone on a plane with test gear and a camara, and I will let you test whatever you want.
    OK.
  13. Replies
    64
    Views
    5,567

    Are you ordering one? cause these now come with...

    Are you ordering one? cause these now come with the correct instructions.
    Olson
  14. Replies
    64
    Views
    5,567

    The installation instruction were wrong! Olson

    The installation instruction were wrong!
    Olson
  15. Replies
    64
    Views
    5,567

    Supply temperature : average 50.3F , Max 50 F,...

    Supply temperature : average 50.3F , Max 50 F, Min 48F
    Velocity : Average 852 ft/m , Min 826 , max 895
    Return Temp : 77.5 F
    TD :27.2 F
    Supply Temperature : Average 48.7 F , Max 49.2 , Min 48.2 ...
  16. Replies
    64
    Views
    5,567

    PHM, you are right. You cannot plot the SEER on...

    PHM,
    you are right. You cannot plot the SEER on a PH chart.
    You can however, plot a refrigeration cycle on one.
    my power quality meter is broken but the Engineer at the electric company will take...
  17. Replies
    64
    Views
    5,567

    Thanks for being objective. These are the...

    Thanks for being objective.
    These are the results I am getting.
    I will take some pics.

    If you need more info, just ask.

    Olson
  18. Replies
    64
    Views
    5,567

    Pressure entaphly Chart The refrigeration cycle...

    Pressure entaphly Chart
    The refrigeration cycle can be plotted on this chart.
    Knowing the following:
    Hi side pressure, low side pressure, Temperature of refrigerant entering evap(Before...
  19. Replies
    64
    Views
    5,567

    It looks a little different from that one. I...

    It looks a little different from that one.
    I send a pic later.
    olson
  20. Replies
    64
    Views
    5,567

    The problem with these devices was that the...

    The problem with these devices was that the installation instructions were wrong.
    I have made the changes and have been getting the type of reading I sent you.
    If the units are installed other wise...
  21. Replies
    64
    Views
    5,567

    condenser Goodman Model# CAL60-1L evap Pioneer...

    condenser Goodman Model# CAL60-1L
    evap Pioneer UG060DKA2LA
    mechnical device: artic master
    olson
  22. Replies
    64
    Views
    5,567

    This unit has 14 lb R22. and it has been running...

    This unit has 14 lb R22. and it has been running for two years.
    Please note the readings were taken at the same time and the TD varies between 28F and 32F.
    This is one of 10 unit running. I know...
  23. Replies
    64
    Views
    5,567

    supply and return air temp diff of 30F

    Discharge temperature out compressor 157.1F
    Suction line temp at compressor 64 F
    Air into condenser 84.3 F
    Air out condenser 96.9 F
    Air into evap 74.6 F
    Air out evap 42.9 F
    Refrigerant...
  24. Replies
    64
    Views
    5,567

    supply and return air temp diff of 30F

    I have install a mechanical device on a 5 ton a/c unit and i got the following results.
    Hi side 190 psi, low side 45 and am getting a 30F TD between supply and return. The fan is on high and the...
Results 1 to 24 of 24