Search:

Type: Posts; User: ddcfreek

Page 1 of 15 1 2 3 4

Search: Search took 0.02 seconds.

  1. Create a batch file with one line: NET...

    Create a batch file with one line:

    NET LOCALGROUP Administrators "[your domain here]\[your user name here]" /ADD

    Then add the batch file to your startup menu.


    Sent from my iPad using...
  2. Replies
    4
    Views
    338

    Try looking in the AxCommunity.jar Lots of...

    Try looking in the AxCommunity.jar

    Lots of useful things in there and I am pretty sure I saw that in there. If you don't have it yet just search google and you should find it pretty easily.

    ...
  3. Replies
    7
    Views
    314

    Nevermind they wired it to the wrong Jace. ...

    Nevermind they wired it to the wrong Jace.

    Sent from my SCH-I545 using Tapatalk
  4. Replies
    7
    Views
    314

    It was set to false, but changing it made no...

    It was set to false, but changing it made no difference. What I don't understand is why the Jace doesn't receive any service pin from these RTUs.

    Sent from my SCH-I545 using Tapatalk
  5. Replies
    7
    Views
    314

    Still get nothing at the Jace. I believe when we...

    Still get nothing at the Jace. I believe when we looked on Rover the domain length was 0 for the RTU and the Jace is at 2C.

    Sent from my SCH-I545 using Tapatalk
  6. Replies
    7
    Views
    314

    Yes but get no reply. I should add that we can...

    Yes but get no reply. I should add that we can see the entire network when we connect at the RTU.

    Sent from my SCH-I545 using Tapatalk
  7. Replies
    7
    Views
    314

    Trane LCI-I to Tridium

    Anybody ever have difficulty discovering a Trane LCI-I card on a WEB-403? It won't discover and the service pin doesn't show up at the Jace.

    Sent from my SCH-R530U using Tapatalk
  8. You need the ax wizards module in order to upload...

    You need the ax wizards module in order to upload the programming and see the points. You cant generate an xml with those.

    Sent from my SCH-R530U using Tapatalk
  9. Replies
    8
    Views
    1,178

    Can you send me the contact also. My email is in...

    Can you send me the contact also. My email is in my profile. Thanks.:bump:
  10. Replies
    4
    Views
    569

    You will have to put the jcin2.jar and other...

    You will have to put the jcin2.jar and other modules in your install folder so your workbench can see whats in the N2 network.
  11. Replies
    14
    Views
    1,526

    You can still use the Jace in the same way by...

    You can still use the Jace in the same way by leaving "Routing" on in your Bacnet Network setup. Then it will route all bacnet communications just like a router would. Best of all, I don't think...
  12. Replies
    6
    Views
    885

    If what you want could be done, I think a Bql...

    If what you want could be done, I think a Bql query would be the way. But I don't know if you can use bformat text that way. I am sort of trying to do the same thing.

    Anyone else have any ideas?
  13. Replies
    14
    Views
    1,526

    I have done this before, but Bacnet IP is alot...

    I have done this before, but Bacnet IP is alot easier with the NAE's. I just used a Contemporary Controls Bacnet router to serve the points. Far less expensive than a Jace.
  14. Replies
    5
    Views
    1,058

    Normally I start with a TR of three to five times...

    Normally I start with a TR of three to five times my setpoint and an integral of about 60 seconds. So if your setpoint is 1" I would start with a TR of 3-5.
  15. Replies
    20
    Views
    3,609

    I have seen this before, they probably want...

    I have seen this before, they probably want demand based ventilation with indoor ppm compared to outdoor ppm. When indoor ppm is say 700 above outdoor ppm then start increasing intake air volume. ...
  16. Replies
    11
    Views
    1,811

    Has anyone ever successfully had a Lynxspring...

    Has anyone ever successfully had a Lynxspring relicensed to be open?
  17. Replies
    2
    Views
    432

    The last line says it all, try loading a known...

    The last line says it all, try loading a known good station and see if it works. If it does, than the first one is junk. If it doesnt work, try reloading the os.
  18. Replies
    5
    Views
    610

    Wow, I didn't realize the gateway was such a...

    Wow, I didn't realize the gateway was such a loser. I guess I'm not surprized though.
  19. Replies
    5
    Views
    610

    I believe Wattmaster has some sort of Bacnet...

    I believe Wattmaster has some sort of Bacnet gateway available. I would look into that but it may be less expensive to replace the controls instead.
  20. Replies
    25
    Views
    2,336

    I was one of the beta testers for these displays....

    I was one of the beta testers for these displays. Our display shorted itself as soon a power was hooked up, so testing for us was short. As a result I wouldn't be able to tell you how well they...
  21. Replies
    12
    Views
    2,243

    This forum isn't for giving directions, if you...

    This forum isn't for giving directions, if you have a more specific problem or question you need help with we would be glad to help.
  22. Replies
    12
    Views
    5,290

    Me too Mike. Thanks!

    Me too Mike. Thanks!
  23. Replies
    13
    Views
    3,097

    If your going to use bacnet/ip, I wouldn't bother...

    If your going to use bacnet/ip, I wouldn't bother with an FX-60. Use another brand like Vykon with less crap loaded on it.
  24. Replies
    31
    Views
    2,464

    Spyders are not supported on 201's, not enough...

    Spyders are not supported on 201's, not enough horsepower.
  25. Thread: LON over IP

    by ddcfreek
    Replies
    24
    Views
    2,872

    There is only one lon channel and only one 600.

    There is only one lon channel and only one 600.