  1. I have seen what Jason has stated. It this...

    I have seen what Jason has stated.

    It this done with other zone type controllers. The zone controller becomes a "floater" no vote. Because these zone controllers use a supply air temp sensor, it...
  2. Replies
    1
    Views
    213

    History Point Lists Default View

    The default view for the history point list is live history chart. The user guide states -

    The default view of this component is the Live History Chart view. The property sheet view is where you...
  3. Replies
    4
    Views
    403

    Thanks for pointing me in the right direction....

    Thanks for pointing me in the right direction. Haven't been on site, but will try this.
  4. Replies
    4
    Views
    403

    Jace direct login? No username paswword

    I have a Jace running a house and have a PC and mobile interface. When connecting to the internal IP, I would like to set it up so the customer can one click in. The external IP of course would use...
  5. Replies
    5
    Views
    215

    Correctamundo! I got it I think. I found...

    Correctamundo!

    I got it I think. I found NumericCovTotalizerExt in the Vykon module. I then linked triggers and a schedule to it to reset. This little thing was driving me nuts all morning.
  6. Replies
    5
    Views
    215

    The are looking for the BTUs through a solar heat...

    The are looking for the BTUs through a solar heat exchanger.

    Only in an Excel spreadsheet. They want that duplicated on the front end.
  7. Replies
    5
    Views
    215

    BTU totals displayed on a Dashboard

    I need to create a dashboard displaying BTUs through a HX. The customer want to see hour, day, week, month totals. I am familiar with the calculation, however I can't seem to figure out how to...
  8. Replies
    11
    Views
    385

    For the ones I have opened, the customer had to...

    For the ones I have opened, the customer had to request it and pay for he license upgrade. From the service they were receiving, they were happy to pay.
  9. Replies
    11
    Views
    329

    It really depends on the system. I think I...

    It really depends on the system. I think I remember following different logic loops in LonSpec and seeing inputs were clearly missing from some blocks. Lonspec of course learned the block and the...
  10. Replies
    11
    Views
    329

    It has been awhile, but I don't remember being...

    It has been awhile, but I don't remember being able to upload referred points in LonSpec. The last time I uploaded a site, I had to redo them. Once you do any commission to a controller, the links...
  11. Replies
    6
    Views
    240

    Thanks for the input guys. I may need a lot of...

    Thanks for the input guys. I may need a lot of points, the goal is to use these as strictly point servers to get to the N2 devices. All supervisory programming would be moved up to the Jace.
  12. Replies
    6
    Views
    240

    I am not sure, I was told they are about a year...

    I am not sure, I was told they are about a year old. I won't be back on site for a while to check, anything in general to prepare for?
  13. Replies
    6
    Views
    240

    JCI NAE BacNet/IP

    If a site has a newer NAE, running the current software, with only one trunk N2, is there a limit to the number of BacNet/Ip points it can server up? Any limits on number of read points vs write...
  14. Replies
    2
    Views
    290

    You are going to have to ignore one on your slave...

    You are going to have to ignore one on your slave device. It is clear how to tie into your master device. If the terminal are not designated on the slave device, in about 6 tries or so you should...
  15. Replies
    20
    Views
    1,425

    Easy I/O, no VAV option.

    Easy I/O, no VAV option.
  16. Replies
    9
    Views
    546

    JCI LX series, which is re-branded Distech.

    JCI LX series, which is re-branded Distech.
  17. Thread: Easy IO 30P

    by Jay_T
    Replies
    0
    Views
    216

    Easy IO 30P

    Anyone here use this controller? Anyone use the Single Loop PID? I have two conditions with it.

    1- Maintains perfect setpoint, however when set point is lowered, never hits zero.

    2- This is...
  18. Replies
    3
    Views
    303

    Worked perfect. Thanks.

    Worked perfect. Thanks.
  19. Replies
    3
    Views
    303

    Batch History Count Change

    Anyway to change default count on all trends at once? Tried with Vykon tools and program service, no luck.
  20. Thread: BQL Search

    by Jay_T
    Replies
    5
    Views
    421

    Got it working. Thanks for the help guys.

    Got it working. Thanks for the help guys.
  21. Thread: BQL Search

    by Jay_T
    Replies
    5
    Views
    421

    Thanks guys. Been trying different versions of...

    Thanks guys. Been trying different versions of these. The bit of trouble I am having is the not part. When searching by display name or name bql doesn't seem to process the not.
  22. Thread: BQL Search

    by Jay_T
    Replies
    5
    Views
    421

    BQL Search

    I have a site that the zones points were named as follows-

    Zn1Tmp
    Zn1StPt
    Zn1FlrTmp

    The Zn number changes accordingly.

    I am trying to pull out just "ZnTmp" with BQL, I can't figure it out....
  23. Thread: Trane BCI-I

    by Jay_T
    Replies
    9
    Views
    464

    Verify the "System Control Command" is set BAS...

    Verify the "System Control Command" is set BAS control

    Verify you are writing to the "Economizer Minimum Position Setpoint BAS" and the points out of service property is set to false. This...
  24. Replies
    2
    Views
    278

    Thanks. That is what I was missing.

    Thanks. That is what I was missing.
  25. Replies
    2
    Views
    278

    NRIO Points Scales

    Here is what I have - loop point (PID) output to an analog out 0-10vdc.

    The loop point outputs 0-100, the analog accepts 0-10.

    I tried a linear conversion on the analog point, got an error...