Search:

Type: Posts; User: krac

Page 1 of 5 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    20
    Views
    507

    Got the official word from Liebert that the...

    Got the official word from Liebert that the Sitelink needs to be downloaded with the MSTP port configuration.
  2. Replies
    20
    Views
    507

    That screen shot was from another project that...

    That screen shot was from another project that had a Sitelink-12 with Port A setup for Modbus and connected to a Siemens system. The Bacnet connection was not used so we connected it to our Jace. ...
  3. Replies
    20
    Views
    507

    Sitelink is visible from the LGR-1000 Arcnet...

    Sitelink is visible from the LGR-1000 Arcnet connection, I am trying to move Sitelink over to a Tridium Bacnet MSTP network.
  4. Replies
    20
    Views
    507

    Worst part of this problem is having to tell my...

    Worst part of this problem is having to tell my local Liebert tech he was right!

    Thanks for the help.
  5. Replies
    20
    Views
    507

    Tried out the CM-Net on another Sitelink today...

    Tried out the CM-Net on another Sitelink today and not able to discover from my Bacnet device. Seems like I am missing something simple but don't see it.
  6. Replies
    20
    Views
    507

    Using Web-Ctrl all I can do is read points from...

    Using Web-Ctrl all I can do is read points from the Sitelink. I have another Sitelink in the office that I will setup and test the Bacnet connection. Not sure when this Sitelink was configured and...
  7. Replies
    20
    Views
    507

    Came backup on Arcnet with no issues. Switches...

    Came backup on Arcnet with no issues. Switches were all down. I will be back on site this week and give it another try. Only other thing I can think of is the Network ID's are not the same. This...
  8. Replies
    20
    Views
    507

    I shut the Sitelink down, moved the jumper then...

    I shut the Sitelink down, moved the jumper then powered it back up.
  9. Replies
    20
    Views
    507

    It's the Sitelink-12 2mb setup as ARCnet. I...

    It's the Sitelink-12 2mb setup as ARCnet. I tried moving the jumper and wasn't sure which dip switch that set the baud but I tried but 9600 and 38k speeds and was not able to discover the Sitelink. ...
  10. Replies
    15
    Views
    946

    I second debug69's comment about the level of...

    I second debug69's comment about the level of support from the Vykon channel being really good. At the Tridium summit the Easy I/O people were constantly saying the FG series was not designed to...
  11. Replies
    20
    Views
    507

    We are connecting the Sitelink to another system...

    We are connecting the Sitelink to another system and don't need connectivity to the LGR. The Sitelink is currently using CM-Net (Arc156) to communicate with the LGR1000. When I look at the Sitelink...
  12. Replies
    20
    Views
    507

    Under the Drivers tab on the Sitelink, I have the...

    Under the Drivers tab on the Sitelink, I have the option to select a port for MSTP or Modbus and save.
  13. Replies
    20
    Views
    507

    Sitelink-12 port setup

    Working at a site that has a Sitelink-12 connected to an ALC LGR1000 using the ARC156 Bacnet network and need to move the Sitelink-12 to a new Bacnet MSTP network. Tried moving the jumpers to...
  14. Replies
    3
    Views
    251

    http://www.ecsgroup.net.au/index.php?option=com_co...

    http://www.ecsgroup.net.au/index.php?option=com_content&view=article&id=106:ecs-group-slideshow-release&catid=77:news&Itemid=467
  15. Replies
    3
    Views
    251

    Spinwave was purchased by an Australian company...

    Spinwave was purchased by an Australian company this year and thought they were still supporting the product. That Modbus gateway has a Web UI that allows you to configure and view the devices...
  16. Thread: TAC Vista / Xenta

    by krac
    Replies
    21
    Views
    2,161

    Was on onsite at my new project this week and...

    Was on onsite at my new project this week and moved the LON network over to the Jace to see if we could discover any of the devices. Turns out several of the devices have been removed so all that is...
  17. Replies
    13
    Views
    623

    Don't feel bad I know a control tech that...

    Don't feel bad I know a control tech that connected a Jace to a Cummins generator that uses LON for their internal control bus and also commissioned the network. Needless to say the Cummins tech was...
  18. Thread: TAC Vista / Xenta

    by krac
    Replies
    21
    Views
    2,161

    Look at another site that did the same...

    Look at another site that did the same integration and the Non A controllers show up in the device list, but there are no points.

    Name Status Type Model Exts ...
  19. Thread: TAC Vista / Xenta

    by krac
    Replies
    21
    Views
    2,161

    Sounds like the modules without the A will work...

    Sounds like the modules without the A will work as LON devices, but we can change the I/O configuration which is ok

    From the drawings we have (2) 701's and (1) 913 that looks like a Modbus...
  20. Thread: TAC Vista / Xenta

    by krac
    Replies
    21
    Views
    2,161

    Looking at a similar project that has a bunch of...

    Looking at a similar project that has a bunch of 400 series module connected to some 701 gateways. Most of the modules are setup to monitor dry contacts and temp sensors. 3 modules are use to...
  21. Thread: Andover CX 9400

    by krac
    Replies
    6
    Views
    516

    Its been a while since I have used a terminal...

    Its been a while since I have used a terminal connection to a CX controller, (Thank God!) but if you can get connected (you will need login/PW) turn on your terminal program text capture and issue a...
  22. Replies
    3
    Views
    363

    The LGR1000 has three networks, local, 2401 which...

    The LGR1000 has three networks, local, 2401 which has bacnet devices, and 2402 which is connecting to the DataGuard network. Not sure how the WebCTRL Server connects to the LGR1000 but all I see is...
  23. Replies
    3
    Views
    363

    ALC LGR1000 Bacnet IP to Jace

    One of our customers recently took over a site that has what looks like an up to date WebCtrl server accessing a network of what looks like CMNet and Bacnet MSTP/Arcnet devices. Looking at the...
  24. Replies
    6
    Views
    572

    That is the standard Tridium power supply that...

    That is the standard Tridium power supply that depending who you purchase from costs over $110 which makes it one of the most expensive power supplies on the market for any application.
    For this...
  25. Thread: Jace Alternative

    by krac
    Replies
    8
    Views
    614

    If the existing controls are Bacnet MSTP checkout...

    If the existing controls are Bacnet MSTP checkout the Easy I/O FG-20. HTML-5, MSTP/Modbus support and should cost you around Pricing Removed From Post
  26. Replies
    6
    Views
    572

    Jace power supply options

    Working on a Data Center project that we need to mount the Jace 7 controllers in a 2 post equipment rack and need to find a 208vac to 15vdc power supply that will be installed in a UL listed panel. ...
  27. Thread: Niagara Summit

    by krac
    Replies
    22
    Views
    2,329

    The security outside the sessions was amusing....

    The security outside the sessions was amusing. Wonder how many other venders were trying to sneak into the sessions. I know I am losing sleep over the release of Niagara 4.01, even if it is 2 years...
  28. Replies
    16
    Views
    1,086

    The Fluke 125 S is a dual channel 40 mHz scope...

    The Fluke 125 S is a dual channel 40 mHz scope with a comm diagnostic function that made troubleshooting RS-485 networks for dummies like me real simple. Only problem is the price of $3000. The...
  29. Replies
    16
    Views
    1,086

    Rented a Fluke 125S which has a built-in function...

    Rented a Fluke 125S which has a built-in function for testing RS-485 and other serial types. The 125S quickly showed us the bacnet MS/TP bus had issues and allowed us to visual see the results of...
  30. Replies
    16
    Views
    1,850

    We are able to write values to AO/DO points and I...

    We are able to write values to AO/DO points and I think we can actually override them but have not tested that yet. Yes, the gateway needs a device address between 1 and 30, and the baud is 9600.
  31. Replies
    16
    Views
    1,850

    We are using the Maxline driver with the Easy I/O...

    We are using the Maxline driver with the Easy I/O gateway that is actually one of the Easy I/O FG-20 controllers that we had download the gateway firmware into. The Driver/gateway discovered all the...
  32. Replies
    16
    Views
    1,850

    We are in the process of moving a C-Bus network...

    We are in the process of moving a C-Bus network over to Tridium using a gateway and driver. Tested the gateway way out a few weeks ago and we were able to discover all the C-Bus devices and points. ...
  33. Replies
    12
    Views
    1,321

    I built Numeric bits writable as Hex address of...

    I built Numeric bits writable as Hex address of 10 with Numeric bits beginning bit 8 and number of bits 8.

    Since you are using Hex 10 is actual 0A, but figure you already have that covered.
  34. Replies
    8
    Views
    719

    We have a Fuji portable ultrasonic meter we use...

    We have a Fuji portable ultrasonic meter we use for flow testing. There is a company that sells a made in China ultrasonic meter that looked interesting: ...
  35. Replies
    12
    Views
    1,321

    This is a little different then most...

    This is a little different then most implementations but not that bad. You need to use Numeric bit point for the analog values (two for each address) with bits 0-7 for the low byte value and 8-15...
  36. I have played with the Notifier web interface and...

    I have played with the Notifier web interface and don't see anyway to edit or add a Bacnet device instance. When the gateway is restarted in goes through a discovery process (I captured the...
  37. Having the same problem with a Tridium to...

    Having the same problem with a Tridium to Notifier integration today. I can discover Gateway device, but the point discovery only shows enum (multi-state inputs) for the panel and a & b networks....
  38. Replies
    5
    Views
    670

    Wow reading this thread about Adaptive...

    Wow reading this thread about Adaptive Intelligent Recovery and figured I might learn something new, only to see an AC256 Drum program used as an example! Had to read it a couple of times just to...
  39. Great question!

    Great question!
  40. Thread: LON Null value

    by krac
    Replies
    2
    Views
    448

    The ENE Workplace Tech program in the MZ treats...

    The ENE Workplace Tech program in the MZ treats any value other than 1 as off. Just figured out that I can enter a value as sci notation. Entered 2e+038 as 2E38 in the slot and override is...
  41. Thread: LON Null value

    by krac
    Replies
    2
    Views
    448

    LON Null value

    Finishing up our ENE Lon to Tridium upgrade, and found some nVI points SNVT_count_inc_f (Type 52) that you can use to manual override equipment on off or auto. Problem is on=1, 0=off, and auto in...
  42. Replies
    21
    Views
    6,519

    We used the Maxline ASD driver on a recent...

    We used the Maxline ASD driver on a recent project with good results. The driver supports serial tunneling but haven't been able to make a reliable connection. I think the problem is with XPSI which...
  43. Replies
    43
    Views
    3,669

    For the JCI integration we used an FX-60 because...

    For the JCI integration we used an FX-60 because we know the N2 driver is solid. Found several VMA's offline and needed to troubleshoot an N2 bus wiring issue. For the ALC we left the Langate in...
  44. Replies
    43
    Views
    3,669

    Finally over the Invensys LON learning curve (at...

    Finally over the Invensys LON learning curve (at least I hope so) Found copies of all the Workplace Tech project files which allowed us to get a handle on what is going on inside the MZ's. Discovered...
  45. Replies
    43
    Views
    3,669

    Looks like the Node Utility program only works...

    Looks like the Node Utility program only works directly connected to the local lon bus. Is there an export function that is part of LonMaker running on the server?

    One issue I am having is not...
  46. Replies
    43
    Views
    3,669

    Looks like the XIF files used for the MZ's are...

    Looks like the XIF files used for the MZ's are not on the Server. Is there a way to export the Lonmaker database into a format that Tridium could use?
  47. Replies
    43
    Views
    3,669

    The system I am working on was installed in 2005,...

    The system I am working on was installed in 2005, and the newest building is 2010. You guys are not making me feel warm and fuzzy about the system we taking over. So your saying without the source...
  48. Replies
    43
    Views
    3,669

    Now that we have the LON discovery working the...

    Now that we have the LON discovery working the last thing we need to figure out is how to program MNL-800's. This is not something we actually have to do as part of our contract, but I feel bad for...
  49. Replies
    1
    Views
    478

    Not sure but if you look at the manual on page...

    Not sure but if you look at the manual on page 2-15 they talk about installing the communications card as an option. I would bet the switches are on the card.
  50. Replies
    43
    Views
    3,669

    Found some of the xif files in a working...

    Found some of the xif files in a working directory and the backup zip file, but the Device manager property sheet shows the xif path pointing to a CD for a few devices. I will give see if I can...
Results 1 to 50 of 218
Page 1 of 5 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event