  1. Replies
    6
    Views
    489

    I have added other existing points successfully,...

    I have added other existing points successfully, I'll try the bacnet point tomorrow

    Thanks
  2. Replies
    6
    Views
    489

    They are RC Points. The Mac address on...

    They are RC Points.
    The Mac address on controller "A" is 2
    The Mac Address on controller "B" is 1
    The Mac Address on controller "C" is 3

    I'm not a Reliable rep so I can't say with certainty...
  3. Replies
    6
    Views
    489

    Controller "A" is a MACH-Global Controller "B"...

    Controller "A" is a MACH-Global
    Controller "B" is a MACH-Global
    Controller "C" is an ETHER-Link
  4. Replies
    6
    Views
    489

    Reliable Controls System Groups

    I have a variable on controller "A". I'm trying to display that variable on a system group in controller "B". When I drag the point out and put it into "live" mode, the point value is correct, but...
  5. Replies
    9
    Views
    1,666

    There's an existing Reliable controls system...

    There's an existing Reliable controls system consisting of multiple Globals, Mach1's, procoms and 700 VAV controls. I'm looking to add a Jace(Distech-Controls) which will have 17 ECB-VAV controllers...
  6. Replies
    9
    Views
    1,666

    OK, I think I've figured it out, I just need...

    OK, I think I've figured it out, I just need confirmation that I'm doing it correctly. After entering the device ID, and point instance, I have to assign that to a Variable on the reliable system?
    ...
  7. Replies
    9
    Views
    1,666

    Just an extra bit of info, if I pull the point...

    Just an extra bit of info, if I pull the point out onto a Bacnet system group (Graphic) the value shows correct, it's only if I pull it out onto a Reliable system group that it shows the 0.000...So...
  8. Replies
    9
    Views
    1,666

    OK, my understanding of the BACset table is that...

    OK, my understanding of the BACset table is that most of the reliable controllers have the BACset tables in them. If my jace is not connected to any Reliable controler, but over BACnet IP, what...
  9. Replies
    9
    Views
    1,666

    No, I've put it into live mode and it does keep...

    No, I've put it into live mode and it does keep refreshing... On the reliable system, they're also pulling in bacnet points from a johnsons system and the same issue is happening there...so I'm...
  10. Replies
    9
    Views
    1,666

    Jace to Reliable controls

    So I have a Jace with 17 VAV controllers on the BACnet network. I've exported points from the VAV's to the Jace, and can see the Jace and the points over BACnet on the Reliable Controls system. If...
  11. Replies
    2
    Views
    739

    You may have already figured this out, but there...

    You may have already figured this out, but there is a block for this. It's called "NetInMinMaxAvgSum_1.1"

    You can find it in the Code Library under:

    gfxApplications -> 1.1 -> BACnet ->...
  12. Ya, I really wasn't thinking was I lol. Anyways I...

    Ya, I really wasn't thinking was I lol. Anyways I did shut
    down RC-Studio and ran BDT and it did find them all.

    Thanks
  13. Well, I ran the BDT on a PC on the same network...

    Well, I ran the BDT on a PC on the same network range because when I ran it on the OWS, it came up with the error "Another BACnet application is running on this computer" and it doesn't run
  14. I have found a BBMD table, however anytime I...

    I have found a BBMD table, however anytime I enter anything and send it, it just disappears...

    Thanks
  15. I must say I'm not familiar with BBMD, could you...

    I must say I'm not familiar with BBMD, could you please explain a little more.

    When i run the BACnet Discovery Tool, it discovers every single controller, so they are there...

    Thanks
  16. I will try the BACnet Discovery tool, but in the...

    I will try the BACnet Discovery tool, but in the mean time, does this work:

    There are 2 networks here: 192.168.1.x range and 192.168.2.x range

    The OWS is IP 192.168.1.123
    The Reliable...
  17. BACnet configuration settings are: Device...

    BACnet configuration settings are:

    Device ID...520
    Ethernet network...0
    B/IP Network...20

    Thanks
  18. So I've isolated everything on the network and...

    So I've isolated everything on the network and have just the MACH-Global in question connected directly to the OWS. I did a BACnet direct-connect and successfully logged in but the MACH-Global...
  19. The I.P. addresses of the controllers start at...

    The I.P. addresses of the controllers start at 192.168.2.1 and go up to 192.168.2.24. I can't remember what the PC is set at, I'll have to wait for Monday. SubnetMask is 255.255.255.0

    In...
  20. I know what the term 'Max-Master' means. I...

    I know what the term 'Max-Master' means. I worked with Reliable controls when I first started out and remembered that they have an option 'Last Panel' which always had to be set as the highest...
  21. The OWS and network controllers are all connected...

    The OWS and network controllers are all connected via ethernet to a router.

    By Max Master do you mean Last Panel for the Reliable system? If yes, then I do have it set properly.

    I'm thinking...
  22. if i log into M-set with RC-ToolKit and go to the...

    if i log into M-set with RC-ToolKit and go to the MACH-Global, SubA is set up for BACnet/Sub....Main network is also set for BACnet, unless I'm not looking at the right place?
  23. Sorry about the lack of information, this is the...

    Sorry about the lack of information, this is the setup:

    There's a 20-story office tower with with an existing Reliable controls using RC-Studio 2.0. Theres roughly 7 Ether-Links, a couple...
  24. Adding foreign BACnet device to reliable controls

    I'm trying to add a Distech BACnet VAV to an existing Reliable BACnet MS/TP network. Can anyone shed some light on this, if at all possible.

    Thanks