Search:

Type: Posts; User: D1G

Page 1 of 6 1 2 3 4

Search: Search took 0.01 seconds.

  1. Thread: WebCtrl Vs I-vu?

    by D1G
    Replies
    5
    Views
    1,197

    WebCTRL has all of the data types for CCN in its...

    WebCTRL has all of the data types for CCN in its database under /defs/ccn/. Support is most likely removed via a string in the license file but I've never personally tried so YMMV. There also...
  2. Replies
    42
    Views
    3,688

    You can access it without logging into the dealer...

    You can access it without logging into the dealer portal. I'm not sure that's "working as intended" but it's also not a child of accounts.automatedlogic so it seems intended to be public.
  3. Replies
    42
    Views
    3,688

    I think rellufnalla was talking about...

    I think rellufnalla was talking about EquipmentBuilder. It's a little gui, you select what type of equipment and answer a few questions (valves, stages, economizer type, single zone, multi-zone,...
  4. Replies
    57
    Views
    5,354

    Poll: Itchy clicky finger syndrome :) my apologies for...

    Itchy clicky finger syndrome :) my apologies for the double post.

    Browser to endpoint web technology doesn't negate the need for a server, it just moves the server to each end point which...
  5. Replies
    57
    Views
    5,354

    Poll: Both of my questions were more rhetorical than...

    Both of my questions were more rhetorical than anything but they'll ultimately determine if a project would be beneficial. Hence the reason I voted "I don't know".

    I'll take your OO example. ...
  6. Replies
    57
    Views
    5,354

    Poll: There are several open source projects in various...

    There are several open source projects in various stages of development, perhaps contributing to one of them may be a better route? Mango M2M (thx Digo) is a "complete" open source front end that...
  7. Replies
    31
    Views
    2,648

    Do they let Windows on their networks? I hear...

    Do they let Windows on their networks? I hear that platform has had a couple worms and viruses (including Stuxnet) target it over the years.

    That doesn't really make a lot of sense. Are they...
  8. Replies
    23
    Views
    2,419

    I'd have to agree with Sysint and Digo. This...

    I'd have to agree with Sysint and Digo. This isn't going to be as big a deal as some seem to think mostly because a lot of work has already been done and no one noticed.

    You have to look at...
  9. Replies
    23
    Views
    2,419

    Encryption, and by proxy of sorts authorization,...

    Encryption, and by proxy of sorts authorization, has been in the standard a while but without a defined method for key management. Because of this secure messaging hasn't been implemented. If...
  10. Replies
    14
    Views
    26,094

    To see if broadcasts are passing you can simply...

    To see if broadcasts are passing you can simply ping your device and spoof the source address with the broadcast IP, if you see a response broadcasts are being routed within the subnet. You'd be...
  11. Replies
    14
    Views
    26,094

    tcping...

    tcping is a great little simple tool that runs on windows easily and generally won't blow up your customer's IDS should you happen to typo a command.
  12. Thread: Bacnet tools

    by D1G
    Replies
    36
    Views
    5,379

    Wireshark has/had MS/TP support which is good for...

    Wireshark has/had MS/TP support which is good for basic protocol troubleshooting assuming you have a compatible interface.

    The Contemporary Controls USB interfaces are pretty nice and do a lot to...
  13. Replies
    7
    Views
    1,294

    I managed to make it seem a lot simpler than it...

    I managed to make it seem a lot simpler than it is. I assumed the intent would be obvious but I agree it's not. I was trying to imply that between SQL's tools and access to the application it's...
  14. Replies
    7
    Views
    1,294

    Is there a reason you can't use Osql to reset the...

    Is there a reason you can't use Osql to reset the password? Logged in as admin and assuming the admin group has admin SQL privs something like:
    START > RUN > cmd
    Osql -S <servername> (or -p...
  15. Replies
    12
    Views
    1,710

    BACpypes (http://bacpypes.sourceforge.net/) is a...

    BACpypes is a decent framework and it's written in python so it's easy to play with and extend. It also includes a few applications that are commented fairly well. It probably wouldn't be too...
  16. Thread: Is s Stuxnet real

    by D1G
    Replies
    34
    Views
    2,312

    So you're saying you install PLCs that can't be...

    So you're saying you install PLCs that can't be programmed? Doesn't that kind of defeat the purpose?

    In this case the software used to program the PLCs is "altered" when a Windows machine w/...
  17. Thread: Is s Stuxnet real

    by D1G
    Replies
    34
    Views
    2,312

    The Siemens products targeted do use the Windows...

    The Siemens products targeted do use the Windows platform for their head end DAS, OWS, and device configuration software.

    Technically the actual control device isn't being "infected" with a...
  18. Replies
    9
    Views
    636

    Without shadows looks far cleaner. The shadows...

    Without shadows looks far cleaner. The shadows in the other one are inconsistent, they look as if the sun were shining through the roof but from various angles.

    Now if you conditionally...
  19. Thread: NAE Upgrade Tool

    by D1G
    Replies
    9
    Views
    1,717

    You forgot to launch NUT with --work set. This...

    You forgot to launch NUT with --work set. This is required to have the software actually work, otherwise it just siphons money from your wallet.

    It's not actually documented and it only works...
  20. Replies
    50
    Views
    3,734

    That looks nice, is it one image or did you...

    That looks nice, is it one image or did you composite images together?
  21. Replies
    21
    Views
    1,617

    Do they crash & reboot or just hang from lack of...

    Do they crash & reboot or just hang from lack of resources as they attempt to send and subsequently recieve traffic as fast as the network will carry it? The smaller more resource limited devices...
  22. Replies
    21
    Views
    1,617

    Creating circular paths with BBMD tables is kind...

    Creating circular paths with BBMD tables is kind of fun and a common occurrence especially when you have multiple installers and vendors with varying levels of skill. Throw in FDR for a little more...
  23. Replies
    6
    Views
    2,129

    Since I can't edit.. I'd also add: Current...

    Since I can't edit..

    I'd also add:
    Current transmitters/transducers are most often used when current needs to be normalized to a "standard" span whereas a simple current transformer simply...
  24. Replies
    6
    Views
    2,129

    Current transformers are often used in revenue...

    Current transformers are often used in revenue grade metering of high voltage (>480V) circuits (e.g transmission systems). Here CTs (current transformers) and PTs (potential transformers) are used...
  25. Replies
    16
    Views
    1,520

    You could use physical layer failover switches to...

    You could use physical layer failover switches to build an N+1 fieldbus and use SNMP or a simple relay to control the failover. I've only ever seen them used in extremely critical control...