Search:

Type: Posts; User: GYUR22

Search: Search took 0.01 seconds.

  1. Replies
    5
    Views
    412

    I'd not say L-VIS easy to programm ;) ps As...

    I'd not say L-VIS easy to programm ;)

    ps As for me Weintek panels more easy to programm but they haven't advanced bacnet features like schedulers....
  2. sc-9100 looks like hard coded- different firmware...

    sc-9100 looks like hard coded- different firmware diferent language and functions
  3. Possibly they are configured as remote alarms...

    Possibly they are configured as remote alarms look into:
    Feature 41 - Alarm Route 450.20-CP2.41 (603) Pages 1 to 10
    Feature 42 - Alarm Configuration 450.20-CP2.42 (202) Pages 1 to 6
  4. We have another device - Modbus RTU cards for...

    We have another device - Modbus RTU cards for FX14/15/16 and FX07, so it's possible to use any Modbus TS
  5. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    1,196

    yes you need the image files with your version

    yes you need the image files with your version
  6. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    1,196

    Try to reflash w NUT

    Try to reflash w NUT
  7. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    1,196

    smallest file ;)

    smallest file ;)
  8. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    1,196

    Check this:...

    Check this:
    http://files.mail.ru/77A89297009D4C509869F52DC69A8212
    p.s. I can't attach file to message
  9. Thread: NAE Problem

    by GYUR22
    Replies
    14
    Views
    1,196

    looks like security system issue, check if you...

    looks like security system issue, check if you can use remote desktop
    ps ask guys from local JCI they shoud know
  10. Replies
    1
    Views
    357

    both because consists of two independent devices

    both
    because consists of two independent devices
  11. Replies
    5
    Views
    649

    1. remove associated w nae55 files from tftp...

    1. remove associated w nae55 files from tftp directory
    2. unzip from archive all files again
  12. Thread: NCE Question

    by GYUR22
    Replies
    23
    Views
    1,485

    1. NAE part Recomended object quantity on NAE...

    1. NAE part
    Recomended object quantity on NAE part of NCE :2500objects - including network objects
    Recomended network objects per ms/tp or n2 trunk : 1000
    So for example 1000 network objects...
  13. Replies
    10
    Views
    1,989

    yes http://files.mail.ru/237EN4

    yes

    http://files.mail.ru/237EN4
  14. Thread: FX05

    by GYUR22
    Replies
    1
    Views
    542

    NO mstp on Fx05,06 only on FX07

    NO mstp on Fx05,06
    only on FX07
  15. Thread: NAE animations

    by GYUR22
    Replies
    6
    Views
    587

    You need Advanced graphics package (it's a Visio ...

    You need Advanced graphics package (it's a Visio plugin) to make your own animation
    or only standart graphic with it's animated fan only
  16. Because of FEC for NCE and it's display siting on...

    Because of FEC for NCE and it's display siting on this bus
  17. As I can understand McQuay is third party...

    As I can understand McQuay is third party equipment for MSEA.
    You should try- go to Integration
    1.Add Field bus (if you have it don't need)
    2.Then add Bacnet on Field bus
    3. Scan network
  18. Replies
    3
    Views
    493

    I think you should care about M-Authorize patch,...

    I think you should care about M-Authorize patch, file name - M_Authorize 5.4.30 Patch.EXE (I can e-mail it)

    Bad thing that you need authorize M3 again
  19. Thread: JCI M3i

    by GYUR22
    Replies
    1
    Views
    548

    I have some installations My opinion - works...

    I have some installations
    My opinion - works well
    M-Graphics - perfect
    other parts M-alarm, M-Trend, etc- not so convinient
    EDE OPC- good convinient tool
    BACnet OPC - I have not BACnet systems...
  20. Replies
    9
    Views
    1,397

    You need YES or ICE and programm file for it

    You need YES or ICE and programm file for it
  21. Thread: FX upload

    by GYUR22
    Replies
    4
    Views
    638

    controllers like - FX16X - possible to upload,...

    controllers like - FX16X - possible to upload, FX16D - NOT
    They are even different in hardware
  22. Replies
    16
    Views
    5,479

    This may help

    This may help
  23. Thread: NAE issue

    by GYUR22
    Replies
    28
    Views
    1,797

    Try to put BACnet integration with you Fieldbus...

    Try to put BACnet integration with you Fieldbus as parent then discover
  24. Replies
    5
    Views
    709

    Thank you

    Thank you
  25. Thread: MS/TP under NAE

    by GYUR22
    Replies
    20
    Views
    1,552

    I tested York CX UDC on NAE R3.1 MS/TP trunk -...

    I tested York CX UDC on NAE R3.1 MS/TP trunk - it works
    but it was only a test not serious job
  26. Replies
    12
    Views
    1,320

    Objects restrictions: NAE35,45 - 2500 NAE55...

    Objects restrictions:
    NAE35,45 - 2500
    NAE55 -5000
    This mean overall objects in NAE

    I think you better go cgproducts.johnsoncontrols.com and search docs with words like: NAE, MSEA

    ps Example...
  27. Replies
    5
    Views
    709

    ddcfreek, Salmon_king Thank you I already have...

    ddcfreek, Salmon_king
    Thank you I already have xif and profile but not shure in exact variables
    for example CurrentA and CurrentD?
  28. Replies
    12
    Views
    1,320

    I have no statistics on NAE MS/TP, only N2...

    I have no statistics on NAE MS/TP, only N2 (previous experience on MS/TP was on Connexsys controllers)
    Every thing depends on points quantity, as for me ~ 1000 points or less per trunk and router...
  29. Replies
    5
    Views
    709

    Trane Integration

    Going to integrate 3 trane RTHD chillers with LCI-C LON card with JCI XTlon device to N2 interface. I'm not familiar with Trane and LON
    What for parameters:
    Base Loading Auto/on Request
    Base...
  30. Replies
    12
    Views
    1,320

    You can use BACnet IP router with NAE to make...

    You can use BACnet IP router with NAE to make additional connectivity or to speed up your comms
  31. Replies
    5
    Views
    694

    krac I did a same - changed export files then...

    krac
    I did a same - changed export files then tried to import them back - nothing imported R3.1

    steeve4
    NAE can Bacnet IP - you need to add: Integration ->BACnet then discover
    If you want...
  32. Replies
    5
    Views
    694

    Unable to save NAE's config with UI you need SCT...

    Unable to save NAE's config with UI you need SCT software
    As it seems to me you need additional BACnet router to get MS/TP data (am I right?)
    NAE can - BACnet IP
  33. Replies
    2
    Views
    498

    Open display, right click -System points and put...

    Open display, right click -System points and put 2 points Default color and Alarm color
  34. Replies
    3
    Views
    617

    Never had a same mistake FX06 adress is on...

    Never had a same mistake
    FX06 adress is on display, right click -System point
    I think it's not necessery to configure arrows - only if you want some exact action
    Check the firmware version
  35. Replies
    5
    Views
    622

    you need to map display and right click choose...

    you need to map display and right click choose System point ->Unit of measure
    then change it as you wish and place it on display (even if you have no display :))
  36. look object site parameters (toggle advanced...

    look object site parameters (toggle advanced view)
    1.BACnet site=true
    2.BACnet encoding=ASCII
  37. Thread: FX15?

    by GYUR22
    Replies
    4
    Views
    740

    So there are two major differences classic &...

    So there are two major differences classic & universal - you need to know which you have. Another step if you are not shure what firmware shoul be used, so you can write simple programm with 2-3...
  38. Replies
    8
    Views
    867

    Do you have any configured data on display string...

    Do you have any configured data on display string or value?
  39. Replies
    8
    Views
    867

    remove the onboard display and you will see

    remove the onboard display and you will see
  40. Replies
    8
    Views
    867

    only onboard display will work if you have it on...

    only onboard display will work if you have it on controller.
    You can remove it then try to connect remote dispay everything will be ok
  41. Replies
    12
    Views
    1,531

    My email in profile. Thank you in advance

    My email in profile. Thank you in advance
  42. Replies
    12
    Views
    1,531

    Send me too please!

    Send me too please!
  43. Replies
    5
    Views
    906

    Rev A. FX16 - only

    Rev A. FX16 - only
  44. Replies
    5
    Views
    906

    Rev A - marked controllers

    Rev A - marked controllers
  45. Replies
    2
    Views
    853

    may be you can use +15V reference from controler...

    may be you can use +15V reference from controler with 500ohms and your feedback as divider than configure input as 0-10v / 0-100% must be ok