  1. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    yea that building has about 60 units 55 are yorks...

    yea that building has about 60 units 55 are yorks 5 tranes the last two i worked on were trane . Fixed to leaks on the one in three weeks third time replaced condenser.
  2. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    dont know what it was but there was a good bit of...

    dont know what it was but there was a good bit of it.
  3. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    Dont know what it was black hard as hell crap.We...

    Dont know what it was black hard as hell crap.We were thinking compressor windings so we changed out compressor had about 4 inchs of liq line plugged. I felt like a jackass for not seeing the...
  4. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    Thought i would let you guys know that the liquid...

    Thought i would let you guys know that the liquid line was blocked almost completley shut about 10 inches from condenser. Running like a champ now.
  5. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    thanks for your help

    thanks for your help
  6. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    Yea its the first for me it has a another coil...

    Yea its the first for me it has a another coil that sits under the unit in the supply duct that the discharge goes through before it goes to the condenser. It has louvers that open and close on the...
  7. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    southern mech what does that mean?

    southern mech what does that mean?
  8. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    It was a parker filter dryer i think factory .

    It was a parker filter dryer i think factory .
  9. Thread: trane problem

    by brute1
    Replies
    20
    Views
    1,616

    trane problem

    looking for a little help. Im working on a 10 ton trane hot gas reheat morginizer. When the unit starts suction pressure drops so low it opens the lps and the unit shuts off with in 5 second pressure...
Results 1 to 9 of 9