07-02-2012, 10:30 AM
- Replies
- 51
- Views
- 2,507
To test the TXV actally place the sensing buld in...
To test the TXV actally place the sensing buld in a cup with ice then warn it up just to determinate if the valve is responding, if the valve is stuck wide open like you are suspecting, why the...
-
07-02-2012, 08:38 AM
- Replies
- 51
- Views
- 2,507
OT 50F , suction is a way high, remove the...
OT 50F , suction is a way high, remove the sensing buld and warm it up, with ur hand that should start to close the TXV, IF it does not, valve need to be repraced or the head.
Also due the the... -
06-15-2012, 06:59 PM
Thread: 410A System with high head
by ticotech cayman- Replies
- 17
- Views
- 1,145
Delta T across the coil is kind of high, it could...
Delta T across the coil is kind of high, it could be due to low air flow, and someone charged the system by pressure only, pressure low oh yes more refrigerant and more and mo:gah:re till it gets...
-
06-25-2011, 07:07 PM
Thread: 3 phase motor winding resistance
by ticotech cayman- Replies
- 15
- Views
- 3,634
Is it a chilled water AHU? Few week ago I...
Is it a chilled water AHU?
Few week ago I went to a service called, I found one of the fuse blown, the costumer told me that it wasn't the first time this happened,
The issue had been ... -
05-08-2010, 08:08 PM
- Replies
- 97
- Views
- 4,069
have the tranformer been replaced? maybe the VA...
have the tranformer been replaced? maybe the VA ARE TOO SMALL , LOOSE OR RUSTY CONECTION SOMEWHERE
-
04-02-2010, 04:41 PM
- Replies
- 12
- Views
- 2,016
yeah thats true.Good point
yeah thats true.Good point
-
04-02-2010, 04:31 PM
- Replies
- 12
- Views
- 2,016
with a axu 2 pole relay,kill the common of the...
with a axu 2 pole relay,kill the common of the fan and in the other contactor the yellow wire for cooling
-
03-30-2010, 08:39 PM
Thread: Causes of Negative Subcooling
by ticotech cayman- Replies
- 47
- Views
- 3,920
INTECBILL; IF the condenser is restricted the...
INTECBILL; IF the condenser is restricted the high pressure 'll increaes as well the compressor amps drawing , due to that , the widing temp 'll raise and the compressor overheats , but that...
-
11-06-2009, 06:26 PM
- Replies
- 26
- Views
- 1,549
normally the dip switches have one for cool and...
normally the dip switches have one for cool and other one for heat mode
-
10-05-2009, 10:04 PM
- Replies
- 26
- Views
- 1,677
make sure he , set the dip swicthes rigth , to...
make sure he , set the dip swicthes rigth , to mach out door unit.the grill siza is can of small too.
-
08-19-2009, 06:18 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
just check on post #2 its already explained over ...
just check on post #2 its already explained over there, why this happens / and the unit was a 2 ton corfort tech , the piston i think it was 23 i dont remenber but it definely was a lot smaller...
-
08-18-2009, 10:04 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
belive it or not the orifice works like this ...
belive it or not the orifice works like this larger piston = lower suction and higher head pressure, and smaller piston higher suction pressure and lower head pressures (in the same size evap), the...
-
08-18-2009, 09:02 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
ok now it has sence , thanks a lot for ur help,...
ok now it has sence , thanks a lot for ur help, one more last thing with a larger piston the suction pressure gets lower so I think if I AM not wrong , what happens in this case the refrigerant ...
-
08-17-2009, 10:33 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
oh and other thing ,was than the liquid line with...
oh and other thing ,was than the liquid line with a lower high head pressure felt warmer? I dont get it
-
08-17-2009, 10:29 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
thanks, that is what I was thinking about the low...
thanks, that is what I was thinking about the low side but i could not understand what was happening with the high side, now has sence thanks for ur help. what i dont get is why like u said smaller...
-
08-17-2009, 10:05 PM
Thread: fix orifice question?
by ticotech cayman- Replies
- 9
- Views
- 1,675
fix orifice question?
hey guys , I got a called the other day , costumer reported outdoor unit making a huming noise , I arrived to the place ,there was a little huming noise in the compressor , not too loud and I ...
-
07-09-2009, 06:41 PM
Thread: 3 phase wild leg?
by ticotech cayman- Replies
- 38
- Views
- 2,486
my bad !! lol
my bad !! lol
-
07-08-2009, 09:35 PM
Thread: 3 phase wild leg?
by ticotech cayman- Replies
- 38
- Views
- 2,486
a high leg won't affect the compressor in three...
a high leg won't affect the compressor in three phase system , check the rotation,must of 5 ton system have a single face motors. how was the pressures? was the compressor noise after stared it up?
-
07-01-2009, 10:52 PM
Thread: Please help me help my tech
by ticotech cayman- Replies
- 61
- Views
- 2,636
he changed the coil and few days later he found a...
he changed the coil and few days later he found a obstruction in the dryer, if he service it right the first day that would not ever happend . that seens to me just a bad installation and the tech...
-
07-01-2009, 10:28 PM
- Replies
- 11
- Views
- 435
i have done it , more like small refrigeartion...
i have done it , more like small refrigeartion aplications , when i dont have a label plate with amount of freon , but also checkin TD and pressures at the same time , this its just to make sure...
-
06-29-2009, 10:27 PM
Thread: Central AC with too much air?
by ticotech cayman- Replies
- 36
- Views
- 1,093
the manual will tell the min cfm for ur ahu, but...
the manual will tell the min cfm for ur ahu, but u deffinily have to check the system 's pressures. the compressor could be flooding with liquid freon and not necesary icing up at the evap.
-
06-29-2009, 09:55 PM
- Replies
- 18
- Views
- 751
some times what happends the drain is not glogged...
some times what happends the drain is not glogged its just than the drain line gets air lock specially the ones that coming under the house, cause makes like a kind of p -trap , put some water in...
-
06-29-2009, 09:43 PM
Thread: 5 ton RTU
by ticotech cayman- Replies
- 18
- Views
- 1,425
does the fan seen that is working full speed?...
does the fan seen that is working full speed? .... are the fan motor and fan blades originals or they have been replaced? I had a problem like that and the fan blade some other tech had replaced it...
-
06-29-2009, 09:32 PM
Thread: txv failure
by ticotech cayman- Replies
- 8
- Views
- 1,599
yeah it can fail totally closed , if the gas in...
yeah it can fail totally closed , if the gas in the sensing bulb leaks out , we need more info to help u out, is this system a dual system or single system?
-
06-28-2009, 06:55 PM
Thread: A coil Freezing
by ticotech cayman- Replies
- 32
- Views
- 3,628
THE FIRST TECH ADDED FREON AND THEN HE SAID THE...
THE FIRST TECH ADDED FREON AND THEN HE SAID THE PRESSURES IS TO HIGH , HUH ? YEAH IT SOUNDS LIKE A TXV PROBLEM , I WISH WE CAN KNOW THE PRESSURES READING.