  1. I've used these before to rescale to old...

    I've used these before to rescale to old actuators.

    http://workaci.com/content/arm
  2. Should be 2-15 VDC

    Should be 2-15 VDC
  3. Very first result in google searching for...

    Very first result in google searching for MA40-7170

    http://iportal.schneider-electric.com/Contents/docs/F-26742-5.PDF
  4. Yes very easy. The respective numeric data point...

    Yes very easy. The respective numeric data point does not have to be on the wire sheet, just link to each point and connect to the multiply block or whatever math block you are using. Are you...
  5. Replies
    17
    Views
    607

    I couldn't agree more. I would much rather be the...

    I couldn't agree more. I would much rather be the lone inconspicuous BMS.
  6. Replies
    0
    Views
    225

    VykonPRO Modules for 3.8

    Is there a 3.8 version of VykonPro modules and docs someone could send me that works in a non Vykon branded JACE? Emails is in my profile. TIA.
  7. Replies
    17
    Views
    607

    Are you a Distech dealer? There is specific...

    Are you a Distech dealer? There is specific information regarding securing EC-BOS's and EC-Net on the Distech partner site.
  8. Replies
    22
    Views
    1,933

    According to Lynxspring late July for N4 and late...

    According to Lynxspring late July for N4 and late September for the new JACE's with heavy caution these could change.
  9. Replies
    22
    Views
    1,933

    Tridium talk and a webinar from lynxspring as...

    Tridium talk and a webinar from lynxspring as well as the niagara summit breakout sessions
  10. Replies
    22
    Views
    1,933

    True. Sorry about that.

    True. Sorry about that.
  11. Replies
    22
    Views
    1,933

    No JAVA plugins in Niagara 4, HTML5

    No JAVA plugins in Niagara 4, HTML5
  12. Replies
    22
    Views
    1,933

    If you are using chrome version 42 it disables...

    If you are using chrome version 42 it disables NPAPI by default which JAVA uses. It can be re-enabled via a flag for now but Google has said that flag will be removed later this year.
  13. Replies
    11
    Views
    742

    rofl

    rofl
  14. Replies
    3
    Views
    266

    Have to change it in niagara network alarm...

    Have to change it in niagara network alarm service for a jace to use existing.
  15. Replies
    25
    Views
    1,595

    If only Sysint were here to provide true...

    If only Sysint were here to provide true perspective :grin2:
  16. Replies
    7
    Views
    997

    According to every company ever acquired nothing...

    According to every company ever acquired nothing is changing.
  17. Thread: Networking

    by controlgeek
    Replies
    8
    Views
    552

    :eek2:

    :eek2:
  18. Replies
    3
    Views
    396

    I would contact lynxspring and ask about this. I...

    I would contact lynxspring and ask about this. I have never heard of a locked down jene. Ask them to unlock it.
  19. Replies
    14
    Views
    1,320

    FA is a non branch device. It is a Facilitator...

    FA is a non branch device. It is a Facilitator and communicates on a proprietary Facilitator bus. It was the way JCI at one time would keep the ABCS and Branch separate.
  20. Thread: Niagara 4

    by controlgeek
    Replies
    6
    Views
    683

    At the summit last year they were talking about a...

    At the summit last year they were talking about a built in web browser in workbench also if I recall. Their big thing was tagging, device templates to easily duplicate systems, and tag searching.
  21. Replies
    16
    Views
    835

    Can you ping it?

    Can you ping it?
  22. Replies
    3
    Views
    345

    If you intend to use the dcimages library it is...

    If you intend to use the dcimages library it is restricted to a distech branded jace.
  23. Replies
    7
    Views
    497

    If I understand correctly licenses become open at...

    If I understand correctly licenses become open at the end of the year. The last time my R2 license updated it went to a 2030 expiration.
  24. Connect with serial shell and you can reset...

    Connect with serial shell and you can reset platform credentials.
  25. Replies
    1
    Views
    638

    To upgrade a program to 5.x it first needs to be...

    To upgrade a program to 5.x it first needs to be upgraded to 3.2 SP1 if it isn't already at that revision. 3.2 or 4.0 should run for 30 days under a demo license if you install on a new computer....
  26. Replies
    49
    Views
    3,246

    GPL is a separate dos based program that does not...

    GPL is a separate dos based program that does not come with M-Tools. It should be on the archive workstation and run from there as it references the compiled database. If it is not installed there...
  27. Replies
    49
    Views
    3,246

    If the reset is being done in the DX-9100 it...

    If the reset is being done in the DX-9100 it would probably be in a 4-Segment Program Module. The reset may be done in GPL or JC-Basic tho.
  28. Replies
    49
    Views
    3,246

    See the point mapping table on the attachment....

    See the point mapping table on the attachment. DX-9100 starts on page 47.
  29. Replies
    49
    Views
    3,246

    Generate a DMO file from the GXS and it should...

    Generate a DMO file from the GXS and it should list so you can reference the CS Object unddl.
  30. Replies
    49
    Views
    3,246

    DXS is the DX-9100 program files for the...

    DXS is the DX-9100 program files for the controllers. If you have the GX-9100 programming tool on the computer you can open those and see the tag names if they have them filled out and also see the...
  31. Check your mail.

    Check your mail.
  32. Replies
    49
    Views
    3,246

    The compiled DDL resides in the NCM. You can...

    The compiled DDL resides in the NCM. You can upload the NCM using PMI to the archive workstation and then unddl (decompile) it. The CS Model will reference points in a DX-9100.
  33. Have you checked out export tags?

    Have you checked out export tags?
  34. Replies
    49
    Views
    3,246

    The points will have been in a JC-BASIC or GPL...

    The points will have been in a JC-BASIC or GPL process and you would need the source code to see how it was being calculated. JC-BASIC is a line based *.BAS text file for source that is compiled to...
  35. Replies
    7
    Views
    479

    The Supervisor should be subscribed to the JACE's...

    The Supervisor should be subscribed to the JACE's to get the history data. If it were me I would evaluate what is being trended and modify (reduce trends or adjust periods or archiving time) so that...
  36. Thread: JCI

    by controlgeek
    Replies
    4
    Views
    458

    If it is the local branch refusing i would bypass...

    If it is the local branch refusing i would bypass them and call corporate parts line. I also would not feel bad posting on their social media sites.
  37. Replies
    8
    Views
    522

    History Groups are the way to go imo. The...

    History Groups are the way to go imo. The metabrowser is painfully slow at least for me. The batch editor is much faster.
  38. Replies
    42
    Views
    3,472

    The problem is they and others put proprietary...

    The problem is they and others put proprietary head ends and software on top of the "Fully BACnet compliant" controllers. Works great as long as the performance is good and the customer is happy. I...
  39. Replies
    42
    Views
    3,472

    Johnson is Proprietary BTW....Hope they do a good...

    Johnson is Proprietary BTW....Hope they do a good job where you are, where I am we pay more to not use them.
  40. Replies
    5
    Views
    624

    They are similar. Distech considers RDIO to be a...

    They are similar. Distech considers RDIO to be a configurable controller (i.e. ECC-301). It has no internal logic and you would use Niagara to perform logic and send it over the network to the RDIO...
  41. Replies
    5
    Views
    624

    Distech does not sell the RDIO product or the...

    Distech does not sell the RDIO product or the IO-485 NRIO products in looking at their website and the new pricelist starting in March. Other non Vykon distributors do like Lynxspring so I don't...
  42. Replies
    4
    Views
    624

    DT-9100

    DT-9100
  43. Replies
    5
    Views
    426

    Ive heard good things about ecobee but dont have...

    Ive heard good things about ecobee but dont have any direct experience yet
  44. Replies
    1
    Views
    365

    Do you need to demux it first?

    Do you need to demux it first?
  45. Replies
    8
    Views
    700

    Belimo and KMC both rebrand actuators but I'm...

    Belimo and KMC both rebrand actuators but I'm sure they are not the only ones.
  46. That indicates it is not seeing the wizard...

    That indicates it is not seeing the wizard application for the controller. Did you checkoff installing the configuration wizards on the EC-NET AX tab in smart installer? I believe the wizard service...
  47. That is the Maxline Solutions driver previously...

    That is the Maxline Solutions driver previously sold by EasyIO.
  48. Schneider Electric if you are a dealer or Maxline...

    Schneider Electric if you are a dealer or Maxline Solutions if not:

    http://maxlinesolutions.com/index.html
  49. Replies
    2
    Views
    446

    I don't have any specifics but I believe Climatec...

    I don't have any specifics but I believe Climatec acquired that office by acquiring Cohesive Automation in the last year or two.
  50. Assuming it is a Staefa Smart II System you could...