  1. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    i understand what your saying TF12 but in my...

    i understand what your saying TF12 but in my situation the head pressure is a little high and also the suction pressure is high but my amps are low?????? and also with my suction being so high could...
  2. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    thanks for the relies and i did check the pump...

    thanks for the relies and i did check the pump down on it and it came to a 10" vacumm and the LL temp leaving the condenser was 100 degrees
  3. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    thanks again icemeister for taking the time to...

    thanks again icemeister for taking the time to help me out
  4. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    and also one more thing that puzzles me is why is...

    and also one more thing that puzzles me is why is the amp draw suppost to be so much lower then the RLA rating yet i would think with the pressures being high it should make me think it should be...
  5. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    thanks icemeister for the info... is there a link...

    thanks icemeister for the info... is there a link or some way to get these performance charts for different compressors? thanks again
  6. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    404a cleaned the condenser and 90...

    404a cleaned the condenser and 90 ambient....for what its worth the rated RLA are 11.4
  7. Thread: weak comp?

    by jat2020
    Replies
    21
    Views
    774

    weak comp?

    this is for a walk in freezer just wondering if someone could run the numbers to see if i got a weak compressor?
    copeland model CF06K6E-PFV-253
    suction pressure 28lbs
    discharge pressure 325lbs...
  8. Thread: Manitowoc

    by jat2020
    Replies
    13
    Views
    1,574

    i would replace the curtain switch if it wont...

    i would replace the curtain switch if it wont shut off, also a thought about the clicking noise you hear, is it the compressor overload you hear?
  9. Replies
    20
    Views
    1,946

    this is just one of those ice machine and bin all...

    this is just one of those ice machine and bin all in one deals right? if so i was told by tech support once that its part of the normal cycle and will eventually start pumping water give it a couple...
  10. Replies
    16
    Views
    2,479

    first thing that comes to mind is its the...

    first thing that comes to mind is its the thermister not taking machine out of defrost i would also make sure that during the night when no one is using hot water that its not migrating to the ice...
  11. Replies
    28
    Views
    2,383

    is copeland the ony manufacturer that has...

    is copeland the ony manufacturer that has performance charts or can u get them from tecumseh too
  12. Replies
    56
    Views
    5,604

    "I was convinced of it when I got the static 305#...

    "I was convinced of it when I got the static 305# with 99F air on the condenser. Then after it cooled off and started, seeing the out of sight head, cool LL and no overcharge clinched it for good."...
  13. Replies
    42
    Views
    2,736

    the refrigerant is 134a and i did weigh it back...

    the refrigerant is 134a and i did weigh it back in after changing out the filter drier and i did push nitro from hight to low and it did flow through it, and i think your right it was about 18 ozs...
  14. Replies
    42
    Views
    2,736

    ya i agree with u guys head pressure should fall...

    ya i agree with u guys head pressure should fall with a resticted cap tube, actually i thought my pressures looked good too but just couldnt see why me liquid line was still so hot and the suction...
  15. Replies
    42
    Views
    2,736

    ya thats why im thinking partially plugged cap...

    ya thats why im thinking partially plugged cap tube. but it seems to cool the box quickly. ive heard differnt techs say differnt things about plugged cap tubes and the effects on head pressure, some...
  16. Replies
    42
    Views
    2,736

    having cooler problems

    working on a superior 3 door cooler. got there and found liquid line way to hot felt like the discharge line. condeser plugged solid. cleaned coil started unit back up unit come down to temp but the...
  17. Replies
    26
    Views
    2,054

    talked to tech support said to hook up both red...

    talked to tech support said to hook up both red wires from magnetic switches to ground and turn machine on and if it starts the switches need to be replaced or the one i didnt replace but if it...
  18. Replies
    26
    Views
    2,054

    well i got the model # its qydual4c

    well i got the model # its qydual4c
  19. Replies
    26
    Views
    2,054

    sorry about no model # will try to get it and...

    sorry about no model # will try to get it and post it but i do know that this machine is only about 1.5 years old and the manager said that the board has already been replaced once and i saw where...
  20. Replies
    26
    Views
    2,054

    manitowac problem

    working on this ice machine duel evap it keeps shutting down and styaying off until its reset by either the on off switch or the curtain switch but is not giving me any safetys lights. once it shuts...
  21. Thread: hoshizaki

    by jat2020
    Replies
    7
    Views
    1,578

    hoshizaki

    to increase ice thickness do u raise or lower the float assembly
  22. Replies
    24
    Views
    2,203

    were your gauges leaking by

    were your gauges leaking by
  23. Replies
    24
    Views
    2,203

    were your gauges leaking by?

    were your gauges leaking by?
  24. Replies
    24
    Views
    2,203

    read through entire post and thought i wonder if...

    read through entire post and thought i wonder if the refrigerant was going through your gages from high to low side. just a thought
  25. Thread: trane

    by jat2020
    Replies
    4
    Views
    603

    trane

    just wondering if anyone knows of any good links to explain trane contols for a rooftop a/c unit like differnt spects and what voltage reading your suppost to get at different points in the...