Search:

Type: Posts; User: iceboxer449

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Thread: BBQ Sauce

    by iceboxer449
    Replies
    19
    Views
    2,622

    Sounds good. Never tried it. I'm a sweet baby...

    Sounds good. Never tried it. I'm a sweet baby rays fan when in a pinch.
  2. I would check your hot gas temp at your cases and...

    I would check your hot gas temp at your cases and hot gas diff valve. If you dont have flow or proper diff you can fill the coil with liquid. If you have coffin cases check for ice. Do you have...
  3. Replies
    2
    Views
    396

    http://www.emersonclimate.com:8765/ctppub/query.ht...

    http://www.emersonclimate.com:8765/ctppub/query.html?col=ctppub&qt=reflecs
    Im sure u have probally checked cpc website but the are some upgrades available. See if customer will go for and E2;) now...
  4. Not changing them in the feild, they are being...

    Not changing them in the feild, they are being used on new installs and all new equipment being ordered
  5. In my area we have switched to the A4a valve (...

    In my area we have switched to the A4a valve ( its huge) but so far more reliable. It also has very little pressure drop across it when full open where as ive seen as much as 5psi on a A2BL when full...
  6. Replies
    18
    Views
    2,763

    wow nice install. You do not even have to bend...

    wow nice install. You do not even have to bend over to put your gauges on, wish they all could be this way:eek:
  7. Replies
    28
    Views
    2,267

    That rachet cutter can get u out of a jam. ME...

    That rachet cutter can get u out of a jam. ME LIKE:D
  8. Replies
    20
    Views
    840

    This should be a great cup. But I must say GO...

    This should be a great cup. But I must say GO PENS !!!!!!!!!!!!!:D:D:D:D:D
  9. Replies
    42
    Views
    3,255

    I would agree with JP. If all that checked out, I...

    I would agree with JP. If all that checked out, I would check for clogged sentronic screen while checking pick up screen, systems blowing back during hot gas defrost, and even switching ofc control...
  10. Thread: ultrasite?

    by iceboxer449
    Replies
    17
    Views
    1,386

    virtual mode displays on your laptop as if your...

    virtual mode displays on your laptop as if your were standing at pc. The key strokes are the same as if you were at the cpu. As you know ultrasite looks completley different than the actual screens....
  11. Replies
    28
    Views
    2,267

    I don't use them every day but I have two ridgid...

    I don't use them every day but I have two ridgid cutters that I have had for over 10 years. They out lasted my imperial but it also preformed well for medium use.
  12. Replies
    16
    Views
    728

    Yea, customer wants to wait till friday at...

    Yea, customer wants to wait till friday at midnight to agree to oil change. Also the inhouse maint does not check sump screens because " oil float is full " usually find them sucked closed and...
  13. Replies
    8
    Views
    786

    Have any white rubber roofs. target stores in my...

    Have any white rubber roofs. target stores in my area use them. The reflective light is blinding.:eek:
  14. Replies
    16
    Views
    728

    Low temp 22 with demand cooling. I have had major...

    Low temp 22 with demand cooling. I have had major problems with the white teflon seat in the demand cooling valve holding the valve open. It then proceeds to blow out the reeds. If you are not having...
  15. Replies
    33
    Views
    1,545

    I hate know it alls. We all have our specialties...

    I hate know it alls. We all have our specialties and still have room to learn in our respective day to day encounters. Its such a diverse industry and it supplies the ability to humble us all and...
  16. Replies
    16
    Views
    728

    Were they the new style where the reeds are fixed...

    Were they the new style where the reeds are fixed or the old style where the reeds were removable. On the old style the reeds would wear an oval where they sat on the pins after time they would work...
  17. Where were the condensing units located ( how far...

    Where were the condensing units located ( how far from evaps ) regaurdless 70* is high. I would pump down and check txv strainers since the oil looked "cruddy" before I would start adjusting...
  18. Replies
    51
    Views
    3,312

    Cool stuff!!!!! I have a hard time finding...

    Cool stuff!!!!! I have a hard time finding seashells:)
  19. Replies
    38
    Views
    2,563

    Ribeye is hard to beat, but a porterhouse you get...

    Ribeye is hard to beat, but a porterhouse you get two cuts YUMMMMM
  20. Replies
    125
    Views
    9,122

    Tried sushi twice. NO MORE guess i dont have that...

    Tried sushi twice. NO MORE guess i dont have that refined taste. Catfish like it though and I will fry one of them up.:eek:
  21. Replies
    25
    Views
    1,388

    Never seen that before. I have almost all...

    Never seen that before. I have almost all hussmann racks in my area and never have even heard of such a rack. Just doesn't make sense, would like to know what hussmann says. I would try to convince...
  22. Thread: Fluke 902

    by iceboxer449
    Replies
    39
    Views
    2,376

    Good general purpose meter, use it daily. The...

    Good general purpose meter, use it daily. The hold button is anoying but still a recomended purchase.
  23. Replies
    8
    Views
    1,205

    New way to repair a 3-way valve

    Was ask to evaluate a small chain of stores and how the equipment was being maintained. Found this gem in the first store in the first 2min. Needless to say the list was long.
  24. Thought that transformer for the fiberoptic hand...

    Thought that transformer for the fiberoptic hand held looked familiar. I just switched a store over that had five racks with the old epc's. Had to solder all the circuit branch board jumpers back in...
  25. Replies
    17
    Views
    1,152

    if they were very negelected I would use some...

    if they were very negelected I would use some rust preventer before you paint. It usually shows on the receiver and suction service valves. A wire brush also goes a long way.