  1. Final resolution/conclusions

    Inducer motor has been replaced and unit has run for two hours with no problems. Previously it reset within about 15 minutes predictably. If I hit any issues in the future, I will call on a...
  2. Temperature rise and blower motor speed

    One point I left out and just researched. First two techs measured rise and noted it was high per my last posts. I asked them about adjusting blower speed, not knowing anything other than this...
  3. From a consumer perspective that link is...

    From a consumer perspective that link is invaluable thank you. I could call 100 hvac people on the phone and the people answering the phone wouldn't be able to spell combustion. By having a website...
  4. All sound like excellent points. Btw not one tech...

    All sound like excellent points. Btw not one tech came out with their own co meter. I am buying one just for regular testing I addition to detectors in house. I did look at the one co experts...
  5. Keeping facts accurate in thread for posterity sake

    Thanks to everyone for their help. Some recent posts are inaccurate so I want to try to keep the facts right for anyone reading it in the future.

    - nowhere in the carrier instructions does it...
  6. Conclusions/Summary after having everyone out

    The chimney folks came-out today as did the second tech per my previous post. The chimney is in the same condition as when it was built in 1952, meaning there is no wear or damage. However, they...
  7. please read the thread - that is not what was said

    What I said was he took the venting off and the CO detector DID go-off. This is what I wrote above.

    Another technician came-out today. Here is what he stated. He did not have the equipment to do a...
  8. Flue off and venting into room when tech tested

    Thanks, will do. Want to make sure I understand and was clear in the info I provided, I may not have been clear. The tech entirely removed the vent from the unit meaning that the unit was venting...
  9. CO and next steps

    Thanks. I have them around the house and they have gone off when car was running in garage once (dumb move, a little too long) they are higher end units. Some came with Simon xt alarm system and...
  10. Thank you, this is definitely not about being...

    Thank you, this is definitely not about being cheap, it is about understanding as I don't cut corners on this but need info as getting a quality job done is difficult. Also I have a CO sensor in the...
  11. Thanks for your help, this is what I was looking...

    Thanks for your help, this is what I was looking for. I did call a tech and have another coming. My purpose here is to understand the issues as not all hvac technicians are as experience or honest...
  12. Here are some pictures showing system

    Pictures show chimney adapter, burners, dss switch etc
  13. 11 year old Carrier 58yav stumping the technician and me - yet another flame rollout

    After trying to troubleshoot, reading this forum, tand having a technician out, the problem can't be solved and hoping for help here.

    Equipment: carrier 58yav 110btu installed 2001. Installed in...