    It's like I said before I'm not saying this is...

    It's like I said before I'm not saying this is the only possible thing it could be. Obviously there are several things that can cause a Low Refrigerant Temp alarm. How hard is it to watch the amps...
  2. Replies
    60
    Views
    3,379

    Have you watched the amps on the display at start...

    Have you watched the amps on the display at start up? It's pretty simple to see if you are starting loaded, if the amps are above 45% then your starting loaded. If there close to 45% then your...
  3. Replies
    60
    Views
    3,379

    Yep that's what I'm talking about, there's some...

    Yep that's what I'm talking about, there's some other seals also if I remember correct that can cause similar problems. I realize it's hard to believe but I had two chillers last year going off on...
  4. Replies
    60
    Views
    3,379

    Call Trane tech support and ask them. I had it...

    Call Trane tech support and ask them. I had it happen on two different chillers last summer alone. The exv is stepped down and it sucks the suction pressure down real quick and it doesn't run long...
  5. Replies
    60
    Views
    3,379

    This is we're I'd start. Watch your display on...

    This is we're I'd start. Watch your display on start up watch the amps for that circuit if they go much higher than 45% then it's starting loaded. The RTAA is an older chiller a lot of times after so...
  6. Replies
    11
    Views
    1,340

    I have a 116 and have never had any luck with the...

    I have a 116 and have never had any luck with the temperature function on it. I bought a seperate fluke that only does temperature and it works good can't remember the model number right now.
  7. Replies
    36
    Views
    3,502

    I have the C&Ds and the appion. You can buy new...

    I have the C&Ds and the appion. You can buy new o rings for the c&ds I'm not sure if you can get them for the appions. I just got the appions and have to say I'm not to impressed with them yet. I...
  8. Replies
    12
    Views
    1,365

    Powering up a compressor under a deep vacuum will...

    Powering up a compressor under a deep vacuum will usually smoke the windings.
  9. Nice to know. I've had the same YJ vacuum pump...

    Nice to know. I've had the same YJ vacuum pump for over 7 years and rarely open the gas ballast on start up. I guess I'll start opening it now.
  10. Been there done that. **** happens. I found a...

    Been there done that. **** happens. I found a unit that was missing a screw and thought I would replace but apparently used to long of a screw and pierced the coil.
  11. Replies
    33
    Views
    2,360

    This just happened to me today, I had a capacitor...

    This just happened to me today, I had a capacitor that was rusted and couldn't read the label on it or the compressor. I had an instructor in school that taught me to measure the amps on the common...
  12. Thread: impact driver

    by GOVHVAC
    Replies
    45
    Views
    2,518

    A drill is for drilling, an impact is for driving...

    A drill is for drilling, an impact is for driving screws. When I use my drill to drive drywall or any phillips head screw it ends up stripping the head out 9 out of 10 times. A impact driver can...
  13. Replies
    10
    Views
    1,167

    Appion G5 Twin recovery unit. JB Platinum vacuum...

    Appion G5 Twin recovery unit.
    JB Platinum vacuum pump.
    Yellow Jacket micron gauge with replaceable sensor.
  14. Thread: fluke 116

    by GOVHVAC
    Replies
    16
    Views
    1,795

    I have the fluke 166/322 hvac combo kit. The 322...

    I have the fluke 166/322 hvac combo kit. The 322 is a clamp on amp meter. Both work great. One thing I really like about the 116 is the magnetic hanging strap, didn't know what I was missing until...
  15. Replies
    59
    Views
    4,712

    Been using milwaukee for the past year seem to be...

    Been using milwaukee for the past year seem to be great. Good battery life. I used dewalt before going to milwaukee, the dewalts are more powerful but the batteries don't last near as long and the...
  16. Thread: Vacuum Pump

    by GOVHVAC
    Replies
    20
    Views
    1,236

    JB platinum is a good vacuum pump. Get the 3/8"...

    JB platinum is a good vacuum pump. Get the 3/8" hoses to get a faster vacuum.
    The appion is good but there over $800.00. Little overkill for residential work imo. You can get a good JB or yellow...
  17. Thread: hvac veto bag

    by GOVHVAC
    Replies
    175
    Views
    29,013

    Thanks, called the Bloomington store they didn't...

    Thanks, called the Bloomington store they didn't have one but Indianapolis did and they are going to ship me one. Thanks for letting me know.
  18. Thread: hvac veto bag

    by GOVHVAC
    Replies
    175
    Views
    29,013

    Thank you

    Thank you
  19. Thread: hvac veto bag

    by GOVHVAC
    Replies
    175
    Views
    29,013

    The closest C.C. Dickson is about 3 hours away. ...

    The closest C.C. Dickson is about 3 hours away. I emailed Young Supply to see if they have any left they can ship me. If not I'll give Jason a call.
  20. Thread: hvac veto bag

    by GOVHVAC
    Replies
    175
    Views
    29,013

    I have been waiting for these to come out since I...

    I have been waiting for these to come out since I first read about them in September or October. I can't find one anywhere. I emailed Jason at Ace Tool and never heard back. So I emailed Jim Brooks...
  21. Thread: multi tool

    by GOVHVAC
    Replies
    31
    Views
    1,888

    I currently have a SOG, but don't care for it. ...

    I currently have a SOG, but don't care for it. The Powerlock blade lock sucks, my hand hits it and unlocks the blades everytime. The covers on the handles suck to, they fall off quite often. I'm...
  22. Most commercial units don't come with a factory...

    Most commercial units don't come with a factory charge weight stamped on them.
    If your running the unit at 50 degrees it should have some type of low ambient kit or a fan cycling switch, just...
  23. Replies
    30
    Views
    1,816

    Expansion Joints.

    Expansion Joints.
  24. Replies
    21
    Views
    2,077

    Relay!

    Relay!
  25. But if you just replace compressor you will still...

    But if you just replace compressor you will still have a matched system. If you go with a new heat pump and don't replace the indoor coil then you won't have a matched system which will effect...