Search:

Type: Posts; User: dingman

Page 1 of 12 1 2 3 4

Search: Search took 0.01 seconds.

  1. Isn't that crazy, all that the automation system...

    Isn't that crazy, all that the automation system does and the customer gets wound up about the graphic printouts.

    I haven't dug into this much but found good improvement by using the printer...
  2. Replies
    2
    Views
    317

    that's the funniest thing I've heard in awhile....

    that's the funniest thing I've heard in awhile. Are you sure they weren't pulling your leg? Astounding.
  3. Replies
    7
    Views
    314

    That sounds pretty straightforward. The virtual...

    That sounds pretty straightforward. The virtual point should be controlled by a PID loop in the PPCL. Find the PID values in a unit that is working properly and copy those values into the offending...
  4. Replies
    7
    Views
    314

    The loop speed may not be the issue. Is the unit...

    The loop speed may not be the issue. Is the unit tripping off on startup or when it's been running and OA temp drops?

    Is it a new issue? Have you checked temps during trouble periods (look for...
  5. Replies
    134
    Views
    24,102

    I have saved every version since the DOS days. ...

    I have saved every version since the DOS days.

    I've already put them all out on the web, and all have nice little rootkits in them. Just run the install and don't worry about any security error...
  6. Just to be clear, PPCL doesn't need manual or...

    Just to be clear, PPCL doesn't need manual or auto-unbundling anymore.

    Graphics still do.
  7. Replies
    34
    Views
    10,708

    Full functionality via Hyperterminal. Of course,...

    Full functionality via Hyperterminal. Of course, you can't backup\restore databases.
  8. That's the ethernet ALN connection - look for the...

    That's the ethernet ALN connection - look for the MMI connection (also looks like an RJ45), plug your RJ11 in there.
  9. Well, it all sounds pretty good, sounds like...

    Well, it all sounds pretty good, sounds like you've put alot of time working into this.

    Despite being a long term tech with Siemens, you guys are above my head on this - you're at engineering...
  10. Replies
    8
    Views
    693

    LOL ya, it was a compliment. If you get crazy...

    LOL ya, it was a compliment. If you get crazy busy and need a well rounded, experienced tech, let me know. I could be talked into jumping ship - some great recreational activities in your area - way...
  11. This is correct.

    This is correct.
  12. Thread: Siemens node

    by dingman
    Replies
    10
    Views
    697

    Correct Willy, I've never found that LINK point...

    Correct Willy, I've never found that LINK point very useful. The only thing I did with it one time was to attach a light to a DO and turn it on when the panel would drop off the network. Then, people...
  13. Thread: Siemens node

    by dingman
    Replies
    10
    Views
    697

    I assume you are talking about TEC controllers....

    I assume you are talking about TEC controllers.
    The controllers attached to a specific panel would be available via the FLN device list. Pull that either from Insight or the panel.
  14. Replies
    8
    Views
    693

    hiyas air1! I'm chuckling over here, your...

    hiyas air1!
    I'm chuckling over here, your explanation is way more than the OP needed. Obviously you know your stuff, and we have an tech opening here in Iowa, you should apply. :)
    if you indeed a...
  15. Disconnect all the inputs\outputs except power....

    Disconnect all the inputs\outputs except power. If it still does it, replace the TEC. If it stops, inspect wiring\devices.
  16. Willy, doesn't it sync automatically with each...

    Willy, doesn't it sync automatically with each change?

    Seagar, you won't add the info block in Designer, you add it in the Graphics application, take your TEC graphic, and put it in edit mode, and...
  17. Replies
    6
    Views
    830

    Actually, one would try to avoid having to define...

    Actually, one would try to avoid having to define the graphic in each TEC definition in the system profile.

    The create-on-the-fly TEC graphics are already done and available in Insight. If there's...
  18. Replies
    6
    Views
    830

    Actually, one would try to avoid having to define...

    Actually, one would try to avoid having to define the graphic in each TEC definition in the system profile.

    The create-on-the-fly TEC graphics are already done and available in Insight. If there's...
  19. There's a couple of failsafe modes, where it...

    There's a couple of failsafe modes, where it won't let you command the fan.

    IIRC, both the LTD and the DA temp sensor can cause failsafe mode. Make sure LTD isn't tripped and that DA sensor isn't...
  20. This isn't an answer to your question, so pardon...

    This isn't an answer to your question, so pardon my interjection.

    Siemens TEC's have historically been very robust and quite difficult to damage. If you have more than a few that are damaged, then...
  21. Thread: Siemens Log

    by dingman
    Replies
    6
    Views
    679

    If you have access to it, there should be a...

    If you have access to it, there should be a button in the Insight main tool bar.
  22. Thread: Siemens Log

    by dingman
    Replies
    6
    Views
    679

    Yes.

    Yes.
  23. Replies
    11
    Views
    1,119

    Seems like there's a common path, not shared by...

    Seems like there's a common path, not shared by all, but by a majority.
    My path was~
    Industrial Electrician
    to
    Commercial\residential Electrician
    to
    AA in Electronics
    AA in Robotics (yea, I...
  24. Replies
    7
    Views
    963

    Dead JNL files are easy to check and correct. I...

    Dead JNL files are easy to check and correct. I find this less and less due to the increased reliability of networks\clients. Haven't found any dead JNL's for months now.

    However, in the last few...
  25. Replies
    10
    Views
    783

    Ton78, I commend you for searching out people to...

    Ton78, I commend you for searching out people to help.

    I understand you're in a tough spot, with not having adequate training for what you're working with.

    My best suggestion would be to read...