Search:

Type: Posts; User: Failure2Comply

Page 1 of 2 1 2

Search: Search took 0.01 seconds; generated 10 minute(s) ago.

  1. Replies
    18
    Views
    526

    Thanks!

    Thanks!
  2. Replies
    18
    Views
    526

    Thank you.

    Thank you.
  3. Replies
    18
    Views
    526

    Yes I saw that while configuring the VMA that was...

    Yes I saw that while configuring the VMA that was a choice for stat type. So if I had a fully adjustable stat would I leave the heat and cool temps along with common set to 0F?
  4. Replies
    18
    Views
    526

    So if you had a stat with the +/- 5F adjustment,...

    So if you had a stat with the +/- 5F adjustment, this is how you would configure the VMA?
  5. Replies
    3
    Views
    278

    I am running Java 6 v30 for compatibility issues.

    I am running Java 6 v30 for compatibility issues.
  6. Replies
    18
    Views
    526

    Thank you sir.

    Thank you sir.
  7. Replies
    3
    Views
    278

    FX60 with embedded Workbench

    When accessing the Jace is says "loading Workbench". I have admin rights to the Jace so how do I access Workbench?
  8. Replies
    18
    Views
    526

    Do you have a link to that manual?

    Do you have a link to that manual?
  9. Replies
    18
    Views
    526

    Thank you sir, you are right on the money. Set...

    Thank you sir, you are right on the money. Set Common to 0F and now they are reading correctly.
    Thanks to all that helped!
  10. Replies
    18
    Views
    526

    And this...

    And this...
  11. Replies
    18
    Views
    526

    Appreciate your help... STANDARD...

    Appreciate your help...


    STANDARD CONFIGURATION PRINT - SHORT FORM
    -----------------------------------------

    PROJECT INFORMATION
    HVAC PRO Version : 8.04
    Configuration File :...
  12. Replies
    18
    Views
    526

    This...

    This...
  13. Replies
    18
    Views
    526

    VMA1420 issues

    I have a VMA1420 controller that keeps setting the "Cooling PID" to 146.0F and the "Heating PID" to 140.0F? I am using HvacPro with a rs232 to rs485 converter and I have full access to the vma. I...
  14. Replies
    23
    Views
    5,286

    Thank you, I will see about getting it.

    Thank you, I will see about getting it.
  15. Replies
    23
    Views
    5,286

    Actually I got it from M&M during a class I took....

    Actually I got it from M&M during a class I took. Great people!
  16. Replies
    23
    Views
    5,286

    I have M-Tools v5.1.

    I have M-Tools v5.1.
  17. Replies
    23
    Views
    5,286

    Sorry to resurrect an old thread. I have HVAC Pro...

    Sorry to resurrect an old thread. I have HVAC Pro for my old XP laptop but it will not load on my new Win 8.1 Toshiba. My old Dell 600m running XP Pro is like watching paint dry, very painful but it...
  18. Replies
    10
    Views
    1,395

    As stated the "T" wire was hooked to an outdoor...

    As stated the "T" wire was hooked to an outdoor thermistor for heating anticipation of a mercury bulb thermostat, just omit it.
  19. There are many factors that go into making an...

    There are many factors that go into making an informed decision, warranty is just one of them. I will put Honeywell's' track record up against Nest any day of the week. just my $.015
  20. A "King Valve" is the liquid line shut off valve...

    A "King Valve" is the liquid line shut off valve at a receiver tank. A liquid line service valve is what you find on outdoor units. I ALWAYS wrap and cool with water ANY valve that I solder in, or...
  21. Is this a multi-stage unit?

    Is this a multi-stage unit?
  22. Replies
    17
    Views
    4,088

    It is a little over 20 tons (024 = 20tons) and...

    It is a little over 20 tons (024 = 20tons) and was made the 45th week of 1993. It should be a standard Carlyle cast iron compressor with one or two unloaders, most likely suction cut-off unloading.
  23. Isn't "H1" the humidity sensor? Do you get a...

    Isn't "H1" the humidity sensor? Do you get a humidity reading at the stat now?
  24. The Vision Pro 8000 has a five year warranty,...

    The Vision Pro 8000 has a five year warranty, what does the Nest have. The 8000 is a rock solid stat with years of proven performance. I have installed many ecobee's and was not all that impressed...
  25. Sounds like you are talking about PTAC (package...

    Sounds like you are talking about PTAC (package terminal air conditioner) units not window shakers. They must be pulled and chemically cleaned (and lubed if equipped) before the cooling season to get...
  26. Being a VAV unit all it knows is discharge air...

    Being a VAV unit all it knows is discharge air temp setting and static pressure setting. It will ramp up and stage up accordingly. Make sure the time delay between rooftop units is set to allow...
  27. Lennox = Dec 1999 (2.5ton) Payne = 11th week...

    Lennox = Dec 1999 (2.5ton)

    Payne = 11th week of 2003 (4 ton)
  28. Replies
    7
    Views
    1,231

    Thank you for the manual and information. John

    Thank you for the manual and information.
    John
  29. Replies
    7
    Views
    1,231

    I am in Chesterfield Co. Thanks, John

    I am in Chesterfield Co.
    Thanks,
    John
  30. Replies
    7
    Views
    1,231

    Teletrol 186 info needed

    I ran into an old Teletrol 186 Integrator today that is has the "error light" on solid. They lost their building's transformer and now the system will not run. There is no information on site about...
  31. Replies
    7
    Views
    920

    Sounds like Precedent models.

    Sounds like Precedent models.
  32. I would suggest you look at fan speed control...

    I would suggest you look at fan speed control along with auto-reset freeze stats.
  33. Replies
    7
    Views
    1,265

    If it was "Snowball" it would take twenty years...

    If it was "Snowball" it would take twenty years of that to kill it.
  34. Replies
    9
    Views
    1,369

    Is the underside of the head smooth or does it...

    Is the underside of the head smooth or does it have a square plate bolted on?

    Smooth = hot gas bypass
    Square plate = Suction cut-off.
  35. Did they run a "Heat Load" on your house to...

    Did they run a "Heat Load" on your house to determine exactly what was needed for upstairs and downstairs, not just replace "like for like"? Houses change over time with trees growing up and more or...
  36. Replies
    11
    Views
    1,008

    Carrier and Data Aire (IMHO) can not tie...

    Carrier and Data Aire (IMHO) can not tie Liebert's shoes (even though a lot of older Liebert units used Carlyle cast iron compressors). I take care of three at a local TV station that have been...
  37. Replies
    6
    Views
    1,139

    All "39 Series" Carrier air handlers are purpose...

    All "39 Series" Carrier air handlers are purpose built so you will have to call Carrier( and hope you get someone that even knows what they are) to decipher its numbers. It appears to be built in the...
  38. Does it have anything attached to its "Emergency...

    Does it have anything attached to its "Emergency Stop" terminals? And if yes have you tried jumping them out?
  39. Replies
    21
    Views
    2,251

    Is this a Trane Voyager with the UCP? If yes,...

    Is this a Trane Voyager with the UCP? If yes, have you taken the outdoor air sensor and discharge air sensors and checked their ohm readings? Also have you taken the outdoor sensor loose, pulled the...
  40. Replies
    11
    Views
    1,008

    More information please. Are you trying to...

    More information please. Are you trying to replace the remote condenser, the indoor unit or what? How is Mitsubishi involved?

    Data Aire is a poor man's Liebert.
  41. Replies
    10
    Views
    1,067

    Best bet is to take it to a motor shop for...

    Best bet is to take it to a motor shop for confirmation.
  42. Replies
    36
    Views
    8,054

    Amen Brother! What, you mean I can't take a...

    Amen Brother!

    What, you mean I can't take a little pill that will cure all the world's ailments? You mean that I ACTUALLY have to do my job? :gah: :grin2:
  43. Replies
    26
    Views
    2,720

    If I get a questionable meg reading I take an...

    If I get a questionable meg reading I take an acid/moisture test of the refrigerant to see if the reading is caused by contamination or winding insulation beginning to deteriorate.
  44. Replies
    2
    Views
    704

    5 ton natural gas 79k BTU 208/230v 3p. In case...

    5 ton natural gas 79k BTU 208/230v 3p. In case you are interested.
  45. Replies
    14
    Views
    2,080

    Check with Carrier. You will see a R86489 which...

    Check with Carrier. You will see a R86489 which would be 1988 but not two numbers until they went to "Week/Year" ex. 0399E which was made the third week of 1999 and was made in Syracuse. Prior to the...
  46. Replies
    46
    Views
    5,212

    With manufacturers using more fins/inch to try...

    With manufacturers using more fins/inch to try and get max efficiency out of system it is tough to get the embedded dirt, pollen, and debris out without using a foaming coil cleaner. The only issues...
  47. Just be careful of your changeover setting. Also...

    Just be careful of your changeover setting. Also consider a mixed air thermostat to stage on the cooling if the outside ambient can't keep up with the load.
  48. Replies
    14
    Views
    2,080

    Just like with the older Carrier units the serial...

    Just like with the older Carrier units the serial numbers can be deciphered:

    A-M = 1970's
    N-Z (Never O) = 1980's

    example:

    C9 = 1979
    S9 = 1989
  49. Replies
    14
    Views
    2,080

    No manual, just from memory.

    No manual, just from memory.
  50. Replies
    14
    Views
    2,080

    008 = 7.5 ton 501 = 208/230V 3ph 300 series =...

    008 = 7.5 ton
    501 = 208/230V 3ph

    300 series = 208/230V 1ph
    400 or 500 series = 208/230V 3ph
    600 series = 480V 3ph
Results 1 to 50 of 100
Page 1 of 2 1 2

Related Forums

Plumbing Talks | Contractor Magazine