05-21-2013, 08:38 PM
- Replies
- 68
- Views
- 943
I talked with manufacturer the head pressure...
I talked with manufacturer the head pressure control is set to 235 max for 410a water cooled my head pressures were over 300 normal 410 pressures, they had three belimo valves 2 stayed open one which...
-
05-20-2013, 07:42 PM
- Replies
- 68
- Views
- 943
384941384951384961384981[ATTACH=CONFIG]problem...
384941384951384961384981[ATTACH=CONFIG]problem solved went back topday to pm all units there was 3 water accuator valves on the in/outlet 2 were open one was closed, the closed one was labbled head...
-
05-19-2013, 06:21 PM
- Replies
- 68
- Views
- 943
it says l1 terminal is control voltage so if it...
it says l1 terminal is control voltage so if it is wired through y like you say how is this problem fixed where is your y connected to if not l1
-
05-19-2013, 05:51 PM
- Replies
- 68
- Views
- 943
that's my point these units weren't put back...
that's my point these units weren't put back properly the pink 410a label on top of both compressors in one unit means they are regular scrolls according to what your saying while in the other unit...
-
05-19-2013, 05:39 PM
- Replies
- 68
- Views
- 943
makes sense because one unit the compressor was...
makes sense because one unit the compressor was unloading the other wasnt
-
05-19-2013, 05:06 PM
- Replies
- 68
- Views
- 943
im pretty sure both these units were broken down...
im pretty sure both these units were broken down to get into space if 2 regular scrolls went in one unit and 2 digital in the other would this be causing the problem im having? becaue when I was...
-
05-19-2013, 04:17 PM
- Replies
- 68
- Views
- 943
384551384561when I go back this week ill take...
384551384561when I go back this week ill take some pictures and post them, there is a 50 page book in the controls box showing how everything is wired and works, didn't have time to really go through...
-
05-19-2013, 04:04 PM
- Replies
- 68
- Views
- 943
well if both compressors have their own low/head...
well if both compressors have their own low/head pressure switches its not a single circuit wright? so that would eliminate the low pressure point your making, but I do believe its a installation...
-
05-19-2013, 03:42 PM
- Replies
- 68
- Views
- 943
well the most common thing between both units is...
well the most common thing between both units is the water supply they share the water temp going in I believe was 70 pressure going in was 60
-
05-19-2013, 03:23 PM
- Replies
- 68
- Views
- 943
I don't know was only there for a hour on Friday...
I don't know was only there for a hour on Friday unit is still under warrenty so I don't know if I will be fixing it, yes both compressors shut off at the exact same time weird, they both don't turn...
-
05-19-2013, 02:11 PM
- Replies
- 68
- Views
- 943
there's a pressure transducer on the discharge...
there's a pressure transducer on the discharge line, when the 2nd compressor comes on they both run a minute or so then both shut off and the 3 red blinks show on controller then they come on again a...
-
05-19-2013, 01:41 PM
- Replies
- 68
- Views
- 943
so its normal operation for these digital scrolls...
so its normal operation for these digital scrolls to constantly short cycle with poor modulation what a bad design
-
05-19-2013, 12:48 PM
- Replies
- 68
- Views
- 943
yeah this is the controller both compressors are...
yeah this is the controller both compressors are the same and I have one of these controllers in each unit with 2 compressors in each unit never worked with this type of controller doing some weird...
-
05-18-2013, 06:11 PM
- Replies
- 68
- Views
- 943
well i only have low and high pressure controls...
well i only have low and high pressure controls high is manual reset so cant be that low is auto maybe faulty low pressure water is good but 2 separate units doing the same thing weird
-
05-18-2013, 04:04 PM
- Replies
- 68
- Views
- 943
ok so my problem is I have a call for compressor...
ok so my problem is I have a call for compressor but its getting locked out due to no amperage being detected
-
05-18-2013, 03:58 PM
- Replies
- 68
- Views
- 943
what im thinking is that when the 2nd stage...
what im thinking is that when the 2nd stage compressor kicks in there is a power drop goes below 208 and is sensed through this device shutting down the compressors when I go back next week im going...
-
05-18-2013, 03:51 PM
- Replies
- 68
- Views
- 943
it did start that's not the problem 1st stage...
it did start that's not the problem 1st stage runs second stage comes on 1 minute or so later both compressors go off then come on again minutes later same thing olver and over red light blinks 3...
-
05-18-2013, 03:49 PM
- Replies
- 68
- Views
- 943
like I said there are 2 units same make model...
like I said there are 2 units same make model brand new doing the same thing just odd I checked everything already covering the basics
-
05-18-2013, 03:06 PM
- Replies
- 68
- Views
- 943
I need to know what causes this type of code ...
I need to know what causes this type of code
Flash Code 3 - Compressor Protector Trip
The demand signal from the system controller is
greater than 1.44VDC and there is no compressor
current... -
05-18-2013, 02:39 PM
- Replies
- 68
- Views
- 943
I don't have a pick of the diagnosis box only the...
I don't have a pick of the diagnosis box only the one mounted to the compressor its black has a green status light a red light that says alarm and a yellow light that says unloaded yessss that's it...
-
05-18-2013, 01:30 PM
- Replies
- 68
- Views
- 943
know a regular scroll compressor the black box...
know a regular scroll compressor the black box mounted in the unit tells me by the blinking lights compressor overload that's it
-
05-17-2013, 09:16 PM
Thread: comperssor black overcurrent box tripping
by raven22- Replies
- 4
- Views
- 160
not that I know of ill take a better look when I...
not that I know of ill take a better look when I go back next week but I was leaning towards that gotta be the voltage maybe running a little low I think I was getting 199 volts on all three phases...
-
05-17-2013, 09:06 PM
- Replies
- 68
- Views
- 943
units are in a closed loop system connected to a...
units are in a closed loop system connected to a dry cooler I have 2 leiberts for a server room running off the same dry cooler and their doing fine,you talking about replacing the motor protector or...
-
05-17-2013, 07:51 PM
- Replies
- 68
- Views
- 943
compressor black over current box tripping
I'm working on a Aaon water cooled self contained unit ac only 3 months old first ac season, theirs a black phase monitor box that keeps blinking 3 times red light, code says overloaded compressor, I...
-
05-17-2013, 07:49 PM
Thread: comperssor black overcurrent box tripping
by raven22- Replies
- 4
- Views
- 160
comperssor black overcurrent box tripping
I'm working on a Aaon water cooled self contained unit ac only 3 months old first ac season, theirs a black phase monitor box that keeps blinking 3 times red light, code says overloaded compressor, I...