    The KMD-5576 USB, "hockey puck" interface, is...

    The KMD-5576 USB, "hockey puck" interface, is used to direct connect a PC to a Tier-2 controller network. It's an EIA-485 to RS-232 serial communications interface, and needs it's proper MS Windows...
  2. Replies
    16
    Views
    1,795

    If you have the software up and running, you need...

    If you have the software up and running, you need to do the following;

    -Create a system in the WinControl systems list by entering the your existing system's name. Configure this connection type...
  3. Replies
    6
    Views
    296

    Guess you need to configure your Tier 1 panel...

    Guess you need to configure your Tier 1 panel with your SMTP server IP address. You would also need KMC's HCM.exe utility program, and a direct connection to do this.
  4. Replies
    3
    Views
    371

    Thanks for info. Trane rep could not find the...

    Thanks for info. Trane rep could not find the part #, yet they qouted a price on it anyways. Geeeez!
  5. Replies
    3
    Views
    371

    BCI/UC400, Trane part no.

    Need Trane part no. for a BCI/UC400 Bacnet interface controller for a CGAM-100 chiller. Still waiting on my Trane rep. to produce and qoute a cost. Any help out there would be appreciated!
  6. Check this link...

    Check this link http://www.kmccontrols.com/events/newsArticle.aspx?nid=126
  7. Thread: KMC Modbus

    by bobcontrols
    Replies
    2
    Views
    966

    Have 21 tier-2 KMD 5540-005's, reading points off...

    Have 21 tier-2 KMD 5540-005's, reading points off 21 Veris H-8036 power meters. Each can read/write up to 32 Modbus points as long as you program the proper registers. Modbus devices can be networked...
  8. Replies
    15
    Views
    3,299

    A KMD-7301 is a 4in/4out, tier 2 controller, and...

    A KMD-7301 is a 4in/4out, tier 2 controller, and a KMD-5502 is an 8in/8out, tier 2 controller. So no, they are not compatible replacements as such, yet they are compatible peers on a KMC network. The...
  9. Replies
    15
    Views
    3,299

    Emailed what you need! Try to buy a KMD-5576 USB...

    Emailed what you need! Try to buy a KMD-5576 USB dongle, and use HCM with XP or Win7. Load USB driver so you end up having a USB comm port X, installed in windows hardware manager. Kset will run on a...
  10. Replies
    15
    Views
    3,299

    Tried to send you some zipped files but your...

    Tried to send you some zipped files but your profile email fails on delivery.
  11. Replies
    15
    Views
    3,299

    You should be all set. Take some known good...

    You should be all set. Take some known good cables to the site with you, to eliminate the possibility of a bad converter connection. Try rebooting the panel by pulling the power jumper. Factory...
  12. Replies
    15
    Views
    3,299

    Kset vs HCM

    You can use Kset to change address and baud rate on a new board, but thats about it. To access new features you will need HCM. AIC's have access to a utility program called PFC (Program File...
  13. Replies
    20
    Views
    2,501

    I would start looking at the Mcquay AGZ030C...

    I would start looking at the Mcquay AGZ030C technical literature and catalog specs, available at the manufacturers home page. Optional sound attenuation is available at additional price to the...
  14. Replies
    5
    Views
    928

    KMC Control Basic

    KMC Control's Basic language is readily available right off the editor screen, with examples on notation and use. Wincontrol XL programming software also has a fairly good help file with a complete...
  15. Replies
    2
    Views
    1,037

    The KMD-5210 is a tier 1 controller and the...

    The KMD-5210 is a tier 1 controller and the KMD-5831 is a tier 2 controller on a subnetwork branch, A or B, of the KMD-5210. A repeater, (KMD-5575) is needed every 32 panels or 4,000 feet of wire, so...
  16. Replies
    7
    Views
    1,498

    Static Pressure PID loop

    You should check your static sensor pressure sample location on the ductwork. It should be installed 2/3 down the duct work, away from any duct transition or elbow. Try teeing in a magnehelic gauge...
  17. Replies
    5
    Views
    636

    KMC analog input averaging.

    Not at all. A typical KMC local controller will execute 10-50 scans per second on average, depending on the amount and byte length of the control basic programs and the amount of configured points....
  18. Replies
    5
    Views
    636

    KMC analog input averaging

    Got this off the Wincontrol XL help file! Hope it helps.
    Average = Sets the number of samples which are averaged together to calculate the displayed value. A sample is taken on each scan.
  19. Replies
    18
    Views
    2,801

    7.5 ton 2 stage RTU

    Lennox makes a LCA090H2B (R22) OR -H4B (R-410A) RTU with 2 scroll compressors, and optional humidity control package that uses a hot gas reheat coil in the evaporator section.
  20. Replies
    6
    Views
    754

    Have a P/N 4950-0356 PCM sitting in my shop for...

    Have a P/N 4950-0356 PCM sitting in my shop for some time! Model # is for 3 outputs / 3/inputs type PCM. Tested operational. Email in profile!
  21. Replies
    8
    Views
    766

    You either have a "questionable" BAC-5001 board...

    You either have a "questionable" BAC-5001 board or your installed input wire runs, are running with or where they shouldn't. Try swapping the board (with known good one) to see if problem persists....
  22. Replies
    2
    Views
    423

    Scar: Is it a Tier 1 or Tier 2 network? I'm...

    Scar:
    Is it a Tier 1 or Tier 2 network? I'm having the same problem and find Analyzer useless without the docs. I've split the suspected network and direct connected with Analyzer but still haven't...
  23. Replies
    15
    Views
    3,910

    Make sure you know your sensor temp/psi range,...

    Make sure you know your sensor temp/psi range, actuator spring range and your 0-15 PSI gauge. The idea is to adjust everything up at half the system pressure range, (7.5PSI if a 6 to 9PSI actuator)....
  24. Replies
    1
    Views
    867

    The "USB hockey puck" (KMD-5576) will not connect...

    The "USB hockey puck" (KMD-5576) will not connect with Incontrol, which is a 16bit legacy software. Try a KMD-5557 with a PC running Windows 95 or 98. To connect an XP PC with the hockey puck you'll...
  25. Replies
    3
    Views
    464

    Trane VAV Command Unit.

    Short terminals TB2-3,4 at the VAV CU, to override all VAV UCM's to heating mode. Using Hyperterminal at the VAV CU's RS-232 port, can also help you enable heating mode. The PCM does not control the...