Search:

Type: Posts; User: ddcctrl

Search: Search took 0.01 seconds; generated 4 minute(s) ago.

  1. Replies
    13
    Views
    2,071

    Is this for KMC BACnet controllers only, or will...

    Is this for KMC BACnet controllers only, or will it work with older KMD controllers as well?
  2. Replies
    1
    Views
    159

    Rebooted both gcm's at the same time, started...

    Rebooted both gcm's at the same time, started talking. Both gcm's were initially powered up this morning without comm wiring connected to the gcm-ech, maybe they have to be wired together when...
  3. Replies
    1
    Views
    159

    Siebe GCM-ECH issue

    Two gcm 86120 with gcm-ech-001 comm modules, communicating. Relocated from one site to another, comm reconnected, gcm's will not talk. Is there setup that can be done to the gcm-ech besides...
  4. Replies
    7
    Views
    887

    Need to same code for older Distech Free Prog...

    Need to same code for older Distech Free Prog controller. I tried using nvi17 without success.
  5. Network 8000 Signal Engineering Units Display Issue

    Signal version 4.4.1, Windows 95 machine. Recently the engineering units displayed for a Microflo II Remote Setpoint Enable point (RSPEN) started displaying "Link Type (1) or Link Type (0)". ...
  6. Replies
    1
    Views
    492

    As follow-up, found that StatusRmTmpActSpt was =...

    As follow-up, found that StatusRmTmpActSpt was = to nciSetpoints occupied heat value, even though StatusOcc read unoccupied.

    nciSetpoint valves appeared to be in correct order, i.e. Unoccupied...
  7. Replies
    1
    Views
    492

    Honeywell T7300 unoccupied issue

    Multiple T7300 tstats connected to Tridium R2 JACE (version 527). On some tstats StatusOcc shows unoccupied, yet stat appears to be controlling around occupied heat setpoint, based on review of...
  8. Replies
    1
    Views
    346

    AX Enum Writable object - override time

    Looking for enum writable object in AX that would allow for override ending time to be set as time and date rather than hours. Thanks.
  9. Replies
    3
    Views
    2,120

    BC Jetronic

    Any info out there available for these? Thanks.
  10. Replies
    17
    Views
    2,104

    See this post from 2008: ...

    See this post from 2008:

    http://hvac-talk.com/vbb/showthread.php?t=185126&highlight=trane+driver


    As dapper said, Trane used the 18/2 "purple" shielded cable early in LON; I think I have seen...
  11. Thread: Dirty group

    by ddcctrl
    Replies
    8
    Views
    767

    Check LonUtilitiesManager-Reports-Verify. This...

    Check LonUtilitiesManager-Reports-Verify. This may reveal an issue with one controller. Also if you have controllers that are offline you may not be able to clear up the dirty groups.
  12. Replies
    1
    Views
    708

    Liebert Sitelink panel

    From Liebert's website, in the SiteLink-E installation document:

    "The Liebert SiteLink-E communicates using BACnet and/or third-party protocols, and can connect to a variety of port types at...
  13. Replies
    2
    Views
    778

    AX will run on Vista Home Premium with no...

    AX will run on Vista Home Premium with no problems. If you are using the computer for engineering R2 will work fine. If you trying to run a station on the computer it will probably not work for R2...
  14. Replies
    10
    Views
    3,065

    Hello Krac: Can you contact me concerning what...

    Hello Krac:

    Can you contact me concerning what your solution was for this? I have similar opportunity. Please see email and IM info in profile. Thanks.
  15. Had similar problem even with the latest BACnet...

    Had similar problem even with the latest BACnet JAR file. I added the following in the bacnet.properties file and all has been well since (as far as I know):

    pollHeartbeatCheck=true # to...
  16. Replies
    23
    Views
    1,518

    I have seen this issue with an AX to R2 BACnet...

    I have seen this issue with an AX to R2 BACnet integration, with setpoint control. The server was R2, sending setpoint info to AX JACE. The BACnet AVP point linked to a Numeric Writable at first...
  17. Replies
    4
    Views
    804

    I have bought and sold controllers on ebay and...

    I have bought and sold controllers on ebay and have had good success. You can also find Belimo stuff on there as well.
  18. Replies
    6
    Views
    1,403

    I second dapper on this one.

    I second dapper on this one.
  19. Replies
    26
    Views
    3,864

    You could team up with a Tridium Vykon System...

    You could team up with a Tridium Vykon System Integrator (http://www.tridium.com/cs/purchase_products/north_america) to provide you with the AX hardware. You should be able to find someone willing...
  20. Thread: Career Advice

    by ddcctrl
    Replies
    8
    Views
    1,231

    Have you considered starting your own controls...

    Have you considered starting your own controls company? Or, if you are in Michigan you might consider touching base with the following company: http://www.abcsys.net/. I have had correspondance...
  21. Replies
    11
    Views
    815

    We have used a custom program object in AX 3.1.30...

    We have used a custom program object in AX 3.1.30 that does most of what you want to do. Email if interested.
  22. Replies
    12
    Views
    1,601

    What type of Network 8000 controllers do you have?

    What type of Network 8000 controllers do you have?
  23. Thread: Invensys

    by ddcctrl
    Replies
    1
    Views
    810

    Signal is the front-end software. Is the system...

    Signal is the front-end software. Is the system Nerwork 8000 (Barber Colman) or DMS (Robertshaw). Signal is connected serially to the GCM (if Network 8000). What type of field controllers do you...
  24. Replies
    9
    Views
    2,064

    I took a look at the cut sheet, and I see now...

    I took a look at the cut sheet, and I see now that these are for the Microzone or Microflo I series controllers. The companies' name has changed (as you may know) from Barber Colman, to Siebe, to...
  25. Replies
    9
    Views
    2,064

    Are you perhaps talking about the TS-90230...

    Are you perhaps talking about the TS-90230 sensor? If you are, you can order an ACI sensor, ACI/10K-AN-RO, and add an 11K ohm, 1/4 watt resistor across the sensor terminals. This sensor also has a...
  26. Replies
    3
    Views
    674

    You may be using an early version of the PEM...

    You may be using an early version of the PEM software. PEM's came out circa 1992 as an application specifc controller. PSI was used to download the application, and you could only edit values. ...
  27. Replies
    10
    Views
    1,173

    I would guess the COS alarm is for a pump. The...

    I would guess the COS alarm is for a pump. The OFF R means the condition has returned to normal. The COS block usually compares the equipment status with the equipment command. If the alarm says...
  28. Replies
    10
    Views
    1,173

    ALARM is numeric alarm (temperature, humidity,...

    ALARM is numeric alarm (temperature, humidity, pressure, etc.). It alarms based on alarm value and return from alarm value set-up in the GCM Blocks (as incontrol said you would have to look at the...
  29. Replies
    4
    Views
    1,077

    Trane Tracker Integration

    I searched through past Controls threads on this forum but was unsuccesful in finding info for the question below.

    Is it possible to integrate Tracker panel via LON or BACnet?

    Customer has...
  30. Thread: microzone II

    by ddcctrl
    Replies
    5
    Views
    951

    Yes, the Patton converter will work for Microflo...

    Yes, the Patton converter will work for Microflo II controllers.
  31. Thread: microzone II

    by ddcctrl
    Replies
    5
    Views
    951

    You can use Patton Electronics RS-232/RS-485...

    You can use Patton Electronics RS-232/RS-485 converter, I think model is 285Barber, or 2085. Others will work as well. PSI does not work with Micronet controllers, different software is needed,...
  32. Replies
    13
    Views
    4,821

    http://www.viconics.com/

    http://www.viconics.com/
  33. Replies
    0
    Views
    671

    JCI M5 BACnet question

    Can an M5 server, late 1990's vintage, serve BACnet points? It is my understanding that it can serve OPC points.
  34. Try disconnecting one of the leads to the...

    Try disconnecting one of the leads to the battery. Had a similar problem recently with a bad battery causing a Tridium R2 JACE to contantly reboot.
  35. Replies
    8
    Views
    2,558

    Some have used Tridium's CSD driver to connect to...

    Some have used Tridium's CSD driver to connect to Tracer 100 (at least in R2 version).
  36. Replies
    30
    Views
    3,997

    Please email me to discuss....see my profile...

    Please email me to discuss....see my profile under additional info for email address.
  37. Replies
    15
    Views
    1,859

    I think JCI in another post as well

    I think JCI in another post as well
  38. Replies
    5
    Views
    1,535

    http://www.unitronics.com/

    http://www.unitronics.com/
  39. Replies
    1
    Views
    1,036

    Invensys IA MN 200 thinks it is a 100?

    Call from customer, two AHU's down after power outage. Used Workplace Tech 3.2, did not have original MN 200 database, modified one from another job. When I went to download it gave an error that...
  40. Replies
    2
    Views
    510

    T7350 Aux Contact - Tridium R2

    Wanting to use Aux contact on T730H1009 for time-of-day control of extra equipment. Anyone know which nvi to use to enable/disable contact? Tridium R2 JACE, T7350Cs shadow object.
  41. Thread: computrols

    by ddcctrl
    Replies
    1
    Views
    602

    Computrols

    See the following link. Contact info at bottom of home page.

    http://www.abcsys.net/
  42. Thread: Barber Coleman

    by ddcctrl
    Replies
    13
    Views
    2,358

    Must have PSI or XPSI software to get to MZII...

    Must have PSI or XPSI software to get to MZII programming. Also must have an RS232-485 converter, Patton electronics Model 285. If site has GCM connected to MZII's you can see values coming from...
  43. Replies
    3
    Views
    662

    Nikko - Was Alerton integration BACnet?

    Nikko -

    Was Alerton integration BACnet?
  44. Replies
    11
    Views
    1,244

    Does Solidyne private label Invensys I/A LON? ...

    Does Solidyne private label Invensys I/A LON?

    See pages 18-19 in link below.

    http://www.solidyne.com/download/sol.cat.6.6.2005.pdf
  45. Replies
    18
    Views
    2,516

    Test and balance techs can make decent DDC techs...

    Test and balance techs can make decent DDC techs as well (if they are good ones)
  46. Replies
    3
    Views
    2,072

    Sysint - please contact me off forum. Thanks.

    Sysint - please contact me off forum. Thanks.
  47. Replies
    3
    Views
    2,072

    Has anyone integrated Trane VariTrac CCP into a...

    Has anyone integrated Trane VariTrac CCP into a LON network other than Trane Tracker or Summit?
Results 1 to 47 of 47