Search:

Type: Posts; User: jczekai

Page 1 of 3 1 2 3

Search: Search took 0.01 seconds.

  1. Replies
    7
    Views
    3,215

    If you could contact someone for me that would be...

    If you could contact someone for me that would be great. My email is in my profile.... I talked w/ a Mike .?. from Mechanicsberg, PA this morning and he told me that he doesn't think Carrier is...
  2. Replies
    7
    Views
    3,215

    I already seen those and took a look at them. The...

    I already seen those and took a look at them. The job I'm looking at has over 400 controllers throughout the buildings. I looked at the LON conversion module, but really would prefer to use a CCN...
  3. Replies
    7
    Views
    3,215

    Carrier CCN to Tridium AX

    I was wondering if anyone has successfully integrated to the Carrier Comfort Network either through RS485 or Ethernet. I would like to use a AX JACE to do the integration if possible. I know Carrier...
  4. Thread: N30 Interlock

    by jczekai
    Replies
    3
    Views
    514

    I always setup the interlocks like that, I use...

    I always setup the interlocks like that, I use the interlocks a lot w/ the VMA controllers and global commands like Morning Warmup, etc...

    I have never had a problem w/ it. Do you have the project...
  5. Replies
    9
    Views
    813

    We use all kinds of different controllers, mostly...

    We use all kinds of different controllers, mostly we choose by what fits application and has lon or bacnet comm on it. I didn't mean that in a bad way, the only time we have been using JCI is when we...
  6. Replies
    10
    Views
    1,445

    So all of the programmed N2 points would then be...

    So all of the programmed N2 points would then be available via BACnet just like a N30 controller?

    Thankx
    Jamie
  7. Replies
    9
    Views
    813

    To be honest, I have found so my reasons not to...

    To be honest, I have found so my reasons not to use the FX line of field controllers. I feel that JCI developed the controlers about 50% then released them to the contractors to deal w/ and BETA test...
  8. Replies
    20
    Views
    1,637

    From my experiene w/ PLC controllers, you usually...

    From my experiene w/ PLC controllers, you usually have to know quite a bit about the programming. This is b/c in the "RUNGS" you usually have to create coils and holding registers to view the values...
  9. Replies
    20
    Views
    1,637

    FYI, Here is a license from a FX40...

    FYI, Here is a license from a FX40...
  10. Thread: N30 Interlock

    by jczekai
    Replies
    3
    Views
    514

    In the interlock "Action Tables" select Override...

    In the interlock "Action Tables" select Override instead of the value from the "Command" drop down. Then select the "List Elements" box button, then select the value you want. Do it this way will...
  11. Replies
    9
    Views
    813

    I have done a few FX15 controllers in R2, it suxs...

    I have done a few FX15 controllers in R2, it suxs b/c you can't learn the NCIs into R2. What I had to do was create NVIs in FX Builder to adjust. It works fine doing this, you just have to make sure...
  12. Replies
    10
    Views
    1,445

    Is this something that JCI has to do w/ there...

    Is this something that JCI has to do w/ there configuration software or is it something that I can do through there web browser? I have all the passwords for the NAE but just haven't connected to it...
  13. Replies
    20
    Views
    1,637

    I would say not to use a JCI Integrator or FX40!...

    I would say not to use a JCI Integrator or FX40! Since the job is already N30s it most likely already has a M3 or M5 Workstation. I have used Integrators before, I basically ended up throwing it out...
  14. Replies
    10
    Views
    1,445

    ..:: NAE to Tridium AX via BACnet ::..

    Does anyone know if there is a way to expose the points in a NAE as BACnet/IP or another protocol that we could then intergrate the points into a Tridium AX system?

    Johnson came in on this...
  15. Replies
    9
    Views
    813

    Just send it to Tridium and they will make it...

    Just send it to Tridium and they will make it into a shadow odject for you! There is no way to make it yourself easily in R2. You could also just use a "DynamicDevice" in R2 and "Upload" the config...
  16. Replies
    5
    Views
    753

    The way we have done it in the past is purchase a...

    The way we have done it in the past is purchase a BCU, then expose the points as BACnet/IP. The BCU is a little high in price but it is cheaper than ripping out all the controls!
  17. Thread: FX40 and M3

    by jczekai
    Replies
    8
    Views
    1,691

    If you open the FX-40 controller, then open up...

    If you open the FX-40 controller, then open up the Bacnet "Jar" file on your palette....

    In the palette you should see a folder called "Point".........

    Expand the folder and you will see a...
  18. Replies
    21
    Views
    6,114

    Did you ever find a driver to communicate to the...

    Did you ever find a driver to communicate to the ASD bus? I have a campus that has hundreds of the Microzone controllers communicating to GCMs throughout the campus, then to a wonderware system that...
  19. Replies
    2
    Views
    645

    There is no demo with any flavor of workbench....

    There is no demo with any flavor of workbench. Its on a per computer license, and the license is digitally signed from Tridium (uneditable).
  20. Replies
    2
    Views
    633

    Go to the objects toolbar, then click outputs,...

    Go to the objects toolbar, then click outputs, add a Position Adjusting Time Output -- used for floating control

    Thankx
    Jamie
  21. Replies
    6
    Views
    1,179

    Y wouldn't you just buy the BACnet (IP or MSTP)...

    Y wouldn't you just buy the BACnet (IP or MSTP) or Lon Interface board from JCI/York. We have bought the both versions of the BACnet in the past. Its probably a lot cheaper and easier than...
  22. Replies
    8
    Views
    3,683

    Good luck, the trane software is very expensive...

    Good luck, the trane software is very expensive and is licensed on a per machine basis. NO SHARING AT ALL, and theres really no way around it besides sending lots of $$$$$$$$.
  23. Thread: York BAS

    by jczekai
    Replies
    16
    Views
    2,423

    Most of Yorks controls weren't porpritory b/c...

    Most of Yorks controls weren't porpritory b/c most they resold other manufacturers controls. Most of the York controls that I have seen are Delta Controllers repackage with the York name on it.
    ...
  24. Replies
    20
    Views
    1,599

    I never really created them, just heard of the...

    I never really created them, just heard of the ability to make them. They would have to be very generic graphics with no animations, pretty much just the data from a point. Then the canvas pane on...
  25. Replies
    20
    Views
    1,599

    Did you make different graphics? HX is used for a...

    Did you make different graphics? HX is used for a PDA, cell, etc. PX is used for IE, Firefox, etc.
Results 1 to 25 of 55
Page 1 of 3 1 2 3
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event