  1. Replies
    2
    Views
    514

    Proxy is part of a control point. It's the...

    Proxy is part of a control point. It's the mechanism making the read/write things over the network.
  2. Replies
    7
    Views
    915

    Using N2 through a Jace by Tunneling the serial...

    Using N2 through a Jace by Tunneling the serial port is tricky. Did work some times, but I got a lot of blue screens. That said, I would not recommend using that.

    Concerning FXVMA, it may not be...
  3. Replies
    25
    Views
    4,860

    Change Navigation Side bar for NAV one...

    Change Navigation Side bar for NAV one...
  4. Replies
    32
    Views
    2,918

    If using Windows 7, you should try using XP...

    If using Windows 7, you should try using XP Virtual machine to run Comm Pro N2. We have stopped trying to connect with Comm Pro directly (an our PCs have true DB-9 serial port...)

    XP Mode of...
  5. You have to understand that BACnet/ip traffic...

    You have to understand that BACnet/ip traffic will only work on the same subnet. BACnet/IP devices use broadcasting (that means every devices on the network will receive the information) and the...
  6. Replies
    0
    Views
    472

    CommPro N2 and Windows 7

    Any of you made it work ?

    PS : I know about JCI "Use Windows XP" thing...
  7. Replies
    5
    Views
    551

    I would think so. There are a lot of new features...

    I would think so. There are a lot of new features in newer version...
  8. Replies
    5
    Views
    551

    Nope... simulator sessions are saved only for the...

    Nope... simulator sessions are saved only for the actuel FXBuilder session.
  9. Thread: Siemens VFD

    by ctremblay
    Replies
    11
    Views
    792

    Add to all those reasons the fact that they are...

    Add to all those reasons the fact that they are rated for 575V max... if you're in Canada, where many of the site are 600V+... you know that some will be busted on the next big power outage...

    In...
  10. Replies
    8
    Views
    1,823

    oBix would certainly be something to look...

    oBix would certainly be something to look at...old Jace can continue doing their job, you just change the interface, and continue building on something up to date, keeping what's working untouched...
  11. I've tried those new drivers... 80% of my points...

    I've tried those new drivers... 80% of my points were STALE and I had to load the "Point page" of the device to wake them up... BQL querys were giving me 0 values (because of the "Stale state"......
  12. We saw the problem with FX-20, FX-40, FX-60...

    We saw the problem with FX-20, FX-40, FX-60
    Running version 1.2 (3.0.106) or 2.0 (3.3.22)
    Stations affected can be brand new / old doesn't matter.

    One thing in common : happens when there are...
  13. JArs and firmware up to date Solution found :...

    JArs and firmware up to date
    Solution found : reset the driver (force a read/write of all points) and you're on 'till the next time.
    Can't think it's the only thing to do !
  14. Replies
    7
    Views
    1,193

    Maybe you can use Analog outputs of the existing...

    Maybe you can use Analog outputs of the existing drive to reflect the actual current of the load, or its voltage... I usually set this up to reflect frequency...
    Depending on your drive model, could...
  15. Seriously, are we alone in the world getting...

    Seriously, are we alone in the world getting communication troubles with the N2 Driver ?
  16. Compared to Siemens Predators, they are just...

    Compared to Siemens Predators, they are just perfect !
  17. Thanks Same The capacitor trick on TEC gave us...

    Thanks Same

    The capacitor trick on TEC gave us more troubles... and this fix is supposed to work only for a certain batch of TEC (date code)... Actually, we have trouble with a lot of different...
  18. Glitches in N2 Comm with AX and FX controllers

    Any of you ever had trouble with N2 comm ?
    We have, most of the time due to an electrical flash that turns off a
    FX controller quickly enough for it to reboot...but not long enough
    for the station...
  19. Thread: Tridium Help

    by ctremblay
    Replies
    22
    Views
    1,069

    If those points are nvo, I would try to set them...

    If those points are nvo, I would try to set them to POLL ONLY, instead of bound... I did this for some controllers... and it worked fine
  20. Replies
    2
    Views
    686

    Some STMP servers require a "from@" adress to be...

    Some STMP servers require a "from@" adress to be specified...
  21. Replies
    23
    Views
    1,408

    I actually use jciN2 3.0.106.40 on old AX version...

    I actually use jciN2 3.0.106.40 on old AX version 1.2 and jciFXDriver 3.0.106.36
    (overridden patch works for that version)

    On version 2.0, jciN2 3.3.22.40 and jciFXDriver 3.3.22.39

    Never had...
  22. Replies
    23
    Views
    1,408

    A solution to the overriden message is available...

    A solution to the overriden message is available with the new jar files proposed by JCI. On the property sheet of the N2 Network, you can unhide the slot named "Use message override flag"... it will...
  23. Thread: FX07 and NAE

    by ctremblay
    Replies
    2
    Views
    433

    I know that you cannot send to the network a...

    I know that you cannot send to the network a Schedule variable linked to a schedule object inside your program... that's why I always use a simple variable linked to a PLC deciding of the...
  24. Replies
    19
    Views
    1,212

    Any example of string you're looking to modify ?

    Any example of string you're looking to modify ?
  25. Replies
    12
    Views
    1,028

    Be sure that you didn't try to write to ClgStpt...

    Be sure that you didn't try to write to ClgStpt AND HtgSetpt at the same time... it can cause troubles