Search:

Type: Posts; User: fl_kcsi

Search: Search took 0.00 seconds.

  1. Replies
    6
    Views
    699

    MDSkiffer, I'm just assuming they have a...

    MDSkiffer,

    I'm just assuming they have a Wizard for Niagara.

    They are the exact same controllers. Perform a 'Replace' and it just shows up as 'Failed.' I'm perplexed as to why it wouldn't work...
  2. Replies
    6
    Views
    699

    Unfortunately, doing a Replace via LON Device...

    Unfortunately, doing a Replace via LON Device Manager did not work. This is what the previous guy had said, I just had a hard time believing that a direct replace wouldn't work.
    Any of the Siemens...
  3. Replies
    6
    Views
    699

    Staefa Talon wizard for Niagara

    I have a job with Staefa Talon controllers and we have integrated some Carrier controllers and Distech on the Jace. I have a controller with a bad output and while I would love to have the program to...
  4. Replies
    23
    Views
    4,584

    :-) Yeah, probably. I'm pretty comfortable...

    :-)

    Yeah, probably. I'm pretty comfortable with the gfx stuff though. The lon and AX part of that 2nd week shouldn't be too bad then, and outside of learning the BacNet side, the overall...
  5. Replies
    23
    Views
    4,584

    I'm going to be taking a Tridium course, also. ...

    I'm going to be taking a Tridium course, also. However, I'm doing the Distech-sponsored Niagara course in Atlanta in March. I'm also staying the 2nd week for their gfx training so we can purchase...
  6. Replies
    12
    Views
    1,232

    Their original front end was VI. They had a...

    Their original front end was VI. They had a major power issue which took out 12 controllers all at once. We replaced those with Distech and put in an iLon. At about the same time, the power supply...
  7. Replies
    12
    Views
    1,232

    No offense taken, I understand your point. ...

    No offense taken, I understand your point. That's what I'm trying to learn. I appreciate your help.
  8. Replies
    12
    Views
    1,232

    I don't blame them for protecting their...

    I don't blame them for protecting their intellectual property. I was just under the impression that plug-ins were readily available for most lon vendors, so I've been surprised at the difficulty...
  9. Replies
    12
    Views
    1,232

    I understand what you're saying Amigo. My...

    I understand what you're saying Amigo. My exchange with Circon never touched on the quality of work, etc. I explained that I had a customer in which we service all of their buildings, one of which...
  10. Replies
    12
    Views
    1,232

    Circon Plug-ins

    I have been in contact with someone at Circon because a job we service has their equipment. We are not a Circon vendor, but are able to service any Lon network. When asking about acquiring their...
  11. Thanks guys for all the help/suggestions. It is...

    Thanks guys for all the help/suggestions. It is clear that this equipment is not supported from Honeywell anymore and we don't have any old (working) laptops and SLTA connections laying around. ...
  12. I understand what you're saying about the E-bus...

    I understand what you're saying about the E-bus versus Lon, but I am able to create a network in LonWatcher and connect to the devices with the standard Lon Browser.

    Also, I downloaded RB4 and...
  13. Honeywell W7751's Version 1 calibration issue

    I've got a building that has a bunch of W7751's. They're v1's (1.02.13, date code 2001) and I've been told that both the commissioning software and the compatible plug-in are both unavailable. I've...
  14. Replies
    11
    Views
    759

    You'll need to update the iLon first. What...

    You'll need to update the iLon first. What version is it? When you go into 'Standard', after everything loads, there should be some text towards the bottom-right of screen above toolbar; i.LON 100...
  15. Replies
    7
    Views
    1,147

    Well, got the Trane equipment back; Lonwatcher...

    Well, got the Trane equipment back; Lonwatcher must have changed the ZL. Had to do a Rebuild on the Summit and re-add the 581's. Their version of Rover is 5. I couldn't find anything in the book...
  16. Replies
    7
    Views
    1,147

    I commissioned them in Lonwatcher as a last...

    I commissioned them in Lonwatcher as a last approach just to prove to myself that the network was okay to true Lon standards. Without any of the devices configured in Lonwatcher, the Summit would...
  17. Replies
    7
    Views
    1,147

    Tron is the devil!

    So, this Trane "Lon" thing...

    Trane likes their Comm5 to be daisy-chained, I get that (now). I needed to add some RH sensors to a network and used BAPI L-Combo. Ran a star-config on the sensors,...
  18. Replies
    53
    Views
    6,035

    The need basis is really my dilemna also. I'm...

    The need basis is really my dilemna also. I'm going to be putting in a Lennox Signature 2-stage HP with variable speed air handler. I would like to throw in a Lon network and put a Distech ECP-103...
  19. Replies
    2
    Views
    441

    Circon plug-ins with Lonwatcher

    I've got a few Circon controllers on a job and I even have the plug-ins (supposedly) that I pulled out of the NI folder. The 2 files I was found were BASICPlugIn and Circon3xxPlugIn. The...
  20. Replies
    7
    Views
    1,229

    May not be using correct terminology, but I'm...

    May not be using correct terminology, but I'm calling Standalone on an e3 similar to that of a Smart, as in no front end server being used. It is just (1) 100 and 3 L-IP's, one router for each...
  21. Replies
    7
    Views
    1,229

    I was actually able to get it back. At the time,...

    I was actually able to get it back. At the time, I was getting a WARNING when rebooting via the console that there was an issue with the shutdown process. It would otherwise reboot normally and...
  22. Replies
    7
    Views
    1,229

    Have I "bricked" a Smartserver?

    I was trying to downgrade an Echelon Smartserver 2.0 to an e3. This was supposed to be a quick job and I needed to turn the graphics around quickly and didn't really have the time to work with a new...
  23. Replies
    7
    Views
    718

    The trends or alarms are not being monitored by...

    The trends or alarms are not being monitored by the customer in the first place. The schedules I'll have to look into.
  24. Replies
    7
    Views
    718

    Wow, thanks, I'll have to try that. I just...

    Wow, thanks, I'll have to try that. I just didn't like the idea of sitting in the customers office tinkering or I would have been apt to try it on my own. This gives me some things to try. I...
  25. Replies
    7
    Views
    718

    Can I add the Distech devices using VI? I've...

    Can I add the Distech devices using VI? I've extracted the db from the NI folder and created it in LonWatcher. I'm wondering if I would be better off creating the devices in LW and then adding the...
  26. Replies
    7
    Views
    718

    Adding Distech to Circon VI?

    We have a service contract on a job with Circon. They had a major power issue and have 2 AHU controllers and 10 VAV controllers to be replaced. My experience is with Distech and I'm wondering how...
  27. Replies
    25
    Views
    2,920

    TL averaging

    Holy crud buckets, y'all are fantastic. I've been struggling with the same thing on an older job that I've been trying to tweak. I never realized that the FAN_IN_AV was an internal calculation of...
  28. Replies
    4
    Views
    696

    Similar problem, schedule sent/received wrong

    I have a similar problem that I have never encountered before. Dapper's answer may be the same, but thought I'd throw it out there.

    I have 4 or 5 Distech RTU-L's on a network of like 25 attached...
  29. Replies
    10
    Views
    587

    Just signed up over there now, dapper. Thanks...

    Just signed up over there now, dapper. Thanks for the heads up on their forum! I know that at least one of the customer's config'ed his schedules correctly. He is on his system like 5 hours a day...
  30. Replies
    10
    Views
    587

    381, Don't take this issue as anything that...

    381,

    Don't take this issue as anything that may influence your confidence in these servers. They are great devices. Our problems with them have been minimal over the last 4-5 years since we...
  31. Replies
    10
    Views
    587

    I could possibly set up an alarm for the schedule...

    I could possibly set up an alarm for the schedule even though I don't know of a point that I could use which would identify data within the .xml file. I'm sure I could work something up to do this. ...
  32. Replies
    10
    Views
    587

    No, all the schedules were entered by the...

    No, all the schedules were entered by the customer through the web interface in both instances. Very maddening. I'm just worried that it IS some kind of firmware issue and dreading the thought of...
  33. Replies
    10
    Views
    587

    We only use the web interface. I went in through...

    We only use the web interface. I went in through the plug-in last night and found out what you just confirmed about using both. Customers only have web interface and usually only on the standard...
  34. Replies
    10
    Views
    587

    Ilon losing schedules

    I have had two Ilon e3's lose their schedules in the last week. Here is what is happening. Our customers are configuring their schedules through the ilon. One particular ilon, the customer would...
  35. Replies
    3
    Views
    1,081

    Honeywell 15B or W7760B problem...

    Alright, I have a problem with a Honewell Excel 15B server that is only about a year old. It's controlling a chiller plant at a school and was working fine until recently. Basically, it stopped...
  36. Replies
    2
    Views
    813

    web page set up

    Inside the box for the iLon there is a disc. On that disc is a trial version for Macromedia Contribute. It is using this software that you can add the 'Show Value' to enable you to add data to your...
  37. Replies
    5
    Views
    815

    I'll try that. I haven't done a whole lot of...

    I'll try that. I haven't done a whole lot of programming. I've done the web design for about 10 of our ilon's in the year I've been in this industry and just starting to do programming. Thanks!
  38. Replies
    5
    Views
    815

    Ah, translation rules. I haven't done any of...

    Ah, translation rules. I haven't done any of that yet, but it makes sense. I know I need to make the multiple presets, just didn't know how to assign a range of numbers to each one of those. As...
  39. Replies
    5
    Views
    815

    iLON snvt_count_inc preset range

    Alright, so I'm trying to do an image swapper for a damper. Distech supplies 11 different damper graphics, representing the damper from 0-100% open in increments of 10%. What I can't figure out...
  40. Replies
    4
    Views
    707

    Let me verify some details first. The SNVT...

    Let me verify some details first.

    The SNVT type in the software is the temp_p#US, right? Now the iLON should pull out that SNVT the same on the web side. Have you verified what SNVT the iLON is...
  41. Replies
    12
    Views
    1,748

    Distech allows you to log within the free...

    Distech allows you to log within the free programmable controllers which is the closest to monitoring you'll get without an iLON. As long as your job is $20k+, there is no reason to not build an...
  42. Replies
    3
    Views
    477

    We have always done the scheduling on the web...

    We have always done the scheduling on the web side. The biggest benefit to this is your customers can config their own schedules and don't have to bother you to do it.
  43. Replies
    2
    Views
    744

    The bootrom file is for the 3.02.07, which is...

    The bootrom file is for the 3.02.07, which is what the original firmware was for. The files I copied over were from an ilon that I had only done the updates for and not added any web folder, so...
  44. Replies
    2
    Views
    744

    Ilon error after updates

    I'm getting an error on my ilon that is new to me. I did the 2 Distech updates, #'s 4 & 5 for Time Zone and IE6+ problems. When I tried to go back into the Service side, I got this error: ERROR:...
  45. Replies
    2
    Views
    659

    Thanks! That helps a lot.

    Thanks! That helps a lot.
  46. Replies
    2
    Views
    659

    Card Access using Distech

    I have a building with the Distech EC-ACC controller set up with all the other hardware needed for the card access. The problem I am having setting it up is that everywhere I look, it seems as if I...
Results 1 to 46 of 46