Search:

Type: Posts; User: Keith D

Page 1 of 5 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    2
    Views
    321

    Looks to me like the Invisibility.jar file is the...

    Looks to me like the Invisibility.jar file is the wrong version. :-)
  2. Replies
    13
    Views
    749

    It was some time back and my memory may not be...

    It was some time back and my memory may not be serving me well, but as I remember it we were having some trouble with an XL10 fan coil unit controller.
    I had a copy of on my laptop Lonmaker for...
  3. Replies
    13
    Views
    749

    So you are sure that if you change a setpoint on...

    So you are sure that if you change a setpoint on one of your XL-10 devices you can see a change in one of the outputs?
    You can use the search facility to get the points you need and display their...
  4. Replies
    13
    Views
    749

    It certainly appears that you have lost the...

    It certainly appears that you have lost the mapping in the zone manager. Or it may simply be in an offline state.
    I cannot see how losing the supervisory computer has lead to this situation though....
  5. Replies
    7
    Views
    607

    I believe from memory that on the earlier...

    I believe from memory that on the earlier outstations it was possible to destroy an IQ3 if the firmware upgrade was interrupted during its process. I know this happened to me on an early version of...
  6. Replies
    3
    Views
    372

    If you have a working licenced copy of SET, which...

    If you have a working licenced copy of SET, which you need to perform the firmware download then you should have been given a Trend P-net login. If not then contact your local Trend office and they...
  7. Replies
    12
    Views
    895

    My bad, I didnt look at you original post well...

    My bad, I didnt look at you original post well enough.

    I have only connected via I/P to Bacnet with SymmetrE (same as EBI but without the fire or legacy interfaces)

    If you need to go down the...
  8. Replies
    5
    Views
    565

    Dave I think when running a station on your...

    Dave

    I think when running a station on your local workbench pc it connects via Localhost. I'm not 100% sure of this however, perhaps someone could confirm.

    Have you tried creating a new station...
  9. Replies
    12
    Views
    895

    Firstly you need to ensure that you have the...

    Firstly you need to ensure that you have the Bacstac protocol installed.
    This should be found on the EBI installation CD, probably under the Third party folder.

    Im assuming you have this already...
  10. Replies
    5
    Views
    565

    Have you started the Daemon before starting your...

    Have you started the Daemon before starting your Workbench?

    You can find the niagarad.exe in the bin folder, just double click it and a dos window will pop up for a short while.

    You can check...
  11. Replies
    0
    Views
    231

    Niagara Px Bound Label Binding

    In a standard Bound Label Binding the 'popupEnabled' slot is by default set to True.
    Is there a way to alter this default to False for the entire station, so that subsequent points that are dropped...
  12. Replies
    55
    Views
    4,968

    In the networks comparison chart I dont see any...

    In the networks comparison chart I dont see any mention of Mstp.
    I thought this would be at the layer of Network or Data Link.

    Am I wrong? if so tell me why please...
  13. Replies
    17
    Views
    1,145

    XBS

    As you have correctly assumed, getting a Jace is not such a straightforward option.
    It can be done however but there may well be a fair bit of other kit and time you would need to pull it off.
    You...
  14. Replies
    17
    Views
    1,840

    Nice info Digo. I will give this a tryout.

    Nice info Digo.

    I will give this a tryout.
  15. Replies
    32
    Views
    1,795

    I see in a previous post about this exact problem...

    I see in a previous post about this exact problem that it was recommended not to commission the network.
    I assume you have now performed a commission, as that would surely reconfigure the echelon...
  16. Replies
    16
    Views
    3,135

    Saeed, In CARE you need to select the position...

    Saeed,

    In CARE you need to select the position of the NI in the lower network sidebar.
    Sorry I dont have my CARE laptop with me to remember the names of certain things.

    In the lower window...
  17. Replies
    16
    Views
    3,135

    Saeed, First of all you will need a dongle...

    Saeed,

    First of all you will need a dongle licenced for CARE with LNS.
    Secondly you need to install a program called 'Remote Synch Server' on the PC running the LNS database.
    Thirdly you need to...
  18. Replies
    11
    Views
    863

    Nice info tim

    Nice info tim
  19. Replies
    11
    Views
    863

    You copied it into your modules folder and then...

    You copied it into your modules folder and then restarted your workbench, yes?

    If its still not available locally then is it of a later version? i.e. a 3.7 module in your 3.6 workbench,
    never...
  20. I only mentioned port 1911 as its been around a...

    I only mentioned port 1911 as its been around a while and caught me out a few times until I put a sticker on the front of my laptop to remind me.

    The port may be blocked by your service provider....
  21. Replies
    7
    Views
    757

    That console output looks normal to me up till...

    That console output looks normal to me up till the end.

    Have you tried a Clean Dist and/or running the station up in your workbench?
    Also what version of AX is this and I assume you have the...
  22. You have Mail.

    You have Mail.
  23. Port 1911 blocked by a firewall by any chance?

    Port 1911 blocked by a firewall by any chance?
  24. Replies
    16
    Views
    2,083

    You might like to have a look at this....

    You might like to have a look at this.
    http://www.cbusopcserver.com/
    Never used it or heard of anyone else using them.

    Keith
  25. Replies
    17
    Views
    919

    I would have thought that Alerton have some sort...

    I would have thought that Alerton have some sort of 'Reset' block or code.
    i.e. when input is at level 'a' then output = x
    when input is at level 'b' then output = y
    any input between a or b = a...
  26. Replies
    17
    Views
    919

    I'm sure many would be able to help here, but...

    I'm sure many would be able to help here, but what line of controls are you talking about?

    You need to describe what inputs and outputs you have.
  27. Replies
    2
    Views
    387

    Could mean that there is some sort of corruption...

    Could mean that there is some sort of corruption of your alarm database.
    I would be tempted to run some alarm database maintenance and possibly delete everything in it (If you dont need a record of...
  28. Replies
    13
    Views
    1,180

    Stability, Your English is better than my...

    Stability,
    Your English is better than my German.
    Do you really have a 1 second derivative time? I bet that's a bugger to stabilise!

    Keith
  29. Replies
    13
    Views
    1,180

    I would be a bit wary of having one loop enabling...

    I would be a bit wary of having one loop enabling the other, but if you've tried it out then give it a go.

    As for you gas heating then yes you will need a fairly wide prop band. Perhaps you might...
  30. Replies
    6
    Views
    597

    We use this type of PSU all the time. I haven't...

    We use this type of PSU all the time.
    I haven't had one go on me yet.

    https://partners.trendcontrols.com/trendproducts/cd/en/pdf/en-tg201128-uk0yr0311.pdf

    The psu info is on page 5
  31. Replies
    13
    Views
    1,180

    OOPs! Somehow lost the attachments there. Now I...

    OOPs!
    Somehow lost the attachments there.
    Now I cant edit my post so they are here.

    Single loop
    495811

    Two loops
    495821
  32. Replies
    13
    Views
    1,180

    The best thing I find with AX is that you can...

    The best thing I find with AX is that you can fiddle around with the strategy on a 'Dummy' controller on the laptop, its the best way to learn and what you do learn you can save to your own Palette...
  33. To change the existing ones (I assume you mean in...

    To change the existing ones (I assume you mean in a Px page)

    In workbench, select the px page you have trouble with and view it, then click on the top right drop-down box and select 'text file...
  34. Replies
    1
    Views
    294

    Missing module help

    Hi guys

    Having a little trouble running a backup of an M2M jace into my workbench.

    Keep getting the following error.

    ERROR [20:44:59 11-May-14 BST][sys] Cannot load station...
  35. Replies
    8
    Views
    537

    Just been nosing around the Centraline...

    Just been nosing around the Centraline Partnerweb, and I cant see any mention of Coach 3.0

    Now I dont use this software, but I know there is the ability to request License upgrades in the License...
  36. Replies
    8
    Views
    537

    Were Jeff or Jim no help to you?

    Were Jeff or Jim no help to you?
  37. Replies
    20
    Views
    1,226

    If you have a Bacnet spyder then you are out of...

    If you have a Bacnet spyder then you are out of luck my friend.
    The XL-10's (Post #8) wont talk natively to a Bacnet spyder unless you have a WEBs or some other form of Jace or gateway between them.
  38. Replies
    55
    Views
    4,968

    Blimey, This is starting to take me back to the...

    Blimey,
    This is starting to take me back to the days when Sysint and Bacnet would have a complete war of words over this subject.

    I kind of miss them really.
  39. Dim question I know but the C-Bus baud rate is...

    Dim question I know but the C-Bus baud rate is ok? poss 9600 or 76800 depending on what version devices you have on your C-Bus.
    You may already have something addressed at 29?
    C-Bus connected the...
  40. Thread: jace branding

    by Keith D
    Replies
    53
    Views
    3,376

    I just hope they dont lose any backward...

    I just hope they dont lose any backward compatibility in R4 with AX.
    Even better would be to make R4 talk seamlessly with AX and R2 devices, maybe even bringing out a patch to allow an AX...
  41. Thread: SymmetrE

    by Keith D
    Replies
    5
    Views
    390

    If you are going to replace the field controller...

    If you are going to replace the field controller with a like for like device then so long as its an Excel5000 device (See prtadko post for types) then you should be able to upload to SymmetrE and...
  42. Replies
    16
    Views
    2,083

    Thanks for the info krac. It certainly looked as...

    Thanks for the info krac.
    It certainly looked as if the Neopsys solution had most of the important bases covered.

    I have tried the Honeywell C-Bus driver (normally runs on a JACE) in a demo mode...
  43. Replies
    9
    Views
    1,016

    I think your version of Workbench will also need...

    I think your version of Workbench will also need the license files to get the HoneywellSpyder.jar file to work as well. I nearly always create and download from a PC version of the station, then...
  44. Replies
    16
    Views
    2,083

    krac, Keep us informed on how this goes would...

    krac,

    Keep us informed on how this goes would you.
    Would you post info on drivers used parts etc?

    I have yet to perform one of these upgrades but the level of info requests is creeping up, so...
  45. Replies
    16
    Views
    2,083

    Check that you have either the XPC500 board (PCI...

    Check that you have either the XPC500 board (PCI board with a two core connector out the back of it) or if not then you should have a BNA somewhere, connected to an Ethernet lead.
    If you have the...
  46. Thread: Station Copy

    by Keith D
    Replies
    2
    Views
    363

    I take it that this FX60 is not controlling...

    I take it that this FX60 is not controlling critical plant, and you have the opportunity to muck around with it and not break any plant.

    If you use the station copier and nothing else has changed...
  47. Thread: Sigmagyr RVL55

    by Keith D
    Replies
    4
    Views
    2,122

    Frank, Stick an Email contact in your profile...

    Frank,

    Stick an Email contact in your profile will ya.

    Keith
  48. Replies
    2
    Views
    356

    A few things spring to mind here. 1. Assuming...

    A few things spring to mind here.
    1. Assuming this is running in a copy of Workbench or some such flavour, then check the Tools> Options> General..Unit conversion, this may be set to Metric. Try...
  49. You haven't lost the little green plug in your...

    You haven't lost the little green plug in your XW584 lead have you? If so then its possible to plug it in upside down. It wont work either (experience)

    Keith

    442321
  50. TAC MNL-11R no values when connected to Jace

    I have a slight headscratcher problem.

    I have replaced a TAC MNL-11RF3 controller on a LON bus with a new identical device.


    At the Jace, the replacement went as planned with the device now...