  1. Replies
    12
    Views
    1,478

    No where in the "yup read above" does it mention...

    No where in the "yup read above" does it mention baud rate ..... maybe you are too smart for all of us and knows "and stuff" is baud rate!!

    Maybe next time you should read the post before your...
  2. Replies
    12
    Views
    1,478

    Did you check the baud rate? They default at...

    Did you check the baud rate? They default at 76,800. Connecting to the USB port is not the same as the mstp comm.
  3. Replies
    1
    Views
    769

    I typically use the device instance, there are...

    I typically use the device instance, there are other options. Have you read the BACnet integration guide for i-Vu? I should have been on the tech tools cd.

    The second network is for the non-open...
  4. Replies
    4
    Views
    1,866

    They are there, select FILES at the top, then ALL...

    They are there, select FILES at the top, then ALL FILES on the right. They are on the 1st page titled "FX-MSTP Controllers-Wiring 4_15_13".

    You do know they recently moved everything to a format....
  5. Replies
    11
    Views
    1,241

    AFAIK only the FX-16 can be uploaded. It was a...

    AFAIK only the FX-16 can be uploaded. It was a feature they added after the original release.
  6. It does not appear to matter if a conventional...

    It does not appear to matter if a conventional thermostat is used or a zone sensor. With conventional stat control, the unit should not need to know occupied/unoccupied as it will follow the stat...
  7. They changed control boards over the years. The...

    They changed control boards over the years. The older ones needed a CTI (Conventional Thermostat Interface) board. The newer Reliatel's can do both. So it depends on the unit and control package the...
  8. Replies
    30
    Views
    3,075

    There will need to be two (2) CCN address in the...

    There will need to be two (2) CCN address in the UPC.

    One is the CCN address of the RTU the UPC needs to talk to ..... Properties > Control Program > Status > CCN (default is 0,1). This should...
  9. Replies
    13
    Views
    1,383

    You will need a Lon adapter. I use the USB--->Lon...

    You will need a Lon adapter. I use the USB--->Lon adapter that was provided with my Trane Rover v7 Service Tool kit. It also did work with the PCMIA--->Lon adapter that I had with Rover v6.0
  10. Replies
    10
    Views
    1,242

    I am corrected :oops: The CIV-IM was used...

    I am corrected :oops:

    The CIV-IM was used with i-Vu v3.0. It is not used with versions v4.0, v5.0 or v6.0 that Carrier sold to independent contractors. How did you manage to get one? As...
  11. Replies
    13
    Views
    1,383

    Sounds like the programs in the controllers are...

    Sounds like the programs in the controllers are different. I would use NodeUtil to get the the xif out of the controller then create your own lnml. With the xif out out of the controller you will...
  12. Replies
    10
    Views
    1,242

    I doubt you have a CCN Integrator. What is the...

    I doubt you have a CCN Integrator. What is the part number of your device? AFAIK the CCN Integrators were Carrier only and used with i-Vu v3.0, which was also Carrier only. I think what you purchase...
  13. Replies
    9
    Views
    1,268

    Have to tried going back to Maxline through your...

    Have to tried going back to Maxline through your support channels?

    I had an issue last summer with their driver on a couple comm4 chillers. Once my local support channel put me in touch via email...
  14. Replies
    10
    Views
    2,557

    Sounds like you have everything correct. Are you...

    Sounds like you have everything correct. Are you seeing the Open devices in FA?

    The discovery will not populate the third-party devices with the Open devices. Even when they are wired to the same...
  15. Replies
    10
    Views
    2,557

    I assume you have i-Vu v6.0 as you are installing...

    I assume you have i-Vu v6.0 as you are installing the Carrier front-end?

    Are you using an OpenLink or CCNLink to integrate the BACnet units?

    What location under Installer are you attempting to...
  16. Replies
    4
    Views
    659

    Once the point is Network Visible, I typically...

    Once the point is Network Visible, I typically map a point with this typical address: exp:#eq_1619519_1 /dew_pt. This mapping is getting the dew point value from device #19 on network 16195. Another...
  17. Replies
    8
    Views
    1,050

    Try the link below. Scroll down the list, it...

    Try the link below. Scroll down the list, it should be the fourth download in the list. You will need a standard USB to Printer cable to connect to the device. This is the cable most newer USB...
  18. Replies
    10
    Views
    1,208

    Post the serial number with the model number. I...

    Post the serial number with the model number. I can lookup the unit easier with the serial number to see how it was shipped .....
  19. Replies
    25
    Views
    1,980

    Sounds like a broadcast acknowledger problem as...

    Sounds like a broadcast acknowledger problem as you are able attach to the device after getting the loading table and communications failure during the attach. Are you getting the loading table and...
  20. Replies
    25
    Views
    1,980

    Sounds like the system pilot security options,...

    Sounds like the system pilot security options, you can access just about everything with a system pilot that NSTV can access. Try the following ....

    The current security level can be overridden...
  21. Replies
    1
    Views
    567

    The basic lead/lag that Carrier offers in their...

    The basic lead/lag that Carrier offers in their PICS's are only for the chillers. They don't offer anything in the package units.

    Not sure which PIC's you have in the package units, but you will...
  22. Replies
    1
    Views
    672

    The UCM's should be Comm4 as the CCP is 1997. If...

    The UCM's should be Comm4 as the CCP is 1997. If you have Rover with Comm4 cable you can check. With the relay board in the VariTrac CCP, there should be no comm to the RTU.

    You should be able to...
  23. Replies
    3
    Views
    1,000

    SketchUp ???? (http://www.sketchup.com/) It is no...

    SketchUp ???? It is no longer owned by Google, Trimble Navigation bought it in 2013 .....
  24. Thread: Trane varitrac

    by Balibe
    Replies
    8
    Views
    1,040

    Contact your local Trane salesman for the...

    Contact your local Trane salesman for the VariTrac software and cable. All they have for download on their website is update v12sp6.

    If you have Rover, you can access the zone controllers but...
  25. Thread: Trane varitrac

    by Balibe
    Replies
    8
    Views
    1,040

    Version 6- uses HyperTerminal, beige panel cover...

    Version 6- uses HyperTerminal, beige panel cover with a 2 line lcd display. Version 10+ uses VariTrac software, white panel cover with touch screen.
  26. Thread: MCS CONTROLLS

    by Balibe
    Replies
    1
    Views
    448

    I have integrated a few of these controllers. The...

    I have integrated a few of these controllers. The ones I have dealt with have been programmed specifically for the chiller/scu it controls and not a generic program.

    I would call their tech...
  27. Replies
    40
    Views
    17,304

    FYI ..... Each software requires a separate key...

    FYI ..... Each software requires a separate key to use the software. The ComfortView Key will not work with NSTV and requires additional adapters. The NSTV USB Converter/Key will not work with...
  28. Replies
    3
    Views
    700

    Below are the LED indications, these are for the...

    Below are the LED indications, these are for the BACnet flavor. There does not seem to be a way to reset the card. Verify the 24vac, if someone switched the + and Com to the translator & chiller pic...
  29. Replies
    9
    Views
    1,631

    I also use comfortsite, the drawing is not there...

    I also use comfortsite, the drawing is not there in the elibrary or under the unit information. From the unit manuals, you have the correct drawing number. There were two units originally ordered,...
  30. Replies
    9
    Views
    1,631

    Post the serial number of the unit, it will be...

    Post the serial number of the unit, it will be easier to lookup with that versus the drawing number .....
  31. Replies
    4
    Views
    695

    A filter for displayname like *DPR* will show all...

    A filter for displayname like *DPR* will show all points with DPR in the name. Works good if you have several points like DPR_O_1, DPR_O_2, etc.

    There is also the option above the filter to narrow...
  32. Replies
    8
    Views
    1,093

    I have used the gateway linked below for comm4...

    I have used the gateway linked below for comm4 vav's, it has worked great with no issues for a couple years. I have not used it on anything else but comm4 vav's, but it states it also works with...
  33. I also like to use the SunPostion. If you need it...

    I also like to use the SunPostion. If you need it earlier/later, just add/subtract to the angle. Typically just a couple degrees
  34. Replies
    3
    Views
    752

    To reiterate mcquire07, the controller must be...

    To reiterate mcquire07, the controller must be off the network for the controller to reply it's address when scanned with 0,0. It is rare, but there a few devices that will not reply to 0,0 like...
  35. Replies
    3
    Views
    651

    It is a separate program, you will find it in the...

    It is a separate program, you will find it in the Programs\ComfortView folder with all the other shortcuts ....
  36. Replies
    5
    Views
    1,146

    You can globally broadcast a single point from a...

    You can globally broadcast a single point from a CC6400 only if the point name is the same in all controllers needing it and the point is writable. The fire shutdown (FSD) in Plinks is a network...
  37. Thread: Ivu server

    by Balibe
    Replies
    6
    Views
    1,070

    Witt no DHCP server as you are directly...

    Witt no DHCP server as you are directly connected, it will take longer for i-Vu to provide the DHCP to the computer versus a network with a DHCP server.

    Once the i-Vu fully restarts and you have...
  38. Replies
    13
    Views
    2,098

    Try 85760430 I did an OPM with 17 units on it...

    Try 85760430

    I did an OPM with 17 units on it with a Chipkin FieldServer. This password is in the config file. I also integrated a CSC panel with Chipkin FieldServer and it was the same password....
  39. Replies
    7
    Views
    1,675

    I have had a similar issue in the past, so make...

    I have had a similar issue in the past, so make sure you verify ..... The older HMI panels may not work with a LCI/BCI. If they are that old you may need to also replace the HMI panel so a LCI/BCI...
  40. Replies
    2
    Views
    716

    In addition to roadgear ..... Typically XIF's...

    In addition to roadgear .....

    Typically XIF's are used for LON integration. The AX platform will use the XIF to create a LNML, which will map out the points based on the XIF with point details...
  41. Replies
    10
    Views
    2,557

    We just had a similar issue with a BCI-R shipped...

    We just had a similar issue with a BCI-R shipped in a unit from Trane.

    Is this a newer unit with the 3 rotary dials for the address? What is the baud rate of your network? Trane ships them at...
  42. Replies
    12
    Views
    2,113

    If a program is created in Snap or edited by Snap...

    If a program is created in Snap or edited by Snap and saved, it cannot be opened with EquipmentBuilder. It can only be opened/edited with Snap.
  43. Replies
    16
    Views
    2,337

    I have never seen this error before either. Have...

    I have never seen this error before either. Have you sent the error thru your local support channels?

    The tech tools cable did not change. You cable sounds good as you find and start uploading.
    ...
  44. Replies
    16
    Views
    2,337

    If these are new controllers I would agree you...

    If these are new controllers I would agree you need v6.0. It would be a good idea to load the August Cumulative Patches into FieldAssistant before you upload. They have made driver changes since the...
  45. Replies
    1
    Views
    825

    Do you have the recent patches installed? The...

    Do you have the recent patches installed? The cumulative patch releases for i-Vu also need to be applied to Field Assistant, which will also patch Snap & Equipment Builder if installed.

    Start...
  46. Not sure if it is wise to remove the CCN...

    Not sure if it is wise to remove the CCN ComfortLink Controls and replace with another controller.

    Carrier sells an Open UPC that will convert the CCN controls to BACnet MS/TP. Not sure if you can...
  47. Version 6 and down is accessed with...

    Version 6 and down is accessed with Hyper-Terminal. Version 10 and up is accessed with Trane's Tracker software.
  48. Replies
    6
    Views
    1,185

    You can find older versions here .......

    You can find older versions here .... http://www.oracle.com/technetwork/java/javase/downloads/java-archive-downloads-javase7-521261.html

    There are version all the way back to v7u1 on this page,...
  49. Thread: Trane VSEE vav

    by Balibe
    Replies
    5
    Views
    1,261

    +1 .... don't reuse the existing assembly. We...

    +1 .... don't reuse the existing assembly.

    We retrofit a lot of these, they are very common in my area. We are in the process of doing two floors with 60 of these per floor.

    We pull the...
  50. Replies
    3
    Views
    825

    +1 Rover will not configure a BCU. You will...

    +1

    Rover will not configure a BCU. You will not be able to access the BCU with a display by just adding one. They are configured, setup and downloaded to a BCU with Summit.