  1. That is interesting. I was hoping you would say...

    That is interesting. I was hoping you would say I was not necessarily the only one with this issue. But I suppose I might be one of only a few to notice what it does. I mean, as long as it keeps...
  2. Thanks again for the time and the effort to help...

    Thanks again for the time and the effort to help me! I will see about swapping it. What changes or "fixes" are addressed with the "ad"? -Mike.
  3. ab....

    ab....
  4. Thanks jrbenny, I appreciate the clarification. ...

    Thanks jrbenny, I appreciate the clarification. HOWEVER, the 04 is still screwing up. Coming out of a setback on hp from 67 to 69, hits second stage immediately because I have the upstage set at...
  5. Goodman ctk04 with modulating gas furnace

    2 stage hp with ctk04 and modulating furnace. Set up parameters have upstage temp differential settings from stage 1 hp to stage 2 hp and stage 2 hp to backup. Also has this from stage 1 to stage 2...
  6. Replies
    15
    Views
    555

    Without seeing the program, would think it would...

    Without seeing the program, would think it would be as simple as ignoring the tstat until the defrost subroutine completed, but that could be wildly simplistic. I'm also guessing I might be the only...
  7. Replies
    15
    Views
    555

    Hi jrbenny! I don't understand your reply.. ...

    Hi jrbenny! I don't understand your reply.. but I think you may seem offended, and offending anyone is the last thing I intended! Can you clarify what you meant?
  8. Replies
    15
    Views
    555

    Improving defrost logic

    Goodman HP. It seems silly that if the call for heat ends in the middle of a defrost cycle that the defrost cycle ends, then starts in a defrost cycle at the beginning of the next call for heat....
  9. Update: Been out of AC weather, but just now in...

    Update: Been out of AC weather, but just now in HP weather. There is now 18/2 shielded solid copper run along side of the current non-shielded 18/4, using this new wire for the communication pair...
  10. Completely true. But it seems to me that good...

    Completely true. But it seems to me that good care was taken to route the wires responsibly.. Would you agree based on my description?
  11. I took a close look at the t-stat wiring. There...

    I took a close look at the t-stat wiring. There are two wires coming out of the furnace on the opposite side where the supply voltage enters the furnace. It runs up the side of the furnace then...
  12. Within 2 miles. I am just south of 422 off...

    Within 2 miles. I am just south of 422 off rapids road. That's too funny.
  13. Ha, small world. You were very close to me.

    Ha, small world. You were very close to me.
  14. Ohio?

    Ohio?
  15. Thank you. However cooling season may be done...

    Thank you. However cooling season may be done for the year!
  16. Have some shielded 18/4 cable at work used for...

    Have some shielded 18/4 cable at work used for our surveillance system, but it is stranded not solid. Would this be appropriate?
  17. Hm... water softener IS on the furnace breaker. ...

    Hm... water softener IS on the furnace breaker. Wow that is a pretty benign item.. hard to imagine that little timer motor causing problems. Could unplug that and see but that would really...
  18. HP has its own breaker, as does the furnace. I...

    HP has its own breaker, as does the furnace. I will have to see if he has the tstat wire running along side the supply voltage wiring. Visually the wire looks great but who knows if there is a kink...
  19. Thanks for the reply. All tstat wiring was new...

    Thanks for the reply. All tstat wiring was new when the hp was installed. He used 18 ga. Solid 5 conductor. Can it be sensitive to induced noise like if it runs parallel to household electrical...
  20. Hi jrbenny, have you had any luck?

    Hi jrbenny, have you had any luck?
  21. CTK04AB, GMVM960805CXAA, DSZC160361AE with...

    CTK04AB, GMVM960805CXAA, DSZC160361AE with PCBHR104 board installed last fall to fix no indoor blower error. Thanks!
  22. I agree 100% with your last statement. Just...

    I agree 100% with your last statement. Just makes me wonder and makes me want to set it at 1cph and watch it, then set it at 6cph and watch it again. Let me ask you a yes or no question that I...
  23. To boil down my question... is the outdoor unit...

    To boil down my question... is the outdoor unit cycling because I have the CPH still at factory default of 3, regardless of the call for cool not being satisfied for 45 minutes?
  24. Hi again, nothing in the comm circuit at all that...

    Hi again, nothing in the comm circuit at all that would add resistance like that. At least I am no longer getting "waiting for equipment" since the BV issue was corrected. Could this be something...
  25. Hi again, there are no trouble codes in the...

    Hi again, there are no trouble codes in the comfortnet diagnostics menu, no alert logs. According to the tstat everything is just fine. Status shows outdoor unit is on. I don't think the blower...
  26. Oh wtf. .. during a 45 minute continuous call...

    Oh wtf. .. during a 45 minute continuous call for cool the outdoor unit cycled 3 times. During these off times the t-stat is telling me low cool on fan automatic on in the comfortnet menu, no...
  27. Thank you sir, I expect I will know tomorrow. ...

    Thank you sir, I expect I will know tomorrow. It will be warm enough for ac but not super hot. The issues were more pronounced on lighter load days.
  28. Tech came out armed with communications...

    Tech came out armed with communications troubleshooting sheets that came directly from Goodman tech support. I understand exactly what he did, I guess I will try to be cryptic here.. Common is no...
  29. Well, ctk02 is now back in, going out of town...

    Well, ctk02 is now back in, going out of town and didn't want to leavey wife with a sketchy system, and it is running nearly nonstop on low stage which I expect on a day like today. Therefore my...
  30. Well, data lines not crossed. 4 wires between...

    Well, data lines not crossed. 4 wires between furnace and t stat. Comm wires only to HP. 40 VA trans at HP. Dip13 at furnace is off. Just can't see what I missed. Actually working fine today...
  31. I understand the rules, I know I crossed over to...

    I understand the rules, I know I crossed over to DIY on this one. Question: Have I missed something simple? The equipment manuals give comm dip switch instructions for ctk01,02 but not 03 or 04. ...
  32. Fall 2014. My tech had many conversations with...

    Fall 2014. My tech had many conversations with goodman for over a year then all of a sudden Goodman said they had a solution and sent a new board immediately.
  33. Thanks for the reply.. regarding faults.. ...

    Thanks for the reply.. regarding faults.. that's the point and I did not elaborate enough above there are NO faults in the comfortnet diagnostics. I have to think it has something to do with...
  34. Not reading faults. Just seeing the home screen ...

    Not reading faults. Just seeing the home screen read "cool on" while the condenser and indoor blower are off. The equipment might cycle 2 or 3 times during 1 call for cool. If near the end of the...
  35. Thanks. I wanted to be completely sure I...

    Thanks. I wanted to be completely sure I understood how it is supposed to work because something seems wrong. The condenser will shut off as well as the indoor blower (after the normal blower off...
  36. Thanks Jrbenny. 1) if set to 3cph will it force...

    Thanks Jrbenny. 1) if set to 3cph will it force 3 cycles even if the t stat has not been satisfied? 2) what effect does the staging setting of furnace back up heat (stage 1 and 2) have on a...
  37. I have 2 questions pertaining to this CTK04. 1)...

    I have 2 questions pertaining to this CTK04. 1) regarding cycles per hour, I assume that means the maximum it will cycle in an hour, not how many cycles it will force the system to run. To...
  38. thanks bald loonie! And jrbenny, thanks for the...

    thanks bald loonie! And jrbenny, thanks for the link.. but the installation guide you have linked me to is the very same one that I have that tells me to contact honeywell for more details! That's...
  39. Thanks.. there seems to be a lot of the prestige...

    Thanks.. there seems to be a lot of the prestige units, is there a model number that would be closest? Again, thanks.. and thanks for speaking English!
  40. goodman CTK04 is equivalent to which honeywell?

    This is extremely frustrating.. The installation guide for the CTK04 gives a brief summary of its programmable functions, and CLEARLY states to go to honeywell for details. I go to honeywell and I...
  41. They're on propane, I wonder if the conversion...

    They're on propane, I wonder if the conversion was done, and if so, if it was done correctly. I am on propane as well, bought a clothes dryer, had it delivered, guy was going to install it, so I...
  42. It leaked condensation when installed.. So...

    It leaked condensation when installed.. So assuming everything was done perfectly in the middle of summer except for a little leak that didn't show up until the heating season, cutting the exhaust...
  43. My wife's parents' house. 4 zone hot water...

    My wife's parents' house. 4 zone hot water through the floor heat. All kinds of interference with all that piping, can't turn off some of the valves without removing the lever and turning with a...
  44. hasn't worked right since new, now 6 years old

    Like the subject says. Pretty sad. Personally, I like the added transformer strapped to the vent pipe. I certainly don't know much about HVAC, but I know this aint good... 599231599241
  45. goodman modulating gas valve, communicating t-stat

    Hello all, I have a new in box, never used CTK02 t-stat, that was swapped out under warranty. Brand new. Since at this time I don't need heat or AC, I thought if I could sell this in a timely...
  46. Replies
    8
    Views
    741

    He's looking into it, will have an answer on...

    He's looking into it, will have an answer on Monday. I was trying to cover all my bases with the "selling on my own" question, and I think my guy was just trying to cover his butt if they don't let...
  47. Replies
    8
    Views
    741

    Thanks for the reply hvacvegas. So far has that...

    Thanks for the reply hvacvegas. So far has that CTK04 proven to be a reliable unit? My tech tells me he may only be able to swap the CTK02, so if I want the CTK04 I will have to buy it and try to...
  48. Replies
    8
    Views
    741

    Hello all, I looked at the the literature on the...

    Hello all, I looked at the the literature on the the CTK04, and it does add some features that I would like over the CTK02. But does the CTK04 still allow the same programming of the fan speeds, fan...
  49. Replies
    8
    Views
    741

    Thanks for the replies. What would I gain with...

    Thanks for the replies. What would I gain with the 04 or even the 03 over the 02?
  50. Replies
    8
    Views
    741

    upgrading t-stat advice.

    My current goodman CTK-02 is being replaced under warranty, due to a bad back up battery. (see other thread) However, I might be able to get partial credit for it and get a different t-stat. I wish...