  1. Circon Integration Upgrade to AX 3.7.106 from 3.2

    I upgraded a workstation and 4 Jace 545ís with extended memory from 3.2 to 3.7.106 with a brief stop at 3.4 system has 200+ Circon VAV 202 using .xml file Uh202as2. They ran fine on the old system...
  2. Replies
    5
    Views
    417

    Thanks Guys! We decided to bid it as if we were...

    Thanks Guys! We decided to bid it as if we were replacing the WS just in case. Sounds like we shouldn't have to, but nothing like a little CYA.
  3. Replies
    5
    Views
    417

    Just got out of prebid meeting license said...

    Just got out of prebid meeting license said
    <feature name="brand" accept.station.in="*" accept.station.out="*" accept.wb.out="*" brandId="FacExp" accept.wb.in="*"/>
    Locked? I'm thinking yes.
  4. Replies
    5
    Views
    417

    Talon Network Manager on FX Workstaion

    Anyone know any problems if I try to put a Talon Network Manager on an existing FX workstation and network?

    Licensing issues with workstation is main fear.
  5. Replies
    1
    Views
    815

    Andover Continuum to AX

    Guys,
    I have a school that has Andover Native BACnet controllers in 17 of the new classrooms. We just took over the rest of the school, ver. AX 3.6.31 and I am trying to talk to these controllers...
  6. Thread: KitControl ?

    by Hensman
    Replies
    8
    Views
    904

    We simply take the Schedule into a boolean select...

    We simply take the Schedule into a boolean select and define outputs of select.
  7. Replies
    24
    Views
    3,185

    Look at where the jobs are going to be. I drove...

    Look at where the jobs are going to be. I drove my own car for 1 year and quit the company. I got $600 per month + $.50 per mile over 500 in 2 week period. Not worth it put over 70K on my car, now...
  8. Replies
    1
    Views
    589

    Found it Sorry. The jumpers enable biasing...

    Found it Sorry. The jumpers enable biasing resistors and I was searching Biasing voltage. Need more coffee.
  9. Replies
    1
    Views
    589

    Jace Biasing doc's

    For whatever reason, I cannot find the documentation on how to configure the jumpers on J6 on a JACE 600 to apply biasing voltage to the RS-485 port. I have done it before but now canít find it...
  10. Replies
    17
    Views
    1,604

    Well said berg

    Well said berg
  11. Replies
    17
    Views
    1,604

    Create the input, then, as berg suggested, go to...

    Create the input, then, as berg suggested, go to define hardware and assign to input.

    And yes it is mandatory.
  12. Replies
    17
    Views
    1,604

    You have to have CCT

    You have to have CCT
  13. Replies
    5
    Views
    743

    If not do a search for .caf.module

    If not do a search for .caf.module
  14. Replies
    5
    Views
    743

    In CCT they are located C:\Documents and...

    In CCT they are located C:\Documents and Settings\All Users\Application Data\Johnson Controls\MetasysIII\CCT\UI\Custom Control Modules
  15. Replies
    13
    Views
    1,022

    Or it could be Duct static sensor location in...

    Or it could be Duct static sensor location in relation to return air path. Just a thought.
  16. Replies
    13
    Views
    1,022

    I have seen this once before and found that the...

    I have seen this once before and found that the return fan riser opening (Plenum Return) for the floor that the sensor was located on was right by the static sensor, with the return fan tracking the...
  17. Replies
    2
    Views
    606

    Sorry for the delay been buried with service...

    Sorry for the delay been buried with service calls. The controllers are not that old maybe 6 months. Itís a Steafa Jace. What points should I be looking for? I donít see anything that would...
  18. Replies
    2
    Views
    606

    JCI LX-VAV Graphics OVRD

    I have a job with 2 JCI LX ĖVAV controllers on a Jace (AX) along with Circon, and Steafa VAVís. The contractor that put the LX-VAVís on the system did not give the user the ability to override the...
  19. Replies
    3
    Views
    495

    Found the issue. I had them defined as network...

    Found the issue. I had them defined as network setpt's. Changed them to Network Inputs and they are exposed for connection. Thanks.
  20. Replies
    3
    Views
    495

    Bacnet Spyder NV problem

    I have a small stand alone job with three BACnet Spyders, one for AHU, and the other two have 3 reheat zones each. I am trying to keep this stand alone and the only thing that needs communicated are...
  21. Replies
    20
    Views
    1,335

    1. What percentages of jobs have included Modbus?...

    1. What percentages of jobs have included Modbus?
    0%


    2. What percentages of jobs have included Lonworks?
    25%

    3. What percentages of jobs have included BACnet?
    75%
  22. Thread: Smart 2 on AX

    by Hensman
    Replies
    2
    Views
    717

    Thanks that’s what I was thinking but could not...

    Thanks that’s what I was thinking but could not remember for sure.
  23. Replies
    16
    Views
    2,142

    I put the freeprog on and didnít have any issues....

    I put the freeprog on and didnít have any issues. I put the .jar files on the Jace and did nothing in the workstation but pull the points up. They canít use the wizards from the workstation I have...
  24. Thread: Smart 2 on AX

    by Hensman
    Replies
    2
    Views
    717

    Smart 2 on AX

    Has anyone successfully integrated to a Staefa Smart 2? I did it in R2 when with Staefa rep. but have not in AX. Iím just starting to search for drivers, .jar files, and a communications gateway....
  25. Replies
    16
    Views
    2,142

    I'm putting a LX 300 on a Steafa Jace as soon as...

    I'm putting a LX 300 on a Steafa Jace as soon as it comes in I will let you know if there are any issues.
  26. Replies
    16
    Views
    2,142

    I just looked up what I had on my Jace that I...

    I just looked up what I had on my Jace that I upgraded the 500.
    Ax 3.2.16
    Bcs 2.7.1
    dcDevices 2.7.1
    dcMain 2.7.1
    lonDistech 3.99.1
    lonworks 3.2.20
  27. Replies
    16
    Views
    2,142

    I will see if I can get on tonight I do not think...

    I will see if I can get on tonight I do not think I upgraded the .dist I think I just added the modules required for .gfx. I just added two LX VAV's (Yes I now work for a Johnson ABCS) to a Staefa...
  28. Replies
    16
    Views
    2,142

    Not so much!

    Not so much!
  29. Replies
    16
    Views
    2,142

    You should just pull out nvi1 and rename it. The...

    You should just pull out nvi1 and rename it. The name from the block/or slot(In C+) does not transfer.

    I looked at a job that has a different converted 500 on it and it was v3.2.22. You can put...
  30. Replies
    4
    Views
    658

    Yes that does do it good to know never touched...

    Yes that does do it good to know never touched that account before. THANK YOU!
  31. Replies
    4
    Views
    658

    Yes, it is enabled will that do it?

    Yes, it is enabled will that do it?
  32. Replies
    4
    Views
    658

    Skipping Login page on WEBs 600

    I have a sight with a Honeywell WEBs 600 installed and when using I.E. I type in the IP the browser skips the login page and goes straight to the Home page. Would not be bad but is a public IP. If...
  33. Replies
    16
    Views
    2,142

    My bad looked at that job and it was 3.4

    My bad looked at that job and it was 3.4
  34. Replies
    4
    Views
    752

    History Grouping AX 3.5

    Anyone used the History Grouping in 3.5? Whatís the trick?
  35. Replies
    16
    Views
    2,142

    I agree. mux all your DI & DO's and use nvi's. ...

    I agree. mux all your DI & DO's and use nvi's. Never had any luck with constants in .gfx.

    I converted some 500's to .gfx in 3.2.22 but that was a while back.
  36. Replies
    3
    Views
    747

    They used to be part of Larson and Binkley a KC...

    They used to be part of Larson and Binkley a KC engineering firm until 2 yrs ago. Had to deal with them a few times, but that was 5+yrs ago know nothing about there Jace's. they used Vykon when I...
  37. Replies
    10
    Views
    1,585

    I have been using this setup in the last couple...

    I have been using this setup in the last couple mechanical rooms that I have done. In the Tridium Literature it states that the power for Jace and I/O need to be separated. I use a 40VA transformer...
  38. Replies
    5
    Views
    591

    Staefa controllers do not use thermistors. They...

    Staefa controllers do not use thermistors. They are T-30 sensors that I believe are no longer manufactured. That is if they are SM-2 controllers if they are Klimo they use a different sensor. The...
  39. Replies
    1
    Views
    517

    Circon on Staefa Jace

    I have been called in by the owner to look at a Staefa system that integrated to existing Circon controls (VAV). I have around 120 Circon VAVís and maybe 30 Predators (VAV) plus RTU's and boilers...
  40. Replies
    3
    Views
    496

    Not sure what you want , if your looking for a...

    Not sure what you want , if your looking for a "Distech ECP VAV" controller program look on their web sight the one I'm using came from tech support so you could call them.
  41. Replies
    2
    Views
    834

    Trane lon interface

    I am trying to use a Jace and pull points out of a Trane OA unit with DA control and the points that come out using the lnml file are not making sense. I am using lnml file MP580P335101 and the...
  42. Controls contractor, tried to get the company to...

    Controls contractor, tried to get the company to supply them but they did not want any part of it. They said they use Dreager Gas System products but all I found was hand held devices made by them.
  43. Oil, not easy to find am getting ready to dig...

    Oil, not easy to find am getting ready to dig hard today.
  44. Hydrogen Sulfide and Hydrogen Flouride sensors

    I am engineering a job that I have to monitor OA intake for Hydrogen Sulfide and Hydrogen Flouride. Has anyone had good luck with a certain brand of duct sensor?