    We all like a good mystery. You're gonna want to...

    We all like a good mystery. You're gonna want to do a performance curve on that compressor. There may be some internal damage that's cutting the capacity.
  2. Replies
    63
    Views
    16,412

    The first thing I thought of was this equipment...

    The first thing I thought of was this equipment may be undersized and maybe wasn't cutting it on a really hot day. May have just been loaded. Running water over the condenser increased capacity and...
  3. Replies
    63
    Views
    16,412

    It this the first really hot day over there?

    It this the first really hot day over there?
  4. Replies
    63
    Views
    16,412

    You have to remember though with a warm box and...

    You have to remember though with a warm box and high suction pressure you're going to be running higher than normal head and your condenser may not be in the perfect shape as it was new.


    How old...
  5. Replies
    63
    Views
    16,412

    What condensing pressure/temperature would you...

    What condensing pressure/temperature would you expect to see with a 98* ambient and a warm box?
  6. Replies
    63
    Views
    16,412

    I don't understand why torch the reciever? With a...

    I don't understand why torch the reciever? With a 98* ambient 300psi would give you a condensing temp of about 118* with 404a. He said he had a full sight glass.
  7. Replies
    63
    Views
    16,412

    Couple things I see... The 300psi head looks...

    Couple things I see... The 300psi head looks about normal for a 98* day. The suction pressure is high for a 20* box. It's hard to say what exactly is going on there. If the txv wasn't feeding or the...