    I believe this is due to your COV...

    I believe this is due to your COV (change-of-value) settings. Let's assume a temperature sensor has a COV of 1. If the temperature changes from 72.0 to 72.5 that will not be reported to Insight...
  2. Replies
    6
    Views
    1,659

    Some more info that may be helpful to the experts...

    Some more info that may be helpful to the experts out there....

    I was looking through System Activity Log and noticed that some of my COMM.FAIL alarms come in right after a failed trend collection...
  3. Replies
    6
    Views
    1,659

    Siemens MBC communication problems

    Hello,

    Long time reader - first time poster.

    I have a Siemens BACnet MBC running firmware MBCE V3.0 BACnet 4.2g. This MBC is an open processor only, gathering data via FLN1 from a Trane Summit...