  4. Thread: trane rtac

    by bku46
    Replies
    14
    Views
    2,646

    Oil over charge will not cause his problem, had...

    Oil over charge will not cause his problem, had several units with oil over charge, unit trips on low refrig level, also tev goes open 100% and flashing in the sight glass. Been there and done that.
  5. Thread: trane rtac

    by bku46
    Replies
    14
    Views
    2,646

    There are no filters on a RTAC, only oil filter...

    There are no filters on a RTAC, only oil filter on compressor. Set your low refrig cutout to 28.0 That is the proper setpt for water. Make sure the chiller is controlling the pump, if pump not...
  6. Thread: trane rtac

    by bku46
    Replies
    14
    Views
    2,646

    Your approach temp should be 5 check your...

    Your approach temp should be 5 check your condenser superheat, should be around 15 degrees, is the sight glass flashing? What is the evap sat temp? what is your suction press.?
  7. Thread: trane rtac

    by bku46
    Replies
    14
    Views
    2,646

    Is this a water or glycol system? What is your...

    Is this a water or glycol system? What is your leaving water stpt? What is your approach temp? what is your superheat? What is the current avg % at start? There are many factors to look at to resolve...
  8. Replies
    8
    Views
    997

    You must get the Trane sensor, do it right...

    You must get the Trane sensor, do it right please, dont basterize another Trane unit.
  9. Replies
    24
    Views
    2,263

    JTRICOR Can you spell Varitrac? daaa I know you...

    JTRICOR
    Can you spell Varitrac? daaa I know you can use old hyper term, but the guy has no laptop, daaaa maybe you can send him yours.
  10. Replies
    19
    Views
    3,142

    Before you go off on a tangent, First did you put...

    Before you go off on a tangent, First did you put gauges on the unit? monitor the compressor amps at start and after? Do the common sense things so you can see what is causing the trips, Check you...
  11. Replies
    24
    Views
    2,263

    Well, it would be great if you had the Tracker...

    Well, it would be great if you had the Tracker software and a laptop, but you can go thru the menues. I would first run the unit thru test mode in make sure everything stages on. Then I would review...
  12. Replies
    38
    Views
    3,527

    Whatever, Thats why I make the big bucks and you...

    Whatever, Thats why I make the big bucks and you dont.
  13. Replies
    38
    Views
    3,527

    I gave you the conventional stat wire...

    I gave you the conventional stat wire terminations jack ass I realize that. I could give you the proper terminations for the Baysensor but your a ahole and you can figure it out yourself.
  14. Replies
    4
    Views
    1,275

    you should see all active and history diagnostics...

    you should see all active and history diagnostics from the display, unless its a auto reset diagnostic like flow loss.
  15. Replies
    38
    Views
    3,527

    Let me tell you want a be mechanics something, I...

    Let me tell you want a be mechanics something, I do know my **** and thats why I make 38.00 per hr. I installed many of these Trane stats with no problem, In fact I work for Trane. I get you guys all...
  16. Replies
    38
    Views
    3,527

    I hope the customer isnt getting billed for your...

    I hope the customer isnt getting billed for your in experience. What would you do if you had a real problem, Maybe you should just call a Trane tech next time.
  17. Replies
    38
    Views
    3,527

    Like I said, if you read the info that comes with...

    Like I said, if you read the info that comes with the stat and follow the directions I think any ass can figure it out but some guys cant read.
  18. Replies
    38
    Views
    3,527

    OK, Listen and listen good, write it down. First...

    OK, Listen and listen good, write it down. First run the unit thru test mode, that will rule out any problem with the UCP, ok now if that checks out, then here are your LTB1 connections as follows:...
  19. Thread: What's this POS?

    by bku46
    Replies
    7
    Views
    1,168

    Jackson Church

    Jackson Church
  20. Replies
    38
    Views
    3,527

    ultatech, I do nkow it all.

    ultatech, I do nkow it all.
  21. Replies
    7
    Views
    1,377

    There are restricters inside the cap tubes where...

    There are restricters inside the cap tubes where it enters the evap, if you look close you can see them, Try heating that spot with a tourch and hope for the best.
  22. Replies
    38
    Views
    3,527

    Maybe you should read the paper that came with...

    Maybe you should read the paper that came with the tstat or did you wipe your ass with it.
  23. Replies
    20
    Views
    1,953

    Dale, go get some training on a thing called...

    Dale, go get some training on a thing called super heat and sub cooling, maybe your problem will go away.
  24. Replies
    7
    Views
    1,402

    Try trouble shooting the unit. Isolate the...

    Try trouble shooting the unit. Isolate the problem and fix it. Sometimes you really have to think in this bussiness.
  25. Replies
    7
    Views
    1,377

    Do yourself a favor, replace the evap coil, had...

    Do yourself a favor, replace the evap coil, had problems with restricted cap tubes, tried heating them up to melt waxing but to no avail, replaced the evap and running like new.
  26. Replies
    5
    Views
    1,068

    As long as its rated for the tonage and dont mix...

    As long as its rated for the tonage and dont mix match, use the right coil with the proper valve.
  27. Replies
    3
    Views
    893

    The right way to evacuate a system is by microns,...

    The right way to evacuate a system is by microns, get yourself a good micron meter and pull your vaccume to a min of 500 or lower. Let stand for a min of 30 mins and you are good to go.
  28. Thread: roof top unit

    by bku46
    Replies
    6
    Views
    956

    Check to see if there is a fan press or temp...

    Check to see if there is a fan press or temp control that makes your condenser fan. trace the wires or if the print is readable check it, It may be a after thought also which was done and not on the...
  29. Well its obvious you have a slugging problem, do...

    Well its obvious you have a slugging problem, do you know much about superheat and subcooling, oil return and level? Thats what you need to focus on and if you get that set up maybe you wont have...
  30. Replies
    10
    Views
    1,318

    ZeroCool, I guess you havent been in the HVAC...

    ZeroCool, I guess you havent been in the HVAC field too long, You dont have a clue of what your talking about. Spot coolers have been around a long time and never caused any problems that you claim....
  31. Replies
    10
    Views
    1,318

    Tell your contractor he full of crap, I have many...

    Tell your contractor he full of crap, I have many spot coolers in operation at various sites doing just what you want. Spot coolers are your best option.
  32. Replies
    1
    Views
    667

    Sounds like you may have some bad wire...

    Sounds like you may have some bad wire connections in the daisy chain.
  33. Replies
    3
    Views
    623

    Evap condensers, pump should start when cooling...

    Evap condensers, pump should start when cooling is requested, Fans will cycle on sump temp iether on or off or with drive if equipped.
  34. Thread: walk in frezer

    by bku46
    Replies
    2
    Views
    717

    All three, ice may form where gasket is missing,...

    All three, ice may form where gasket is missing, added humidity will enter box and cause more ice to form on evap, and gasket leakage will add load to box causing it to run more. How much leakage do...
  35. Replies
    1
    Views
    822

    You must know how to write CPL and only a Trane...

    You must know how to write CPL and only a Trane BAS tech will be able to write a program to do what you want. I suggest you call Trane BAS dept for help.
  36. Replies
    10
    Views
    964

    Are the units equipped with HI touch pad boards?...

    Are the units equipped with HI touch pad boards? If so you can offset the enthalpy thru set up menue. If not and every thing is done thru Summit, then try setting the unit up for referance humidity...
  37. Replies
    10
    Views
    964

    Well then I cant see how we can be over...

    Well then I cant see how we can be over pressurizing unless the dampers themselfs are not stroking. Are there returns in these area,s?? One other note, are you doing morning warm up, this will drive...
  38. Replies
    10
    Views
    964

    What problem are you having with the doors ?? is...

    What problem are you having with the doors ?? is the bld over pressurized or negitive ?? this is not a Tracer problem, check your exh. fan if equipped or relief dampers, also your bld pressure set...
  39. Replies
    6
    Views
    1,336

    Use your common sense, superheat and sub cooling...

    Use your common sense, superheat and sub cooling will get your charge right.
  40. Thread: Head Pressure

    by bku46
    Replies
    11
    Views
    1,119

    Check all condender fans for operation, make sure...

    Check all condender fans for operation, make sure they are drawing amps and rotation correct. Check condenser coil for clogging, may need a good power wash, last may be over charged.
  41. Thread: Evac. level ?

    by bku46
    Replies
    15
    Views
    1,493

    Check your hoses and all connections, I isolate...

    Check your hoses and all connections, I isolate my pump and see if it holds a vaccume first, then I open to my system and see if it rises, Im not to crazy about these micron meters, they dont seem to...
  42. Replies
    25
    Views
    2,234

    Did you install a trap?? Is it possible the water...

    Did you install a trap?? Is it possible the water is comming from somewhere else, leaking above on the duct work. whats abouve unit??
  43. Replies
    9
    Views
    2,108

    The fact is, he had no right switching the...

    The fact is, he had no right switching the equipment without your consent. I would be very pissed off if I went and bought a Chevy and when I went to pick it up. a ford was sitting there. Legally,...
  44. Replies
    89
    Views
    16,031

    You can get all the training, software and Info...

    You can get all the training, software and Info from Trane, but its gonna cost you, nothing is free in this life. It may just be cheaper to call Trane and have a qualified tech come out and help you.
  45. Thread: Trane tonnages

    by bku46
    Replies
    3
    Views
    838

    correction, 5 ton and 10 ton.

    correction, 5 ton and 10 ton.
  46. Replies
    4
    Views
    1,001

    Does the AHU have a heat coil ? a freeze stat, a...

    Does the AHU have a heat coil ? a freeze stat, a controller to open heat valve on low temp? If there is no way to protect the coil other than relying on a outside damper to stay shut or the fan not...
  47. Thread: Trane tonnages

    by bku46
    Replies
    3
    Views
    838

    50 ton 100 ton

    50 ton 100 ton
  48. Replies
    35
    Views
    2,978

    I have been in the field myself for 20 yrs John...

    I have been in the field myself for 20 yrs John and I agree with you but it dosent take 30 yrs of experience to replace filters, belts and lube, thats what Im talking about. They can pay sombody to...
  49. Thread: Intellipak

    by bku46
    Replies
    11
    Views
    1,334

    What you have is a one circut 2 compressors in...

    What you have is a one circut 2 compressors in tandum A and B You have one liq sel. valve per circut. When cooling is required Comp A starts or B if lead lag enabled. Liq sel is energized, if load is...
  50. Replies
    35
    Views
    2,978

    There are no laws in place to stop anyone who is...

    There are no laws in place to stop anyone who is certified to handle refrigerant, to go out and call himself a HVAC tech or work in the field for that matter. Until we become licensed like...
Results 1 to 50 of 169
Page 1 of 4 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event