    If i read what you want right, a BCU will not...

    If i read what you want right, a BCU will not talk BACnet MSTP. So you can not interface directly to the BCU that way. You can do BACnet/IP with a BCU.
  2. Replies
    9
    Views
    275

    I dont remember exactly off hand but it should be...

    I dont remember exactly off hand but it should be something like Site: School, BCU-1 Chiller 1, High Head Pressure in alarm and a date stamp

    I believe it gives you most of what you see in the...
  3. Replies
    9
    Views
    275

    You use outlook 2007 with a valid account made in...

    You use outlook 2007 with a valid account made in it that can send out emails. You must have Summit and Outlook running at all times for emails to be sent. You can only define one alarm class to be...
  4. Replies
    32
    Views
    1,313

    Can you find that board with the neuron id and...

    Can you find that board with the neuron id and isolate it from the link and see if your lon problems go away? Almost looks like you have a bad board that is flooding the link.
  5. Replies
    5
    Views
    331

    Go to Tracer ES Home, then select all buildings,...

    Go to Tracer ES Home, then select all buildings, next page check mark the building you want to delete and hit advanced, next page hit delete
  6. Replies
    1
    Views
    215

    They are called "Common Boxes". When adding vavs...

    They are called "Common Boxes". When adding vavs to the VAS you set up how many common boxes you want to keep occupied during start/stop of the RTU. You can go to vas and then members tab and the...
  7. You might try creating a new area. See if its...

    You might try creating a new area. See if its still grayed. Make sure you have all security rights you need also. When upgrading from that old user privileges changed.

    If you try all this and...
  8. Have you isolated anything out? Have you got on...

    Have you isolated anything out? Have you got on the mstp link and seen how it responds? Is it slow?

    Is the trane controller and the siemens router on the same subnet? Are they on a customers...
  9. Are you integrating into a Tracer SC directly on...

    Are you integrating into a Tracer SC directly on the mstp link or is this a router that is converting over to bacnet/IP and into a SC or BCU? Sorry i am not fimilar with the ATEC.
  10. Replies
    11
    Views
    344

    I 100% agree with qtip here. That is their job...

    I 100% agree with qtip here. That is their job and they need to get the software and input it themselves. Especially since its free as stated earlier. I personally have never inputted values for a...
  11. Replies
    11
    Views
    344

    Air Flow Gain AV-18 Gain set when air balancing ...

    Air Flow Gain AV-18 Gain set when air balancing
    Factory default 1.0 Range 0.000 to 2.000
  12. Replies
    11
    Views
    643

    Its based on box type and if it has a flow ring...

    Its based on box type and if it has a flow ring and transducer. Then if that is setup correct it has to be reading flow. It will switch between the modes automatically based on if it successfully...
  13. Replies
    3
    Views
    336

    Not sure if JCI does it the same way, but do you...

    Not sure if JCI does it the same way, but do you have the BACnet user able to perform writes? Maybe make it a super user to test.

    Also when exporting points did you allow anything in the 1-16...
  14. Replies
    4
    Views
    212

    The SC is a native BACnet device. So anything...

    The SC is a native BACnet device. So anything brought into the panel will be available to you to pull in via IP. We do not have to build a point database like we use to in the old BCUs. If you...
  15. Replies
    9
    Views
    537

    You can make the BAS setpoint adjustment at the...

    You can make the BAS setpoint adjustment at the vav itself. You can also make global bas setpoint adjustments from the spaces page depending on what version of SC you are running.
  16. Even if you upgrade to a bridge/SC you will still...

    Even if you upgrade to a bridge/SC you will still need the CM4.1 in place.
  17. Replies
    3
    Views
    353

    I would say that almost all bindings are...

    I would say that almost all bindings are typically done in a BCU. So once you remove the BCU the bindings are lost. There is two domains that exist, an A and B. Trane by default commissions both...
  18. Replies
    13
    Views
    416

    Rover discovers the link on a ZL domain. If you...

    Rover discovers the link on a ZL domain. If you set the Jace up to a specific domain and set domain B to not used then rover will not discover it. You can either have the Jace set one of the...
  19. Replies
    15
    Views
    761

    The repeater can be anywhere in the link long as...

    The repeater can be anywhere in the link long as it leaves <60 on one side. So it may be physically anywhere. Trane repeaters also do not show up on a scan or in the BCU. So you would not see it...
  20. Replies
    4
    Views
    390

    Also check what voltage you read with it the...

    Also check what voltage you read with it the wires unhooked. If it still reads 13 unwired then not a vsd issue.
  21. Replies
    9
    Views
    537

    Each user preference can be set to display what...

    Each user preference can be set to display what they want. So log in as the user and then go to preferences and select display units you want to see.
  22. The bcu can reside on the network in the ethernet...

    The bcu can reside on the network in the ethernet mode. Just plug the BCU and the PC both into a switch. Ethernet does not cross subnets so if for some reason the network you plugged the bcu into...
  23. Replies
    2
    Views
    360

    Are you running a sql database setup on a larger...

    Are you running a sql database setup on a larger site?
  24. Do a clear ram and reset on the BCU. I would...

    Do a clear ram and reset on the BCU. I would start there.

    It will lose all overrides so run a report before hand to save those and then re-override the points after it comes up.
  25. Replies
    8
    Views
    471

    Summit should be the one that puts the unit into...

    Summit should be the one that puts the unit into morning warmup if configured correctly. The vav and the rtu needs to be properly setup in area and vas and scheduling to allow it to happen.

    I do...