    MKnyc- I agree, the RTAA needs to start the pump...

    MKnyc- I agree, the RTAA needs to start the pump and it does both start/stop of the pump and lets the pump run for 5 minutes after chiller is disabled. I use the remote contacts on the RTAA board to...
  2. Replies
    51
    Views
    6,960

    Graham, Yeah last October was about the last...

    Graham,
    Yeah last October was about the last time I had time to really look at this problem.
  3. Replies
    51
    Views
    6,960

    Chiller, The RTAA onboard computer controls the...

    Chiller,
    The RTAA onboard computer controls the pump. I installed a pressure differential switch which is monitored by the BAS for proof of pump before the chiller is enabled. The pump runs for 5...
  4. Replies
    51
    Views
    6,960

    Thanks my friend :)

    Thanks my friend :)
  5. Replies
    51
    Views
    6,960

    Freonrick-Hadn't thought of that one yet, thanks...

    Freonrick-Hadn't thought of that one yet, thanks I'll include this in my troubleshooting.
  6. Replies
    51
    Views
    6,960

    rtaa trips

    One thing I've learned and that's that this can be tricky problem on a RTAA.
    My stage 2 runs perfect. But stage 1 constantly trips on "low saturated refrigerant temperature". I've ran the EXV...
  7. Thread: VFD training

    by koolncali
    Replies
    8
    Views
    1,550

    chillerguy- It used to be that when I needed a...

    chillerguy-
    It used to be that when I needed a vfd replaced I would call for the ABB drive (we are sticking to ABB) factory rep and coordinated his visit with the EMS rep. But I stuck my neck out...
  8. Replies
    27
    Views
    1,988

    jayguy- thanks for the word of encouragement, I...

    jayguy- thanks for the word of encouragement, I just need to get back into the habit of double checking everything.
  9. Replies
    27
    Views
    1,988

    Thanks fcs

    Thanks fcs
  10. Replies
    27
    Views
    1,988

    Graham- thanks for trying to get me to think....

    Graham- thanks for trying to get me to think. sometimes i have to be knocked over the head :).

    And thanks to everybody who tried to help.

    It's really a great feeling that there are so many...
  11. Replies
    27
    Views
    1,988

    jayguy- Talk about troubleshooting from afar!...

    jayguy-

    Talk about troubleshooting from afar! Let me tell you that you hit the nail on the head! I read your post then I went and did what I should have done (and normally do) and double checked...
  12. Replies
    27
    Views
    1,988

    chiller- another interesting possibiliy. first...

    chiller- another interesting possibiliy. first I'm going to concentrate on the sensors I replaced since the new alarm started after I replaced them. Then I'll have to look elsewhere if necessary....
  13. Replies
    27
    Views
    1,988

    Psycho- this one is going off on low pressure...

    Psycho- this one is going off on low pressure cutout but I realize that temperature is being converted to a pressure reading so it's all related. I'll keep in mind your input about the solenoids.
  14. Replies
    27
    Views
    1,988

    Graham- Thanks for the great advice, I really do...

    Graham- Thanks for the great advice, I really do appreciate the input from you and all the other guys here.

    Yeah with the discrepancies of readings between my gauges and the UCM readings it looks...
  15. Replies
    27
    Views
    1,988

    Graham- Thanks for the input. My chiller (I work...

    Graham- Thanks for the input. My chiller (I work at a jr college) is an RTAA125 and it does have a low pressure switch for each compressor (2). Looks like 12vdc comes out of the module, passes...
  16. Replies
    27
    Views
    1,988

    Ok jayguy I see what you're saying is that if the...

    Ok jayguy I see what you're saying is that if the pressures are not actually what the UCM is reading and telling the low pressure cutout to open, then it can throw it out of balance and maybe cause...
  17. Replies
    27
    Views
    1,988

    Plugger I ran a check on circuit #1 EXV at the...

    Plugger I ran a check on circuit #1 EXV at the module and it ran the check ok.
  18. Replies
    27
    Views
    1,988

    Graham- it's a RTAA125 chiller. I replaced the...

    Graham- it's a RTAA125 chiller. I replaced the "saturated evaporator sensor" and the "suction temp sensor" because the chiller was tripping daily on "low saturated temperature". I ran the...
  19. Replies
    27
    Views
    1,988

    Maxpower- no it's a packaged chiller sitting on a...

    Maxpower- no it's a packaged chiller sitting on a rack. It has two low pressure switches at the outlet of the chiller barrel.
  20. Replies
    27
    Views
    1,988

    RTAA trips on Low Pressure Cutout

    I need help from anyone who is knowledgeable on Trane RTAA chillers. I previously had a thread because my RTAA chiller circuit 1 was shutting off on "low saturated evap temperature". I replaced both...
  21. Replies
    51
    Views
    6,960

    Excellent advice Paceleader. I will check for...

    Excellent advice Paceleader. I will check for proper load/unloading of the compressor at the conditions you mentioned.
  22. Replies
    51
    Views
    6,960

    Yeah there is i guess i'm in luck.:cool:

    Yeah there is i guess i'm in luck.:cool:
  23. Replies
    51
    Views
    6,960

    Bowhunter- Thanks for the info now I just have...

    Bowhunter-

    Thanks for the info now I just have to see where I can get the part.
  24. Replies
    51
    Views
    6,960

    Cntrl- Thanks I'll check the manual for sh...

    Cntrl-
    Thanks I'll check the manual for sh adjustment. It's a temporary chiller set-up with fire hoses and primary flow only (one pump). The flow is constant. I hadn't thought about flow as an issue...
  25. Replies
    51
    Views
    6,960

    Bowhunter- Thanks for that advice. This morning...

    Bowhunter-
    Thanks for that advice. This morning circuit #1 was in a latched fault "low saturated refrigerant temperature" alarm once again. I took some readings on ciruit #1 while still in alarm and...